PART 4 SPECIFICATIONS
SENSOR SPECIFICATIONS
Relative Humidity (RH)
Accuracy/Range:
Non-linearity: ±3%
Hysteresis: ±1% RH
Response Time:
4 sec (63% slowly moving air)
Repeatability: ±0.1%
Resolution: 0.03%, 12bit
NOTE: Reconditioning of the probe may
be necessary if the probe is stored for a
period of time in a harsh environment
(e.g. high humidity or exposure to
chemicals). To recondition the probe:
heat probe for 1 day at 100°C to return
it to calibration conditions.
Temperature (T)
Accuracy/Range*:
±1°C (±2°F) for
-40 to 0°C and 80 to 123.8°C
(-40 to 32°F and 176 to 254°F)
±0.5°C (±1°F) for 0 to 80°C (32 to 176°F)
*NOTE: extended temperature range is
for Probe only, the Controller's
operating temperature is 0-50°C
Response Time:
5 sec (63% slowly moving air)
Repeatability: ±0.1°C
Resolution: 0.01°C, 14 bit
METER SPECIFICATIONS
NMRR: 60 dB
CMRR: 120 dB
A/D Conversion:
12 bit RH and 14 bit Temperature
Reading Rate:
2 samples per seconds max.
Digital Filter: Programmable
Decimal Selection:
None, 0.1 for temp and humidity
Warm up to Rated Accuracy: 30 min.
Display: 4-digit, 9-segment LED
10.2 mm (0.40"): i32, i16D, i8DV
10.2 mm (0.40") & 21 mm (0.83"):i8DH
red, green and amber programmable
colors for process variable, set point
and temperature units
ALARM 1 & 2: (programmable to
display color change)
Relay*: 250 Vac or 30 Vdc @ 3 A
(Resistive Load);; configurable for
on/off, PID and Ramp and Soak
Output 1*: SPDT type, can be
configured as A larm 1 output
Output 2*: SPDT type, can be
configured as A larm 2 output
SSR*: 20-265 Vac @ 0.05-0.5 A
(Resistive Load);; continuous
DC Pulse*: Non-Isolated;;
10 Vdc @ 20 mA
Operation: high/low, above/below,
band, latch/unlatch, normally
open/normally closed and
process/deviation;; front panel
configurations
* Only with -AL Limit A larm Option
NETWORK A ND COMMUNICATIONS
(Optional -C24, -C4EI, -EI)
Ethernet: Standards Compliance
IEEE 802.3 10Base-T
Supported Protocols: TCP/IP, A RP,
HTTPGET
RS-232/RS-422/RS-485/MODBUS:
Selectable from menu;; both A SCII
and modbus protocol selectable from
menu.
Programmable 300 to 19.2 K baud;;
complete programmable setup
capability;; program to transmit current
display, alarm status, min/max, actual
measured input value and status.
RS-485: Addressable from 0 to 199
Connection: Screw terminals
34