Programming SITRANS LR250

Notes:
• While the device is in PROGRAM mode the output remains active and continues to
respond to changes in the device.
• SITRANS LR250 automatically returns to Measurement mode after a period of
inactivity in PROGRAM mode (between 15 seconds and 10 minutes, depending on
the menu level).
Change parameter settings and set operating conditions to suit your specific application.
(For remote operation see
Parameter menus
Note:
For the complete list of parameters with instructions, see
(LUI) on page 96
Parameters are identified by name and organized into function groups, then arranged in a
5-level menu structure (see
1.
Enter PROGRAM mode
Point the programmer at the display (from a
maximum distance of 300 mm [1 ft]).
RIGHT arrow
mode and opens menu level 1.
Mode
displayed in PROGRAM mode within the last
10 minutes, or menu level 1 if power has been
cycled since then.
7ML19985KL01
Operating via AMS Device Manager on page 40
.
LCD Menu Structure on page 169
1. QUICK START
2. SETUP
2.1. IDENTIFICATION
2.2. DEVICE
..................
2.4. LINEARIZATION
2.4.1. VOLUME
2.4.1.1.VESSEL SHAPE
activates PROGRAM
opens the menu level last
SITRANS LR250 (FF) – OPERATING INSTRUCTIONS
.)
Parameter Reference
).
handheld programmer
display
Max. 300 mm
(1 ft)
Page 33