6.Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol-
lowing.
For 9K, 12K Models
Intake Air temp.
Setting temp. +3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
INDOOR FAN SPEED
COMPRESSOR
• A point; The indoor pipe temperature to be 35°C.
The indoor fan operates minimum 10sec. even if falls lower than 35°C.
• B point; The indoor pipe temperature to be 35°C.
The indoor fan operates minimum 10sec. even if falls lower than 35°C.
7. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C. (BY TEMPERATURE)
• The operation diagram is as following.
Hot
Start
Selecting
OFF
fan speed
ON
PIPE
TEMP 28
°C
INDOOR
FAN SPEED
COMPRESSOR
HOT-START BY TEMPERATURE
A
minimum
minimum
10sec.
10sec.
LOW
OFF
LOW
OFF
60 sec.
OFF
LOW
ON
- 17 -
B
minimum
10sec.
Selecting
LOW
fan speed
ON
SELECTING
FAN SPEED
A
OFF
OFF