Object
1)
14
External sensor 2 type selection
15
3)
External sensor 2 DI action
16
4)
Temperature range high
17
4)
Temperature range low
18
4)
PM2.5 range high
19
4)
PM2.5 range low
20
4)
CO
range high
2
21
4)
CO
range low
2
22
4)
VOC range high
23
4)
VOC range low
24
4)
Humidity range high
25
4)
Humidity range low
26
Reserved 2
27
PM2.5 setpoint high range
28
PM2.5 setpoint low range
29
CO
setpoint high range
2
30
CO
setpoint low range
2
31
Fan type
32
ECM fan output limit LOW
33
ECM fan output limit HIGH
34
Filter time display setting
Siemens
Smart Infrastructure
Read
Write
40014 1
RW
0x03
0x06
40015 1
RW
0x03
0x06
40016 1
RW
0x03
0x06
40017 1
RW
0x03
0x06
40018 1
RW
0x03
0x06
40019 1
RW
0x03
0x06
40020 1
RW
0x03
0x06
40021 1
RW
0x03
0x06
40022 1
RW
0x03
0x06
40023 1
RW
0x03
0x06
40024 1
RW
0x03
0x06
40025 1
RW
0x03
0x06
40026 1
RW
0x03
0x06
40027 1
RW
0x03
0x06
40028 1
RW
0x03
0x06
40029 1
RW
0x03
0x06
40030 1
RW
0x03
0x06
40031 1
RW
0x03
0x06
40032 1
RW
0x03
0x06
40033 1
RW
0x03
0x06
40034 1
RW
0x03
0x06
1
0
0: (no function)
1: Temperature (AI) (NTC 10k)
2: Temperature (AI) (0...10 V)
3: PM2.5 (AI) (0...10 V)
4: CO
(AI) (0...10 V)
2
5: VOC (AI) % (0...10 V)
6: VOC (AI) mg/m³ (0...10 V)
7: rH (AI) (0...10 V)
8: Alarm input (DI)
9: Dummy AI (0...10 V) (Room
unit only)
10: Dummy DI (Room unit only)
1
0
0: Normally open / Open
1: Normally closed / Close
1
x100
50
Max. of low range...100
1
x100
0
-50...Min. of high range
1
500
Max. of low range...1000
1
0
0...Min. of high range
1
2000
Max. of low range...2000
1
0
0...Min. of high range
1
x10
5)
5mg
Max. of low range...100
or
50 %
1
0
0...Min. of high range
1
100
Max. of low range...100
1
0
0...Min. of high range
1
0
0...ffff
1
100
Max. of low range...500
1
12
0...Min. of high range
1
1500
Max. of low range...2000
1
500
0...Min. of high range
1
3
1: On/Off fan
3: 3 speed fan
4: 4 speed fan
5: ECM fan
1
30
0...Min. of high range
1
80
Max. of low range...100%
1
0
0: disable
1: enable
29