Factory Recommended Branch Circuit Protection
WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply
could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more
than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection
devices specified in this manual.
Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input
rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input
rating.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
Model CIMR-Zo o
2A0011
2A0017
2A0024
2A0031
2A0046
2A0059
2A0075
2A0088
2A0114
2A0143
2A0169
2A0211
2A0273
2A0343
2A0396
4A0005
4A0008
4A0011
4A0014
4A0021
4A0027
4A0034
4A0040
4A0052
4A0065
4A0077
4A0096
4A0124
4A0156
4A0180
4A0240
4A0302
4A0361
4A0414
YASKAWA ELECTRIC TOEP C710616 45B YASKAWA AC Drive – Z1000 User Manual
16
Table 6.2 Factory Recommended Z1000 AC Drive Branch Circuit Protection
Nominal Output
AC Drive Input
Power (HP)
(A)
3
10.6
5
16.7
7.5
24.2
10
30.8
15
46.2
20
59.4
25
74.8
30
88
40
114
50
143
60
169
75
211
10
273
125
343
150
396
3
4.8
5
7.6
7.5
11
10
14
15
21
20
27
25
34
30
40
40
52
50
65
60
77
75
96
100
124
125
156
150
180
200
240
250
302
300
346
350
410
MCCB Rating (A)
Time Delay Fuse
<2>
<1>
Rating (A)
200 V Class
20
17.5
30
25
40
40
60
50
90
80
110
100
150
125
175
150
225
175
250
250
300
275
400
350
500
450
600
600
<5>
700
400 V Class
15
8
15
12
20
17.5
25
20
40
35
50
45
60
50
75
70
100
90
125
110
150
125
175
150
225
200
300
250
350
300
450
400
600
500
600
600
800
700
YASKAWA TOEP YAISUP 04A YASKAWA AC Drive – Z1000 User Manual Supplement
6.4 Installing Peripheral Devices
Table 6.2
Bussmann
Non-time Delay
Semiconductor
Fuse Model
Fuse Rating (A)
<3>
(Fuse Ampere)
<4>
30
FWH-40B (40)
50
FWH-50B (50)
70
FWH-80B (80)
90
FWH-100B (100)
125
FWH-150B (150)
175
FWH-175B (175)
200
FWH-225A (225)
250
FWH-225A (225)
300
FWH-250A (250)
400
FWH-275A (275)
500
FWH-350A (350)
600
FWH-400A (400)
FWH-450A (450)
<5>
FWH-600A (600)
FWH-600A (600)
12
FWH-40B (40)
20
FWH-40B (40)
30
FWH-45B (45)
40
FWH-45B (45)
60
FWH-60B (60)
80
FWH-60B (60)
100
FWH-125B(125)
110
FWH-150B (150)
150
FWH-200B (200)
175
FWH-225A (225)
225
FWH-225A (225)
275
FWH-225A (225)
350
FWH-250A(250)
450
FWH-300A (300)
500
FWH-350A (350)
FWH-400A (400)
<5>
FWH-600A (600)
<6>
FWH-800A (800)
1000
<6>
FWH-800A (800)
1200
.
6
245

Advertisement

Table of Contents
loading

Table of Contents