Example 3:
Setpoint 1 = 300,
Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, "ALR.H" = 10
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
RED
•➤ --------------- • ------ • ------ • -------------------------------- • ------ • ------- • ---------------- ➤
0
190 200 210
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.
Example 4:
Setpoint 1 = 200
Setpoint 2 = 200
Alarm 1 Setup: Deviation, Band, "ALR.H" = 20
Alarm 2 Setup: Deviation, Hi/Low, "ALR.H" = 10, "ALR.L" = 5
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display colors change sequences:
AMBER
• -- ➤ --------------- • ---------------- • ------------- • -------------- • ------------- • --------------------- ➤
0
180
Reset: The instrument automatically resets after the last menu of the
Configuration Mode has been entered. After the instrument resets, it
advances to the Run Mode.
RED
RED
GREEN
195
RED
290
GREEN
200
210
33
GREEN
300 310
RED
AMBER
220
RED