Item
Description
TEMH
Temperature sensor high range Max. of low range...100
TEML
Temperature sensor low range
SPMH
PM2.5 setpoint high range
SPML
PM2.5 setpoint low range
SPCH
CO
setpoint high range
2
SPCL
CO
setpoint low range
2
FAN
Fan type selection
ECMH
ECM fan output limit high
ECML
ECM fan output limit low
TC
Filter time display setting
2)
PMES
PM2.5 ECO mode setpoint
COES
2)
CO
ECO mode setpoint
2
BUZZ
Buzzer function
UNIT
Temperature unit
LOCK
Keylock function
OPSL
Operating mode selection
CALT
Internal temperature sensor
calibration
RDF870KN available parameters and their order of appearance:
Room controller:
APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > APP
RDF870MB available parameters and their order of appearance:
Room controller:
MODA > MODB > MODF >APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT >
MODA
Room unit:
MODA > MODB > MODF > LOCK > BUZZ > CALT > MODA
1)
Room controller: 0...8; Room unit: 0...10
2)
The setpoint cannot be changed in ECO mode.
Restriction for sensor selection:
1. If SEN1 and SEN2 are configured with same selection type 1...8, they cannot be the same sensor types:
– For type 1...8, sensor1 cannot be the same as sensor2.
– For sensor types with the same function such as 1&2 or 5&6, if one sensor type is 1 or 5, the other one
cannot be 2 or 6.
Note:
When APP = 2 (both PM2.5 and CO
Siemens
Smart Infrastructure
Range
-50...Min. of high range
Max. of low range...500
0...Min. of high range
Max. of low range...2000
0...Min. of high range
1: 1 speed fan (ON/OFF)
3: 3 speed fan
4: 4 speed fan
5: ECM fan
Max. of ECML...100 %
0...Min. of ECMH
0: Disable
1: Enable
0...100
500...1500
0: Disable
1: Enable
0: ° C (degrees Celsius)
1: ° F (degrees Fahrenheit)
0: Unlock
1: Locked
2: Setpoint only
3: Operating mode only
4: Setpoint and fan speed only
0: ON/OFF
1: ON/ECO/OFF
2: ON/ECO/Protection/OFF (RU
only)
3: ON/ECO/Protection (room unit
only)
-5...5 K
control) is selected, FAN = 1 or 3 only.
2
Factory settings
50
0
100
12
1500
500
3: 3 speed fan
80 %
30 %
0: Disable
60
1000
1: Enable
0: ° C (degrees Celsius)
0: Unlock
1: ON/ECO/OFF
0