Inverter Single-60Hz (R410A) 1. Models Line up ..................5 2. Nomenclature..................8 3. Specifications ..................9 4. Dimensional drawings .................14 5. Wiring diagrams ...................25 6. Refrigerant cycle diagram ..............32 7. Capacity tables ..................37 8. Capacity coefficient factor..............46 9. Operation range..................49 10. Air flow and temperature distributions(reference data)....51 11.
Page 3
6RMI0-01A All models Added N.A models Apr.2010 Change operation range 6RMI0-01B All models Nov.2010 Delete word “ Libero” LAN090HSV / LAN120HSV LAN180HSV / LAN240HSV Add ʼ11 New models LS307HV 6RMI0-02A Mar. 2011 All models Change unit & Etc. Inverter Single...
1) General Wall Mounted Type Units : Units with Simplicity in design. 2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning. 3) Inverter Units : These units are capable of minimising the Power consumption with the unique inverter technology.
Models line up 1. Models Line up 1.1 Indoor Unit kW (kBtu/h) 2.63(9) 3.51(12) 4.68(16) 5.27(18) 7.03(24) 8.79(30) 10.55(36) Indoor Type ASNW093BRU1 ASNW123BRU1 ASNW183CRU1 ASNW243CRU1 (LAN090HSV) (LAN120HSV) (LAN180HSV) (LAN240HSV) ASNW093B1U1 ASNW123B1U1 ASNW163C2U1 ASNW183C2U2 (LSN091HSV) (LSN121HSV) (LSN161HSV) (LSN181HSV) ASNW093ERH1 ASNW123ERH1 ASNW1838RH1 ASNW2438RH1...
Page 7
Models line up 6RMI0-02A 1.2 Outdoor Unit ASUW093B1U1(LSU091HSV) ASUW123B1U1(LSU121HSV) Heat pump ASUW093BRU1 (LAU090HSV) ASUW123BRU1 (LAU120HSV) Total capacity index of connectable 2.63 3.51 indoor units kBtu/h Power supply 1Φ / 208~230V / 60Hz Chassis Heat pump ASUW163C2U1(LSU161HSV) ASUW1838UH1(LAU186HV) Total capacity index of connectable 4.68 5.27 indoor units...
Page 8
6RMI0-02A Models line up ASUW183C2U2(LSU181HSV) ASUW243DGU1(LSU240HSV) Heat pump ASUW183CRU1 (LAU180HSV) ASUW243CRU1 (LAU240HSV) Total capacity index of connectable 5.27 7.03 indoor units kBtu/h Power supply 1Φ / 208~230V / 60Hz Chassis UE1+ ASUW2435SZ1(LSU246HV), Heat pump ASUW303DGH1(LSU306HV) ASUW2438UH1(LAU246HV) Total capacity index of connectable 7.03 8.79 indoor units...
Nomenclature 6RMI0-02A 2. Nomenclature • Model Number Serial Number Function H : Plasma + (A/chageove) + A/Clean + 4Way + Low A U : Plasma + Allergy Filter + 4Way Z : Basic + (A/clean) + 4Way + Low A Look/Color CHASSIS LOOK...
Refrigerant cycle diagram 6RMI0-02A 6. Refrigerant cycle diagram Models : AS-W093B1U1(LS091HSV), AS-W123B1U1(LS121HSV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for sunction air temperature CN-TH1(Indoor) Thermistor for evaporator inlet temperature...
Page 34
6RMI0-02A Refrigerant cycle diagram Models : AS-W163C2U1(LS161HSV), AS-W183C2U2(LS181HSV), AS-W243DGU1(LS240HSV), AS-W363DGU1(LS360HV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for suction air temperature CN-TH1(Indoor) Thermistor for evaporator inlet temperature Thermistor for evaporator outlet temperature...
Page 35
Refrigerant cycle diagram 6RMI0-02A Models : AS-W093ERH1(LA096HV),AS-W123ERH1(LA126HV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for indoor air temperature CN_TH1(INDOOR) Thermistor for evaporating temperature CN_TH2(INDOOR)
Page 36
6RMI0-02A Refrigerant cycle diagram Modes : AS-W1838RH1(LA186HV), AS-W2438RH1(LA246HV), AS-W2435SZ1(LS246HV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for indoor air temperature CN_TH1(INDOOR) CN_TH2(INDOOR) Thermistor for evaporating temperature...
Page 37
Refrigerant cycle diagram 6RMI0-02A Models : AS-W303DGH1(LS306HV) INDOOR UNIT OUTDOOR UNIT LIQUID SIDE 3-WAY VALVE HEAT HEAT EXCHANGE EXCHANGE (EVAPORATOR) (CONDENSER) GAS SIDE REVERSING 3-WAY VALVE ACCUMU VALVE LATOR COOLING Constant Inverter HEATING COMPRESSOR LOC. Description PCB Connector Thermister for indoor air temperature CN-TH1(Indoor) Thermister for indoor pipe(in) temperature Thermister for Indoor pipe(out) temperature...
Sound level 6RMI0-02A ASNW2438RH1(LAN246HV) ASNW123ERH1(LAN126HV) ASNW2435SZ1(LSN246HV) ASNW1838RH1(LAN186HV) Approximate Hearing Threshold 1000 2000 4000 8000 1000 2000 4000 8000 1000 2000 4000 8000 Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) ASNW303DGH1(LSN306HV) ASNW363DGU1(LSN360HV) ASNW303DGU1(LSN307HV) NC-65 NC-65 NC-65...
6RMI0-02A Sound level 11.2 Outdoor Units Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. Center of - Data is valid at nominal operation condition. Outdoor Unit - Reference accoustic pressure 0dB=20Pa.
6RMI0-02A Remote controller 12. Remote controller Wireless Remote Controller The controls will look like the following. ON/OFF BUTTON Used to turn off/on the unit. Signal transmitter OPERATION MODE SELECTION BUTTON Used to select the operation mode. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature.
Page 59
Remote controller 6RMI0-02A The controls will look like the following. Signal transmitter - Optional1 SLEEP MODE AUTO BUTTON Used to set sleep mode auto operation. - Optional2 JET COOL BUTTON Used to start or stop the speed cooling. The Jet Cool operates fan in super high speed in cooling mode.
Page 60
6RMI0-02A Remote controller Wireless Remote Controller Control Display Description panel screen Plasma button*: Purifies the air by removing particles that enter the indoor unit. Display Sleep mode auto button*: Sets the sleep screen mode auto operation. Temperature adjustment buttons: Adjusts the room temperature when cooling and heating.
Page 61
Remote controller 6RMI0-02A 1. START/STOP BUTTON The controls will look like the following. Used to turn off/on the unit. 2. OPERATION MODE SELECTION BUTTON Signal transmitter Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4.
6RMI0-02A Installation 13. Installation Installation Map Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Vinyl tape (Wide) • Apply after carrying out a drainage test. •...
Installation 6RMI0-02A Select the best Location Indoor unit More than 1. There should not be any heat or steam near the unit. 10cm(3.9in) 2. Select a place where there are no obstacles around More than of the unit. 20cm(7.9in) 3. Make sure that condensation drainage can be conveniently routed away.
6RMI0-02A Installation Fixing Installation Plate The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with Installation Plate type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Installation 6RMI0-02A Flaring Work Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure. Cut the pipes and the cable. 1. Use the piping kit accessory or the pipes purchased locally.
6RMI0-02A Installation Check Smooth all round 1. Compare the flared work with the figure by. Inside is shiny without scratches 2. If a flared section is defective, cut it off and do flaring work again. = Improper flaring = Inclined Surface Cracked Uneven damaged...
Installation 6RMI0-02A Installation Information. For right piping. Follow the instruction below. Good case • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. Bad case • Following bending case from right to left directly may cause damage to the tubing. Inverter Single Inverter Single Inverter Single...
6RMI0-02A Installation Installation of Indoor Unit 1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right Installation plate...
Installation 6RMI0-02A If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from sweating (condensation) will not damage furniture or floors. Be sure to install in the sequence of Connecting cable (Conduit), Drain hose and Connecting pipe as the picture below describes.
Page 70
6RMI0-02A Installation Wrap the insulation material around the connecting Insulation material portion. 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap. Cutting Line 2.
Page 71
Installation 6RMI0-02A Outdoor unit 1. Remove the tubing cover from the unit by loosening the screw. Tubing cover 2. Align the center of the pipings and sufficiently tighten the flare nut by hand. 3. Finally, tighten the flare nut with torque wrench until the wrench clicks.
6RMI0-02A Installation Connecting the Cables Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No.
Page 73
Installation 6RMI0-02A Outdoor 1. Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control Terminal block board individually as the following. Over 5mm 2. Secure the cable onto the control board with the (0.2") holder (clamper).
6RMI0-02A Installation Wiring Diagram AS-W186C2U1(LS161HSV) AS-W093B1U1(LS091HSV) AS-W183C2U2(LS181HSV) AS-W123B1U1(LS121HSV) AS-W243DGU1(LS240HSV) AS-W363DGU1(LS360HV) 208/230 VAC AS-W093ERH1(LA096HV), AS-W123ERH1(LA126HV) AS-W1838RH1(LA186HV), AS-W2438RH1(LA246HV) AS-W2435SZ1(LS246HV), AS-W303DGH1(LS306HV) Inverter Single Inverter Single Inverter Single Inverter Single...
Page 75
Installation 6RMI0-02A Power supply cable How to connect wiring to the terminals Strand wire ◼ For strand wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the strand Round terminal wiring about 10mm(3/8in).
6RMI0-02A Installation Checking the Drainage To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain Connecting area drain hose hose of the indoor unit without any leakage and goes out the drain exit. Leakage checking Drain pan...
Installation 6RMI0-02A Forming the Piping In cases where the outdoor unit is Seal small openings installed below the indoor unit around pipings with a perform the following. gum type sealant. 1. Tape the piping, drain hose and connecting cable Connecting cable from down to up.
6RMI0-02A Installation Air Purging The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5.
Installation 6RMI0-02A Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. Liquid side 3. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft Gas side brush to check for leakage of the connecting points of the piping.
6RMI0-02A Installation Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction.
Installation 6RMI0-02A Settlement of outdoor unit Bolt 1. Fix the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount. 2. When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water...
Page 83
Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com All rights reserved The air conditioners manufactured by LG have received ISO9001 certificate for Printed in Korea February/2011 quality assurance and ISO14001 certificate for environmental management system. The specifications, designs, and information in this brochure are subject to...