Panasonic Urban Multi MX1 Series Manual page 43

Hide thumbs Also See for Urban Multi MX1 Series:
Table of Contents

Advertisement

PACD011001G2 / PACD011004G3
Techniques for
1. Snow must be prevented from accumulating around the outdoor unit's air inlet and air discharge outlet
Prevention of
Snow
Accumulation
in
[Points relating to design of snow hood]
Areas of High
Snowfall
2. The unit should be oriented in such a way as to prevent the air heat exchanger from facing into driving
3. The outdoor unit should be set at a higher level in relation to the surface on which it is mounted than the
4. Measures to combat lightning and burying by drifting snow.
When units are
Special care must be taken with respect to short circuits when units are installed on each floors.
located on different
floors
Urban Multi Inverter "MX1" Series
and one possible answer would be to fit a snow hood.
In order to ensure the required outdoor unit airflow the duct resistance must be less than the
permissible eternal static pressure of 3 mmH
The structure must be robust enough to withstand the weight snow building up on it and strong winds or
typhoons.
The construction of the unit should be such as to avoid short circuiting between suction air and
discharge air.
A snow hood is available as an optional accessories so please make use of it where necessary.
snow.
anticipated depth of snow accumulation in order ot prevent it from being buried.
The proposed installation spot should be thoroughly investigated and on no account should the unit be
placed beneath eaves or trees where snow is likely to drift.
O.
2
Installation 1
43