Operating Instructions Levelflex M FMP40 Guided Level-Radar BA00244F/00/EN/13.10 71120272 Valid as of software version: 01.04.zz...
Page 2
Levelflex M FMP40 FOUNDATION Fieldbus Brief Operating Instructions Levelflex M - Brief operating instructions KA189F/00/a2/03.07 52012501 Contrast: measured value dist./ meas value Group selection basic setup tank medium process empty full dist./ check range of start properties property cond. calibr.
Safety instructions Levelflex M FMP40 FOUNDATION Fieldbus Safety instructions Designated use The Levelflex M is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry. Installation, commissioning and operation The Levelflex M has been designed to operate safely in accordance with current technical, safety and EU standards.
Levelflex M FMP40 FOUNDATION Fieldbus Safety instructions Notes on safety conventions and symbols In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
Dat./Insp.: D01301-A Reference to additional safety-relevant documentation L00-FMP4xxxx-18-00-00-en-001 Information on the nameplate of the Levelflex M FMP40 2.1.2 Ordering structure This overview does not mark options which are mutually exclusive. Approval: A Non-hazardous area Non-hazardous area, WHG...
Page 7
Levelflex M FMP40 FOUNDATION Fieldbus Identification Probe: A Rope 4mm / 1/6", mainly liquid Rope 6mm / 1/4", solid H Rope 6mm / 1/4", PA > steel, solid, T = 100°C / 212°F Rod 6mm, liquid Rod 12mm, liquid K Rod 16mm, mainly liquid Coax, liquid Special version, TSP-No.
Page 8
Identification Levelflex M FMP40 FOUNDATION Fieldbus Process Connection: DN100 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527) DN150 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C) DN150 PN10/16, AlloyC22 >316L flange EN1092-1 (DIN2527) DN200 PN16 B1, 316L flange EN1092-1 (DIN2527 C) Thread ISO228 G3/4, 316L...
Page 9
Levelflex M FMP40 FOUNDATION Fieldbus Identification Housing; Cable Entry: F23 316L IP68; gland M20 F23 316L IP68; thread G1/2 F23 316L IP68; thread NPT1/2 F23 316L IP68; plug M12 F23 316L IP68; plug 7/8" Special version, TSP-No. to be spec.
The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Mounting Quick installation guide Mounting with threaded boss F12/F23 or T12 housing AF 60 1½" ¾" AF 50 Caution! Use only the threaded boss F12/F23 or T12 housing Turn housing To simplify access to the...
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Incoming acceptance, transport, storage 3.2.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Installation 3.4.1 Mounting kit For the mounting, you will require the following tool: • The tool for flange mounting • For the mounting of threaded connection: 60 mm Open-end spanner for 1½", 50 mm Open-end spanner for ¾"...
Page 16
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Coax probes The shortening is necessary if the distance to the container floor or outlet cone is less than 10 mm. Coax probes can be shortened max. 80 mm from the end. They have centering units inside which fix the rod centrally in the pipe.
Page 17
Levelflex M FMP40 FOUNDATION Fieldbus Mounting 3.4.4 Mounting rope probes in a partially full silo It is not always possible to empty a silo which is already in operation. Because the probe can be turned in the threaded boss, it can also be mounted when the silo is only partially filled. In order to...
Page 18
Mounting Levelflex M FMP40 FOUNDATION Fieldbus 3.4.5 Engineering hints for level measurement in bulk solids and fluids • Normally, rope probes should be used for bulk solids, rod probes are only suitable for short measuring ranges up to approx. 2 m in bulk solids. This applies above all to applications in which the probe is installed laterally at an angle and for light and pourable bulk solids.
Page 19
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Other installations • Select the mounting location such that the distance to internals (5) (e.g. limit switch, struts) > 300 mm over the entire length of the probe, also during operation. • Probe must within the measuring span not touch any internals during operation.
Page 20
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Type of probe installation • Probes are mounted to the process connection with threaded connections or flanges and are usually also secured with these. If during this installation there is the danger that the probe end moves so much that it touches the tank floor or cone at times, the probe must, if necessary, be shortened and fixed down.
Page 21
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Supporting probes against warping For WHG approval: For probe lengths ≥ 3 m a support is required (see figure). For GL/ABS approval: Rod probes ∅ 16 mm ≤ 1 m permissible, Rod probes ∅ 6 mm not permissible.
Page 22
100 mm 100 mm metal metal tube ø80...150 mm Extension rod / Centering (see accessories) L00-FMP4xxxx-17-00-00-en-008 Strong dust generation can lead to build-up behind the center washer. This can cause an interference signal. For other installation possibilities please contact Endress+Hauser. Endress+Hauser...
Page 23
Levelflex M FMP40 FOUNDATION Fieldbus Mounting 3.4.7 Installation in bulk solid silos Tensile load Bulk solids exert tensile forces on rope probes whose height increases with: • the length of the probe, i.e. max. cover, • the bulk density of the product, •...
Page 24
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Since the tensile forces are also heavily dependent on the viscosity of the product, a higher safety factor is necessary for highly viscous products and if there is a risk of cornice build-up. In critical cases it is better to use a 6 mm rope instead of a 4 mm one.
Page 25
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Installation in underground tanks Use coax probe for nozzles with large diameters in order to avoid reflections at the nozzle wall. L00-FMP4xxxx-17-00-00-yy-022 Measurement in corrosive fluids For measurement in corrosive liquids use Levelflex M FMP41C. When using plastic tanks it is also possible to mount the probe on the outside of the tank (Installation instructions, →...
Page 26
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Mounting Location • Recommended distance B wall-mounted rope probe: ~1/6 to 1/4 of the container diameter. • Not central (2) in metallic tanks. • Not in the filling curtain (3). • Please order the probe length such that it ends approx.
Page 27
Levelflex M FMP40 FOUNDATION Fieldbus Mounting 3.4.9 Notes on special installation situations Welding the probe into the vessel " Caution! Before welding the probe into the vessel, it must be grounded by a low-resistive connection. If this is not possible, the electronics as well as the HF module must be disconnected. Otherwise the electronics may be damaged.
Page 28
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Installation from the side • If installation from above is not possible, the Levelflex can also be mounted from the side. • In this case, always fix the rope probe ("Fixing rope probe", → ä 27).
Page 29
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Installation in nozzles > 150 mm high If, when installing probes in nozzles DN40 (1½" )to 250 (10") with nozzle height of DN50 (2") DN80 (3") > 150 mm (6"), the probe could touch the lower DN150 (6")
Page 30
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Installing FMP40 with heat insulation • If process temperatures are high, FMP40 must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection. • The insulation may not exceed beyond the points labelled "MAX" in the drawing.
Page 31
Levelflex M FMP40 FOUNDATION Fieldbus Mounting Installation for difficult to access process connections For tight spaces or temperatures above that in the graphic, the electronics housing can be ordered with distance pipe or connecting cable (seperate housing). Installation with distance pipe When installing, please observe the installation instructions (→...
Page 32
Mounting Levelflex M FMP40 FOUNDATION Fieldbus Installation with remote electronic • Wall and pipe bracket is contained in the scope of delivery and is already mounted • Follow installation instructions, → ä 18 • Mount housing on a wall or pipe as shown in the diagram...
Levelflex M FMP40 FOUNDATION Fieldbus Mounting 3.4.10 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
Wiring Levelflex M FMP40 FOUNDATION Fieldbus Wiring Quick wiring guide Wiring in F12/F23 housing " Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the FOUNDATION Fieldbus Caution! ENDRESS+HAUSER Made in Germany standard and the desired safety concept.
Page 35
Levelflex M FMP40 FOUNDATION Fieldbus Wiring Wiring in T12 housing " Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the Caution! ENDRESS+HAUSER Made in Germany FOUNDATION Fieldbus standard and the desired safety...
Page 36
Wiring Levelflex M FMP40 FOUNDATION Fieldbus Wiring with FOUNDATION Fieldbus connector " Before connection please note the following: ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Foundation Fieldbus devices are marked on the Order Code: Ser.-No.: IP68 / NEMA 6P nameplate (1).
Levelflex M FMP40 FOUNDATION Fieldbus Wiring Connecting the measuring unit 4.2.1 Ground connection It is necessary to make a good ground connection to the ground terminal on the outside of the housing, in order to achieve EMC security. 4.2.2 Cable gland...
Wiring Levelflex M FMP40 FOUNDATION Fieldbus 4.2.7 Overvoltage protection If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to EN/IEC 60079-14 or EN/IEC 60060-1 (10 kA, Puls 8/20 μs) it has to be ensured that •...
Levelflex M FMP40 FOUNDATION Fieldbus Operation Operation This chapter gives an overview of the different operating options for the device. The different methods of parameter access are described and the preconditions for each method are stated. The meaning of the parameters is not described in this chapter. Instead, refer to: •Chapter 6: "Commissioning"...
Page 40
Operation Levelflex M FMP40 FOUNDATION Fieldbus 5.1.1 On-site operation Options for on-site operation •Display and operating module VU331 •Endress+Hauser operating software "FieldCare" Parameter access by on-site operation The following parameters can be accessed by on-site operation: •Parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block) •Endress+Hauser service parameters...
Levelflex M FMP40 FOUNDATION Fieldbus Operation Operation with the display and operating module VU331 5.2.1 Liquid crystal display (LCD) Four lines with 20 characters each. Display contract adjustable through key combination. (liquid crystal display) Orde Ser.- Orde Ser.- r Code r Code No.:...
Page 42
Operation Levelflex M FMP40 FOUNDATION Fieldbus 5.2.3 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the device is in an alarm state. If the symbol flashes, this indicates a warning.
Page 43
Levelflex M FMP40 FOUNDATION Fieldbus Operation 5.2.5 The operating menu General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, ..., 0C, 0D): The individual operating options of the device are split up roughly into different function groups.
Page 44
Operation Levelflex M FMP40 FOUNDATION Fieldbus Navigation within the menu ENDRESS + HAUSER – >3 s Return to basic setup tank shape medium property Group Selection Standard safety settings aluminium tank lenght adjustment plastic tank bypass / pipe linearisation coax probe concrete wall extended calibr.
The operating program FieldCare is an Endress+Hauser Plant Asset Management Tool based on FDT technology. You can use Field-Care to configure all your Endress+Hauser devices, as well as devices from other manufacturers that support the FDT standard. Hardware and software requirements you can find on the internet: www.endress.com È...
Page 46
Operation Levelflex M FMP40 FOUNDATION Fieldbus Signal analysis via envelope curve L00-FMP4xxxx-20-00-00-en-007 Tank linearization L00-fmp-Ixxx-20-00-00-en-041 Endress+Hauser...
Levelflex M FMP40 FOUNDATION Fieldbus Operation Operation with a FOUNDATION Fieldbus configuration program 5.4.1 FOUNDATION Fieldbus configuration programs The user can obtain special configuration and operating programs offered by different manufacturers for use in configuration. These can be used for configuring both the FOUNDATION Fieldbus functions and all the device-specific parameters.
A FOUNDATION Fieldbus configuration tool offers two types of parameter representation: •Representation by parameter name Examples: "PAROPERATIONCODE", "PARRESET" •Representation by parameter label (identical to the labels on the display module VU331 and in an Endress+Hauser operation tool) Examples: "unlock parameter", "reset" Operation with the handheld terminal Field Communicator 375, 475 5.5.1...
Page 49
Levelflex M FMP40 FOUNDATION Fieldbus Operation 5.5.4 Example basic setup dsdmdm df das. asdas fa asas la. tank properties: standard Fieldbus Live Device List Number of Devices found = 1 standard Address aluminium tank plastic tank E+H_LEVELFLEX_M_XXXXXXX bypass / pipe...
• "Blocking distance", → ä 66 • "Envelope curve", → ä 68 • "Basic setup with the Endress+Hauser operating program", → ä 72 • "Commissioning with a FOUNDATION Fieldbus configuration tool", → ä 78 • "Commissioning with the handheld terminal Field Communicator 375, 475", → ä 82...
Page 51
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning 6.2.2 Key combination (display and operating module VU331) Locking Press S, O and F simultaneously. Unlocking If you try to change a parameter, the following appears: L00-fmrxf0a4-20-00-00-de-001 Press S, O and F simultaneously. The "unlock parameter" (0A4) function appears.
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Resetting the device It is advisable to reset the device parameters before the commissioning if you want to use a device with an unknown history. 6.3.1 Resetting the parameters of the FOUNDATION Fieldbus function blocks Parameters affected •...
Page 53
– "inactive": deactivates the tank map but does not delete it. It can be re-activated when required. – "active": activates the tank map. Resetting the tank map with an Endress+Hauser operating program In the function group "extended calibr." select the "cust. tank map" (055) function. Select the required option ("reset", "inactive" or "active") Resetting the tank map with a FOUNDATION Fieldbus configuration tool In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Basic setup tank shape flange: Standard reference point of measurement measuring cond. Unknown measuring cond. Standard empty calibr. full calibr. mapping E = empty calibr. (= zero) LN = probe length setting in 005...
Page 55
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning " Caution! The basic setupis sufficient for successful commissioning in morst applications. The Levelflex is precalibrated at the factory to the probe length ordered so that in most cases only the application parameters, which automatically adapt the device to the measuring conditions, need the entered.
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Commissioning by the display and operating module VU331 6.5.1 Power up device When the device is switched on for the first time, the following messages appear in a sequence of 5 s on the display: software version, communication protocoll and language selection ⇒...
Page 57
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning 6.5.2 Function group "basic setup" (00) ⇒ ENDRESS + HAUSER – Function "tank properties" (002) ⇒ ENDRESS + HAUSER – This function is used to select the tank properties. Selection: • standard • aluminium tank •...
Page 58
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus concrete wall The "concrete wall" option takes into account the signal-damping property of concrete walls when mounting with < 1 m distance to the wall. Function "medium property" (003) ⇒ ENDRESS + HAUSER –...
Page 59
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Function "process propert" (004) ⇒ ENDRESS + HAUSER – Use this funtcion to adapt the device to the filling speed in the tank. The setting impacts on an intelligent filter. Selection: • standard • fast change •...
Page 60
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Function "probe length" (031) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length.
Page 61
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Function "determine length" (034) ⇒ ENDRESS + HAUSER – Use this function, the probe length can be determined automatically. Due to the mounting conditions, the automatically determined probe length may be larger than the actual probe (typically 20 to 30 mm longer).
Page 62
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (= span). 100% F = full calibration (= span) F max = E –...
Page 63
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Function "check distance" (051) ⇒ ENDRESS + HAUSER – This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available: Options: •...
Page 64
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Manual Mapping is also possible by manually entering the range to be suppressed. This entry is made in the "range of mapping" (052) function. " Caution! The range of mapping must end 0.3 m (20") before the echo of the actual level.
Page 65
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Function "dist./meas.value" (008) ⇒ ENDRESS + HAUSER – The distance measured from the reference point to the product surface and the measured value calculated with the aid of the empty calibration are displayed again. Check whether the values correspond to the actual meas.
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is set to 0.2 m at the factory. For rope probes with lengths of more than 8 m, the upper blocking distance is preset to 2.5 % of the probe length.
Page 67
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Maximum measured error Typical statements for reference conditions: DIN EN 61298-2, percentage of the span. Output: Digital Analogue sum of non-linearity, measurig range: ±0.06 % non-repeatability and hysteresis – up to 10 m: ±3 mm –...
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Envelope curve After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended. 6.7.1 Function "plot settings" (0E1) ⇒ ENDRESS + HAUSER –...
Page 69
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning 6.7.3 Function "envelope curve display" (0E3) You can obtain the following information from the envelope curve display in this function: quality of evaluated echo full calibr. evaluated echo empty calibr. is marked envelope curve...
Page 70
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus 6.7.5 Mapping (empty curve) and difference curve To suppress interference signals, the envelope curve is not directly evaluated in the Levelflex. The mapping (empty curve) is first subtracted from the envelope curve. The system looks for level echoes in the resulting difference curve.
Page 71
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Horizontal Zoom mode Firstly, go into the envelope curve display. Then press to switch to the envelope curve navigation. You are then in Horizontal Zoom mode. Either is displayed. • increases the horizontal scale.
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Basic setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: • Start the operating program and establish a connection. • Select the "basic setup" function group in the navigation window.
Page 73
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Basic setup step 2/6: • Enter the application parameters (see chapter basic setup with "VU331"): – Tank properties – Medium properties – Process properties l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
Page 74
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Basic setup step 4/6: • Enter the application parameters (see chapter basic setup with "VU331"): – Probe length – Probe – Probe length – Determine length l00-fmp4xxxx-20-00-00-en-004 Basic setup step 5/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
Page 75
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Basic setup step 6/6: • Interference echo suppression takes place in this step • The measured distance and the current measured value are always displayed in the header l00-fmp4xxxx-20-00-00-en-006.gif 6.8.1 Signal analysis via envelope curve After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve.
Page 76
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Evaluating the measurement with the aid of the envelope curve Typical curve shapes: The following examples display typical curve shapes for a rope or rod probe in an empty tank. For all probe types, a negative probe end signal is shown. For rope probes, the end weight causes an additional preliminary positive echo (see rope probe diagram).
Page 77
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning Evaluating the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty.
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus Commissioning with a FOUNDATION Fieldbus configuration tool Note! For commissioning of the device with a FOUNDATION Fieldbus configuration tool you need to know the INSTRUMENT_ID, which consists of the following parts: Instrument_ID = 452B481012-XXXXXXXX...
Page 79
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning 6.9.2 Parametrization of the Resource Block (Start Index: 400) Enter the desired block name (optional). Factory setting: RESOURCE_XXXXXXXX Opern the Resource Block On delivery, write protection is disabled so that you can access the write parameters via FOUNDATION Fieldbus.
Page 80
– by the display and operating module VU331 (→ ä 41) – by an Endress+Hauser operating program (→ ä 45) In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display: - parameter names (e.g. "PARTANKSHAPE") - label texts (e.g.
Page 81
Levelflex M FMP40 FOUNDATION Fieldbus Commissioning 6.9.4 Parametrization of the Analog Input Blocks Levelflex M has two Analog Input Blocks that can be assigned to the various process variables. The following descripiton provides an example for the Analog Input Block 1 (Start Index 500).
Commissioning Levelflex M FMP40 FOUNDATION Fieldbus In addition to the limit values you must also specify the action taken if a limit value is exceeded using the alarm priorities (parameters HI_HI_PRI, HI_PRI, LO_PRI, LO_LO_PRI). Reporting to the the fieldbus host system only takes place if the alarm priority is higher than 2.
Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves ("Spare Parts", → ä 95). Please contact Endress+Hauser Service for further information on service and spare parts.
Accessories Levelflex M FMP40 FOUNDATION Fieldbus Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp.
Levelflex M FMP40 FOUNDATION Fieldbus Accessories Remote display and operation FHX40 Wall-mounting Pipe-mounting (without mounting bracket) (mounting bracket and plate supplied optionally, s. product structure) Separate housing FHX40 (IP 65) Micropilot M (4.8) Levelflex M Prosonic M O rd O rd...
Accessories Levelflex M FMP40 FOUNDATION Fieldbus Centering disks If the probes with rod version are used in stilling well or bypass, it must be ensured that the probe does not come into contact with the wall. The centering disk fixes the rod probe in the middle of the pipe.
Accessories Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI00405C/07/EN. Note! For the device you need the "ToF Adapter FXA291" as an additional accessory.
Accessories Levelflex M FMP40 FOUNDATION Fieldbus Extension rod / Centering DN50 (2") DN80 (3") DN150 (6") DN200 (8") DN250 (10") nozzle For DN200 and DN250 height in combination with horn adapter Keep metal tube centering disk at minimum length! at PPS - GF40 Extension rod Not for ¾"...
Levelflex M FMP40 FOUNDATION Fieldbus Accessories Isolated tie down Mounting-kit Order - No. for 4 mm rope probe 52014249 Reliable, isolated mounting for 6 mm rope probe 52014250 If a rope probe has to be fixed and asecure grounded mounting is not possible, we recommend using the insulating...
Trouble-shooting Levelflex M FMP40 FOUNDATION Fieldbus Trouble-shooting Trouble-shooting instructions Levelflex M -Trouble Shooting Check voltage and Not ok Instrument does compare it with the Connect the Instrument works? Ready specifications on the not respond correct voltage nameplate. Check the polarity...
Levelflex M FMP40 FOUNDATION Fieldbus Trouble-shooting System error messages Code Description Possible cause Remedy A102 checksum error device has been powered off before data reset general reset & new calibr. could be stored; avoid emc problem; required emc problem; if alarm prevails after reset,...
Page 92
Trouble-shooting Levelflex M FMP40 FOUNDATION Fieldbus Code Description Possible cause Remedy A251 Feedthrough Lost contact in the process feedthrough Replace process feedtrough A261 HF cable defective HF cable defective or HF connector Check HF connector, replace cable removed if defective...
Levelflex M FMP40 FOUNDATION Fieldbus Trouble-shooting Application errors Error Output Possible cause Remedy A warning or alarm Depending on the configuration See table of 1. See table of error messages (→ ä 91 ) has occurred error messages (→ ä 91) →...
Page 94
Trouble-shooting Levelflex M FMP40 FOUNDATION Fieldbus Error Output Possible cause Remedy E641 (loss of echo) If the device is configured to Hold by loss of noise level during the Repeat once more empty calibr. after turn on the echo the output is set to any value/current.
Levelflex M FMP40 FOUNDATION Fieldbus Trouble-shooting Spare Parts An overview of the spare parts for your device is available in the internet at www.endress.com. To obtain information on the spare parts, proceed as follows: Go to "www.endress.com" and select your country.
Levelflex M FMP40 FOUNDATION Fieldbus Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
10.2008 01.04.04 Function "LAS" improved BA244F/00/en/03.09 ---- 71074798 BA244F/00/en/08.09 71102346 BA00244F/00/EN/13.10 71120272 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress+Hauser...
Technical data Levelflex M FMP40 FOUNDATION Fieldbus Technical data 10.1 Additional technical data 10.1.1 Input The measured variable is the distance between a reference point (see Fig., → ä 14) and the product Measured variable surface. Subject to the input empty distance "E" (see Fig., → ä 54), the level is calculated.
Page 99
Levelflex M FMP40 FOUNDATION Fieldbus Technical data Data of the FOUNDATION Basic Data Fieldbus interface Device Type 1012 (hex) Device Revision 04 (hex) DD Revision 02 (hex) CFF Revision 02 (hex) ITK Version 4.61 ITK-Certification Driver-No. www.endress.com / www.fieldbus.org Link-Master (LAS) cabable Link Master / Basic Device selectable yes;...
Page 100
Technical data Levelflex M FMP40 FOUNDATION Fieldbus Function Blocks Block Content Execution Functionality time Resource Block The Resource Block contains all the data that uniquely enhanced identifies the field device. It is an electronic version of a nameplate of the device.
Page 101
Levelflex M FMP40 FOUNDATION Fieldbus Technical data 10.1.3 Auxiliary energy Terminals Cable cross-section: 0.5 to 2.5 mm (20 to 14 AWG) Cable entry • Cable gland: M20x1.5 (only cable entry for Ex d) • Cable entry: G½ or ½NPT • FOUNDATION Fieldbus 7/8" plug...
Page 102
Technical data Levelflex M FMP40 FOUNDATION Fieldbus 10.1.4 Performance characteristics Reference operating • temperature = +20 °C ±5 °C conditions • pressure = 1013 mbar abs. ±20 mbar • humidity = 65 % ±20 % • Reflection factor ≥ 0.8 (surface of the water for coax probe, metal plate for rod and rope probe with min.
Page 103
Levelflex M FMP40 FOUNDATION Fieldbus Technical data 10.1.5 Operating conditions: Environment Ambient temperature range Ambient temperature for the transmitter: -40 °C to +80 °C. The functionality of the LCD display may be limited for temperatures Ta < -20 °C and Ta > +60 °C. A weather protection cover should be used for outdoor operation if the device is exposed to direct sunlight.
Page 104
Technical data Levelflex M FMP40 FOUNDATION Fieldbus 10.1.6 Operating conditions: Process Process temperature range The maximum permitted temperature at the process connection (see Figure for measuring point) is determined by the O-ring version ordered: O-ring-material min. Temperature max. Temperature FKM (Viton) -30 °C/-22 °F...
Page 105
Levelflex M FMP40 FOUNDATION Fieldbus Technical data 10.1.7 Mechanical construction Material Refer to TI00358F/00/EN, chapter "Material (not in contact with process)" and "Material (in contact with process)". Tolerance of probe length Rod probes Rope probes over (3.2 ft) (9.8 ft) (20 ft) (3.2 ft)
Page 106
The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. WHG. See "Ordering structure", → ä 6 - (see ZE00256F/DE)
Page 107
Levelflex M FMP40 FOUNDATION Fieldbus Technical data Ex approval The devices are certified for use in hazardous areas. The Safety Instructions to be observed are enclosed and referenced on the nameplate: • Europe: EC type-examination certificate, Safety Instructions XA • USA: FM Approval, Control Drawing •...
Page 108
Technical data Levelflex M FMP40 FOUNDATION Fieldbus 10.1.9 Additional documentation Additional documentation This supplementary documentation can be found on our product pages on www.endress.com: • Technical Information (TI00358F/00/EN) • Safety Manual "Functional safety manual" (SD00174F/00/EN) • Certificate "Allgemeine bauaufsichtliche Zulassung" (ZE00256F/00/DE) •...
Page 109
Levelflex M FMP40 FOUNDATION Fieldbus Technical data Endress+Hauser...
Appendix Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.1 Operating menu FOUNDATION Fieldbus basic setup tank properties medium cond. process proper. end of probe 030 determine length empty calibr. enter value standard unknown standard see Function group “leghth adjustment 03” aluminium tank DC: 1.4 …...
Page 111
Levelflex M FMP40 FOUNDATION Fieldbus Appendix full calibr. dist./meas.value check distance range of mapping start mapping dist./meas.value enter value distance = ok input of D and L dist. too small mapping range are displayed D and L manual are displayed probe free dist.
Appendix Levelflex M FMP40 FOUNDATION Fieldbus 11.2 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation "BA00245F – Description of the Instrument Functions" on the enclosed CD-ROM. 11.3 Block model of the Levelflex M The Micropilot M contains the follwoing blocks: •...
Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.4 Resource block The resource block contains the parameters used to describe physical resources of the device. It has no linkable inputs or outputs. 11.4.1 Operation The resource block is opened by a click on the resource line.
Appendix Levelflex M FMP40 FOUNDATION Fieldbus 11.5 Sensor Block The Sensor Block contains the parameters required to calibrate the device. These parameters can also be addressed by using the VU331 display module. The calibration of the device is described in Chapter 6.
Page 115
Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.5.5 Methods The FOUNDATION Fieldbus specification provides for the use of so-called methods to simplify the operation of the device. A method is an interactive sequence of steps that must be followed in order to obtain a particular function from the device.
Page 116
Appendix Levelflex M FMP40 FOUNDATION Fieldbus Parameter Position rel. Variable Name Size Type Access Storage Changeable Indicator Index [bytes] Class in Mode ackn. alarm PARACKNOWLEDGEALARM Unsigned8 dynamic Auto, OOS broken probe det PARBROKENPROBEDETECTION Unsigned8 static level/ullage PARLEVELULLAGEMODE Unsigned8 static linearisation...
Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.6 Diagnostic Block 11.6.1 Operation The diagnostic block contains the error messages of the device. These parameters can also be addressed by using the VU331 display module. The diagnostic block is opened by clicking on the "diagnostic" line. Parameter changes from the tool are made off-line while the device is operating.
Appendix Levelflex M FMP40 FOUNDATION Fieldbus 11.7 Display Block 11.7.1 Operation The display block contains the parameters required to parametrise the display module VU331 (which is contained in the remote display and operating unit FHX40). These parameters can also be addressed by using the VU331 display module.
Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.8 Analog input block The analog input block conditons the signal output by the Sensor block and outputs signal to the PCL or other function blocks. L00-FMR2xxxx-05-00-00-en-008 11.8.1 Operation The resource block is opened by a click on the resource line.
Page 120
Appendix Levelflex M FMP40 FOUNDATION Fieldbus 11.8.3 Output values Parameter Description Either the primary/secondary Sensor block value used to execute the block or a process value associated with it. Comprises value and status. The primary value output as a result of executing the analog input block. Comprises value and status.
Page 121
Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.8.5 Output response parameters Parameter Description LOW_CUT Not relevant to level measurement! Determines a threshold for square root linearization below which the output value is set to zero. PV_FTIME Sets the time constant for the output value.
Appendix Levelflex M FMP40 FOUNDATION Fieldbus 11.8.9 Simulation The SIMULATE parameter allows the Sensor block output value to be simulated, provided simulation has also been enabled at the device DIP switch. The simulation must be enabled, a value and/or status entered and the block must be in AUTO mode. During simulation the Sensor output value is substituted by the simulated value.
Levelflex M FMP40 FOUNDATION Fieldbus Appendix 11.10 List of start indices The following list indicates the start indices for all blocks and objects: Object Start Index Object Dictionary Object Start Index Resource Block Analog Input 1 Function Block Analog Input 2 Function Block...
Appendix Levelflex M FMP40 FOUNDATION Fieldbus 11.11 Patents This product may be protected by at least one of the following patents. Further patents are pending. • US 5,661,251 i EP 0 780 664 • US 5,827,985 i EP 0 780 664 •...
Levelflex M FMP40 FOUNDATION Fieldbus Index Index Accessories ........84 Probe .
Page 126
Levelflex M FMP40 FOUNDATION Fieldbus Index Endress+Hauser...
Page 127
Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.