Control Wiring
1. Compatible types of wire
Wiring Type
Notes:
1. Sheathed wire may be used for transmission winings, but they do not comply with EMI (Electromagnetic
2. For CS-KM indoor unit, use sheathed wire.
2. Problems arising from the use of unsuitable cable
a) When cable less than 0.75 mm² is used
Urban Multi Inverter "MX1" Series
Wiring Specifications
Shield Wire (2 wire) (See NOTE 1, 2)
Size
0.75~1.25 mm²
lnterference) (EN55014). When using sheathed wire. EMI must conform to Japanese standards
stipulated in the Electric Appliance Regulatory Act. (If using a sheathed wire, the grounding shown in
the figure on the left is unnecessary.)
Where the control wiring is particularly long the transmission signals may, for example, become
unstable and the terminal relay cease to function. (Reduced voltage) The control system may become
unduly subject to noise interference.
Installation 1
35