Siemens RDF870KN Series Manual page 34

Touch screen flush-mounted pm2.5 & iaq controllers with knx or rs485 modbus
Hide thumbs Also See for RDF870KN Series:
Table of Contents

Advertisement

Object
116
Function selection for VOC
117
Function selection for CO
118
Function selection for humidity
119
Function selection for FAN
120
Heating / Cooling / Ventilation status
display
1)
If SEN1 and SEN2 are configured with the same selection type 1...8, they cannot be the same sensor
types:
– For type 1...8, sensor1 cannot be the same as sensor2.
– For sensor types with the same function such as 1&2 or 5&6, if one sensor type is 1 or 5, the other one
cannot be 2 or 6.
2)
Displays only when SEN1 is set to DI
3)
Displays only when SEN2 is set to DI
4)
Depends on settings of SEN1 and SEN2
5)
Only for unit μg/m
6)
The setpoint cannot be changed in ECO mode.
7)
When the value is 0, the lock icon is not displayed. When other values are selected, the icon is displayed.
8)
The difference between external and remote:
Object name with external indicates the status, values of the connected sensors via inputs X1, X2, M.
Object name with remote indicates the values received from master controller.
If the values from master controller, external sensors and built-in sensor exist simultaneously, display priori-
ty of value on device is master controller > external sensors > built-in sensor.
34
Siemens
Smart Infrastructure
40209 1
RW
40210 1
RW
2
40211 1
RW
40212 1
RW
40213 1
RW
3
Read
Write
0x03
0x06
3
0x03
0x06
3
0x03
0x06
3
0x03
0x06
3
0x03
0x06
3
2: Enable with setpoint
0
0: Disable
1: Enable without setpoint
2: Enable with setpoint
0
0: Disable
1: Enable without setpoint
2: Enable with setpoint
0
0: Disable
1: Enable without setpoint
2: Enable with setpoint
1
0: Disable
1: 1 Fan
2: 2 Fan
0
0: Disable
1: Heating only
2: Cooling only
3: Ventilation
4: Aux heating
A6V11439454_en--_d
2021-03-31