Siemens RDF870KN Series Manual page 25

Touch screen flush-mounted pm2.5 & iaq controllers with knx or rs485 modbus
Hide thumbs Also See for RDF870KN Series:
Table of Contents

Advertisement

Description of communication objects
Object no. Object name
1
Fault information
Common alarm output. If an alarm occurs, the alarm number is transmitted.
2
Fault state
Common alarm output. If an alarm occurs, the alarm flag is set.
3
Enable alarm info
A supervisor alarm system can disable the broadcasting of alarms by the devices. This has no impact on the
local display of alarms. After a timeout of 48 hours, the sending of faults is automatically enabled again.
4
Room operating mode user:
Preselection
Controls the room operating mode selection of the room controller/room unit via bus.
The command can also be submitted as three 1-bit communication objects (5...7). The last interaction wins –
either from local operating mode button or via bus.
Note: 8-bit and 1-bit object available, selectable by using parameter in ETS
Operating mode user: Preselection
- Comfort
5
- Eco
6
- Protection
7
Switch room operating mode to either Comfort, Economy or OFF.
The last interaction wins – either from local operating mode button or via bus.
Note: 8-bit and 1-bit object available, selectable by using parameter in ETS
8
Room operating mode: State
Effective room operating mode used by the thermostat (considering timer, user selection, etc.) This state
information is available via one 8-bit enumeration or three 1-bit communication objects (9...11).
Note: 8-bit and 1-bit object available, selectable by using parameter in ETS
Room operating mode:
9
- State Comfort
10
- State Eco
11
- State Protection
Corresponding communication object sends "True"
Note: 8-bit and 1-bit object available, selectable by using parameter in ETS
12
Room temperature
Value of the room temperature.
Note: The room temperature value is decided by priority if all value types exist. (Built in > Remote)
13
Remote: Indoor temperature
Remote indoor temperature sensor value
14
Outdoor temperature
Value of the outside temperature is received.
Siemens
Smart Infrastructure
Function
Type/length
Alarm information
219.001
6 Byte
Faulty/normal
1.005
1 bit
Enable/disable
1.003
1 bit
Comfort
20.102
Economy
1 Byte
OFF
ON
1.001
1 bit
OFF
Comfort
20.102
Economy
1 Byte
Off
ON
1.001
OFF
1 bit
Temperature value
9.001
2 Bytes
Temperature value
9.001
2 Bytes
Temperature value
9.001
2 Bytes
Flags
CT
CT
CWU
CWTU
CW
CRT
CT
CRT
CWU
CRT
25
A6V11439454_en--_d
2021-03-31