● Do not install the unit above devices which generate heat such as heaters, transformers or
large scale resistors.
■
Installation space
● Install the unit at least 50 mm away from other devices or wiring duct on the left and right
sides and top and bottom sides of the unit to provide a ventilation space.
● Do not install the unit above devices which generate heat such as heaters, transformers or
large scale resistors.
● In order to eliminate any effects from noise emission, power wires and electromagnetic
devices should be kept at least 100 mm away from the surfaces of the unit. When installing
the unit behind the doors of the control board, be especially careful to secure clearances as
above.
● Secure a clearance of at least 170 mm from the mounting surface of the GM1 Series for
connecting tool software cables.
WUME-GM1H-01
4.1 Installation of the GM1 Series
4-3