Siemens RDF870KN Series Manual page 32

Touch screen flush-mounted pm2.5 & iaq controllers with knx or rs485 modbus
Hide thumbs Also See for RDF870KN Series:
Table of Contents

Advertisement

Object
84
Dummy_DI_X2
85
Dummy_AI_X1
86
Dummy_AI_X2
87
8)
Room temperature_Remote
8)
88
Outdoor temperature_Remote
89
8)
PM2.5_Remote
8)
90
CO2_Remote
91
8)
VOC_Remote
8)
92
Humidity_Remote
93
Fan1 speed
94
Fan 1 status
95
Fan 2 speed
96
Fan 2 status
97
Alarm value display
98
Alarm information
32
Siemens
Smart Infrastructure
Read
Write
30019 1
RO
0x04
30020 1
RO
0x04
30021 1
RO
0x04
40109 1
RW
0x03
0x06
40110 1
RW
0x03
0x06
40111 1
RW
0x03
0x06
40112 1
RW
0x03
0x06
40113 1
RW
0x03
0x06
40114 1
RW
0x03
0x06
40115 1
RW
0x03
0x06
40116 1
RW
0x03
0x06
40117 1
RW
0x03
0x06
40118 1
RW
0x03
0x06
40119 1
RW
0x03
0x06
30022 1
RO
0x04
2: Invalid
4
-
0: OPEN;
1: CLOSE;
2: Invalid
4
x1000 -
0...10 V value
4
x1000 -
0...10 V value
2
x100
0
-50...200 ° C; Use 32767 as non-
valid value
-50...200 ° C; Use 32767 as non-
2
x100
0
valid value
2
0
0...1000; Use 32767 as non-valid
value
0...2000; Use 32767 as non-valid
2
0
value
2
0
x10 for 0.0...10.0 mg/m
it means use 128...228 stand for
0.0...10.0 mg/m
0...100 %; Use 0...100 to stand
for 0...100 %;
Use 127 as non-valid value
2
0
0...100 %;
Use 127 as non-valid value
2
0
0...1 for 1 speed fan;
0...3 for 3 speed fan;
0...4 for 4 speed fan;
0...100 for ECM fan
2
0
0: Auto;
1: Manual
2
0
0...1 for 1 speed fan;
0...3 for 3 speed fan;
0...4 for 4 speed fan;
0...100 for ECM fan
2
0
0: Auto;
1: Manual
2
0
0: Disable
If alarm value ≥1, user can define
the error code display in RU.
4
0
0: No alarm;
Any bit set to 1 means there is
alarm or error defined as below:
Bit0: KNX bus error;
Bit1: KNX ADR error;
Bit2: AL1;
3
plus 128,
3
;
A6V11439454_en--_d
2021-03-31