11 Replace Table D.1 on page 328
11
Replace Table D.1 on page 328
D.2 European Standards
D.2 European Standards
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business
and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• Low Voltage Directive: 2006/95/EC
• EMC Guidelines: 2004/108/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying
the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE
standards. After setting up the device, verify that conditions meet European standards.
u u
CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC61800-5-1, and it fully complies with the Low Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other
devices:
n n
Area of Use
Do not use drives in areas with pollution higher than severity 2.
n n
Installing Fuses on the Input Side
Always install input fuses. Select fuses according to the table below.
WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply
could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more
than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection
devices specified in this manual.
Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input
rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input
rating.
Model CIMR-Zo o
2A0011
2A0017
2A0024
2A0031
2A0046
2A0059
2A0075
2A0088
2A0114
2A0143
2A0169
2A0211
2A0273
2A0343
342
20
Figure D.1 CE Mark
Table D.1 Recommended Input Fuse Selection
Manufacturer: Bussmann
Model
Three-Phase 200 V Class
FWH-40B
FWH-50B
FWH-80B
FWH-100B
FWH-150B
FWH-175B
FWH-225A
FWH-225A
FWH-250A
FWH-275A
FWH-350A
FWH-400A
FWH-450A
FWH-600A
YASKAWA ELECTRIC TOEP C710616 45B YASKAWA AC Drive – Z1000 User Manual
YASKAWA TOEP YAISUP 04A YASKAWA AC Drive – Z1000 User Manual Supplement
Fuse Ampere Rating (A)
40
50
80
100
150
175
225
225
250
275
350
400
450
600