Siemens RDF870KN Series Manual page 33

Touch screen flush-mounted pm2.5 & iaq controllers with knx or rs485 modbus
Hide thumbs Also See for RDF870KN Series:
Table of Contents

Advertisement

Object
99
PM2.5 sensor status
100
External PM2.5 sensor module error 30024 1
External PM2.5 sensor
101
communication error
102
Reserved
103
Clean filter reminder
104
Internal sensor error
105
EEPROM error
106
Filter counter value
107
Room temperature setpoint
108
VOC setpoint
109
Humidity setpoint
110
Temp SP H
111
Temp SP L
112
Idle page display
Function selection for room
113
temperature
Function selection for outside
114
temperature
115
Function selection for PM2.5
Siemens
Smart Infrastructure
Read
Write
30023 1
RO
0x04
RO
0x04
30025 1
RO
0x04
30026
30027 1
RO
0x04
30028 1
RO
0x04
30029 1
RO
0x04
30030 1
RO
0x04
40200 1
RW
0x03
0x06
40201 1
RW
0x03
0x06
40202 1
RW
0x03
0x06
40203 1
RW
0x03
0x06
40204 1
RW
0x03
0x06
40205 1
RW
0x03
0x06
40206 1
RW
0x03
0x06
40207 1
RW
0x03
0x06
40208 1
RW
0x03
0x06
Bit3: AL2;
Bit4: Clean filter;
Bit5: Built-in sensor error;
Bit6: EEPROM error;
Bit7: X1/X2 error
4
0
0: Normal status;
1: Module error;
2: Communcation error
4
0
0: No error;
1: Error
4
0
0: No error;
1: Error
4
0
0...ffff
4
0
0: No reminder;
1: Reminder
4
0
0: No error;
1: Error
4
0
0: No error;
1: Error
4
0
0...9999
3
x100
24
Temp SP L...Temp SP H
3
0.6
x10 for 0.0...5.0 mg/m
0...100 for %
3
50
0...100 %
3
x100
50
Max. of low range...200
3
x100
5
-50...Min. of high range
3
3
0: --- (no function or no any
configured function available)
1: Room temperature value
2: Outside temperature value
3: PM2.5 value
4: CO
value
2
5: VOC value
6: Relative humidity value
3
2
0: Disable
1: Enable without setpoint
2: Enable with setpoint
3
1
0: Disable
1: Enable
3
0
0: Disable
1: Enable without setpoint
3
;
33
A6V11439454_en--_d
2021-03-31