LG LAN090HSV Data Book

LG LAN090HSV Data Book

Inverter single wall mounted
Hide thumbs Also See for LAN090HSV:

Advertisement

Inverter Single
Wall Mounted
(60Hz/R410A)
6RMI0-02A

Advertisement

Table of Contents
loading

Summary of Contents for LG LAN090HSV

  • Page 1 Inverter Single Wall Mounted (60Hz/R410A) 6RMI0-02A...
  • Page 2: Table Of Contents

    Inverter Single-60Hz (R410A) 1. Models Line up ..................5 2. Nomenclature..................8 3. Specifications ..................9 4. Dimensional drawings .................14 5. Wiring diagrams ...................25 6. Refrigerant cycle diagram ..............32 7. Capacity tables ..................37 8. Capacity coefficient factor..............46 9. Operation range..................49 10. Air flow and temperature distributions(reference data)....51 11.
  • Page 3 6RMI0-01A All models Added N.A models Apr.2010 Change operation range 6RMI0-01B All models Nov.2010 Delete word “ Libero” LAN090HSV / LAN120HSV LAN180HSV / LAN240HSV Add ʼ11 New models LS307HV 6RMI0-02A Mar. 2011 All models Change unit & Etc. Inverter Single...
  • Page 4 6RMI0-02A Test condition of international standard CLASSIFICATION AHAM 9306 5151 210/240 1861.1 DB°C(°F) 27.0 27.0 26.7(80) 26.7(80) 27.0 29.0 Indoor Cooling WB°C(°F) 19.5 19.0 19.4(67) 19.4(67) 19.0 19.0 Capacity DB°C(°F) 35.0 35.0 35.0(95) 35.0(95) 35.0 46.0 Outdoor WB°C(°F) 24.0 24.0 23.9(75) 23.9(75) 24.0...
  • Page 5: General Description

    1) General Wall Mounted Type Units : Units with Simplicity in design. 2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning. 3) Inverter Units : These units are capable of minimising the Power consumption with the unique inverter technology.
  • Page 6: Models Line Up

    Models line up 1. Models Line up 1.1 Indoor Unit kW (kBtu/h) 2.63(9) 3.51(12) 4.68(16) 5.27(18) 7.03(24) 8.79(30) 10.55(36) Indoor Type ASNW093BRU1 ASNW123BRU1 ASNW183CRU1 ASNW243CRU1 (LAN090HSV) (LAN120HSV) (LAN180HSV) (LAN240HSV) ASNW093B1U1 ASNW123B1U1 ASNW163C2U1 ASNW183C2U2 (LSN091HSV) (LSN121HSV) (LSN161HSV) (LSN181HSV) ASNW093ERH1 ASNW123ERH1 ASNW1838RH1 ASNW2438RH1...
  • Page 7 Models line up 6RMI0-02A 1.2 Outdoor Unit ASUW093B1U1(LSU091HSV) ASUW123B1U1(LSU121HSV) Heat pump ASUW093BRU1 (LAU090HSV) ASUW123BRU1 (LAU120HSV) Total capacity index of connectable 2.63 3.51 indoor units kBtu/h Power supply 1Φ / 208~230V / 60Hz Chassis Heat pump ASUW163C2U1(LSU161HSV) ASUW1838UH1(LAU186HV) Total capacity index of connectable 4.68 5.27 indoor units...
  • Page 8 6RMI0-02A Models line up ASUW183C2U2(LSU181HSV) ASUW243DGU1(LSU240HSV) Heat pump ASUW183CRU1 (LAU180HSV) ASUW243CRU1 (LAU240HSV) Total capacity index of connectable 5.27 7.03 indoor units kBtu/h Power supply 1Φ / 208~230V / 60Hz Chassis UE1+ ASUW2435SZ1(LSU246HV), Heat pump ASUW303DGH1(LSU306HV) ASUW2438UH1(LAU246HV) Total capacity index of connectable 7.03 8.79 indoor units...
  • Page 9: Nomenclature

    Nomenclature 6RMI0-02A 2. Nomenclature • Model Number Serial Number Function H : Plasma + (A/chageove) + A/Clean + 4Way + Low A U : Plasma + Allergy Filter + 4Way Z : Basic + (A/clean) + 4Way + Low A Look/Color CHASSIS LOOK...
  • Page 10: Specifications

    6RMI0-02A Specifications 3. Specifications High Efficiency Inverter(#1) Sales Model LS091HSV LS121HSV Models Unit AS-W093B1U1 AS-W123B1U1 Cooling Capacity 0.89~2.64~3.70 0.89~3.28~4.30 Btu/h. 3,070~9,000~12,620 3,070~11,200~14,660 Heating Capacity 0.89~3.17~5.00 0.89~3.90~6.00 Btu/h. 3,070~10,800~17,060 3,070~13,300~20,470 Power Input Cooling Running Current Cooling/Heating 3.0 /3.7 4.2 / 4.9 Starting Current Cooling/Heating 3.0 /3.7...
  • Page 11 Specifications 6RMI0-02A Sales Model LS161HSV LS181HSV LS240HSV Models Unit AS-W163C2U1 AS-W183C2U2 AS-W243DGU1 Cooling Capacity 0.90~4.78~6.00 0.90 ~ 5.33 ~ 8.65 0.90 ~ 6.45 ~ 8.80 Btu/h. 3,070~16,300~20,472 3,070~18,200~29,515 3,070~22,000~30,030 Heating Capacity 0.90~5.92~9.00 0.90 ~ 6.45 ~ 11.40 0.90 ~ 8.09 ~ 11.40 Btu/h.
  • Page 12 6RMI0-02A Specifications Artcool Inverter(#1) Sales Model LA096HV LA126HV LA186HV LA246HV Models Unit AS-W093ERH1 AS-W123ERH1 AS-W1838RH1 AS-W2438RH1 Cooling Capacity 0.89~2.64~3.70 0.89~3.46~4.04 1.76~5.16~5.80 3.87~7.09~7.74 Btu/h. 3,070~9,000~12,620 3,070~11,800~13,800 6,000~17,600~19,800 13,200~24,200~25,500 Heating Capacity 0.89~3.43~5.00 0.89~4.43~5.49 1.40~5.98~6.65 3.37~7.91~8.88 Btu/h. 3,070~11,700~17,060 3,070~15,100~18,720 4,800~20,400~22,700 12,300~27,000~29,700 Power Input Cooling 1157 1814...
  • Page 13 Specifications 6RMI0-02A Artcool Inverter(#2) Sales Model LA090HSV LA120HSV LA180HSV LA240HSV Models Unit AS-W093BRU1 AS-W123BRU1 AS-W183CRU1 AS-W243CRU1 Cooling Capacity 0.89~2.64~3.70 0.89~3.28~4.30 0.90 ~ 5.33 ~ 8.65 0.90 ~ 6.45 ~ 8.80 Btu/h. 3,070~9,000~12,620 3,070~11,200~14,660 3,070~18,200~29,515 3,070~22,000~30,030 Heating Capacity 0.89~3.17~5.00 0.89~3.90~6.00 0.90 ~ 6.45 ~ 11.40 0.90 ~ 8.09 ~ 11.40 Btu/h.
  • Page 14 6RMI0-02A Specifications Inverter(#1) Sales Model LS246HV LS306HV LS360HV LS307HV Models Unit AS-W2435SZ1 AS-W303DGH1 AS-W363DGU1 AS-W303DGU1 Cooling Capacity 3.87~7.15~7.74 3.52~7.74~7.91 0.90~9.70~9.96 0.90 ~ 8.79 ~ 9.46 Btu/h. 13,200~24,400~26,400 12,000~26,400~27,000 3,070/33,100/34,000 3,070 ~ 30,000 ~ 32,300 Heating Capacity 3.37~7.62~8.88 3.52~8.91~9.09 0.90~10.31~11.40 0.90 ~ 9.38 ~ 10.81 Btu/h.
  • Page 15: Dimensional Drawings

    Dimensional drawings 6RMI0-02A 4. Dimensional drawings 4.1 Indoor Units Inverter Single Inverter Single...
  • Page 16 6RMI0-02A Dimensional drawings Inverter Single Inverter Single...
  • Page 17 Dimensional drawings 6RMI0-02A Inverter Single Inverter Single...
  • Page 18 6RMI0-02A Dimensional drawings Inverter Single Inverter Single...
  • Page 19 Dimensional drawings 6RMI0-02A Inverter Single Inverter Single...
  • Page 20 6RMI0-02A Dimensional drawings Inverter Single Inverter Single...
  • Page 21 Dimensional drawings 6RMI0-02A 4.2 Outdoor Units Inverter Single Inverter Single...
  • Page 22 6RMI0-02A Dimensional drawings Inverter Single Inverter Single...
  • Page 23 Dimensional drawings 6RMI0-02A Inverter Single Inverter Single...
  • Page 24 6RMI0-02A Dimensional drawings Inverter Single Inverter Single...
  • Page 25 Dimensional drawings 6RMI0-02A Inverter Single...
  • Page 26: Wiring Diagrams

    6RMI0-02A Wiring diagrams 5. Wiring diagrams 5.1 Indoor units Models: ASNW093B1U1(LSN091HSV), ASNW123B1U1(LSN121HSV) Models: ASNW163C2U1(LSN161HSV), ASNW183C2U2(LSN181HSV) Inverter Single Inverter Single...
  • Page 27 Wiring diagrams 6RMI0-02A Models: ASNW093ERH1(LAN096HV),ASNW123ERH1(LAN126HV) Models: ASNW1838RH1(LAN186HV), ASNW2438RH1(LAN246HV) Inverter Single Inverter Single...
  • Page 28 6RMI0-02A Wiring diagrams Models: ASUW2435SZ1(LSU246HV) Models: ASNW303DGH1(LSN306HV) Inverter Single Inverter Single...
  • Page 29 Wiring diagrams 6RMI0-02A Models: ASNW243DGU1(LS240HSV), ASNW363DGU1(LS360HV) Inverter Single Inverter Single...
  • Page 30 6RMI0-02A Wiring diagrams 6.2 Outdoor units Models: ASUW093B1U1(LSU091HSV), ASUW123B1U1(LSU121HSV) Models: ASUW163C2U1(LSU161HSV) Inverter Single Inverter Single Inverter Single...
  • Page 31 Wiring diagrams 6RMI0-02A Models: ASUW183C2U2(LSU181HSV),ASUW243DGU1(LSU240HSV),ASUW363DGU1(LSU360HV) Models: ASUW093EUH1(LAU096HV),ASUW123EUH1(LAU126HV) Inverter Single Inverter Single Inverter Single...
  • Page 32 6RMI0-02A Wiring diagrams Models: ASUW1838UH1(LAU186HV), ASUW2438UH1(LAU246HV), ASUW2435SZ1(LSU246HV) Models: ASUW303DGH1(LSU306HV) Inverter Single Inverter Single Inverter Single...
  • Page 33: Refrigerant Cycle Diagram

    Refrigerant cycle diagram 6RMI0-02A 6. Refrigerant cycle diagram Models : AS-W093B1U1(LS091HSV), AS-W123B1U1(LS121HSV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for sunction air temperature CN-TH1(Indoor) Thermistor for evaporator inlet temperature...
  • Page 34 6RMI0-02A Refrigerant cycle diagram Models : AS-W163C2U1(LS161HSV), AS-W183C2U2(LS181HSV), AS-W243DGU1(LS240HSV), AS-W363DGU1(LS360HV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for suction air temperature CN-TH1(Indoor) Thermistor for evaporator inlet temperature Thermistor for evaporator outlet temperature...
  • Page 35 Refrigerant cycle diagram 6RMI0-02A Models : AS-W093ERH1(LA096HV),AS-W123ERH1(LA126HV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for indoor air temperature CN_TH1(INDOOR) Thermistor for evaporating temperature CN_TH2(INDOOR)
  • Page 36 6RMI0-02A Refrigerant cycle diagram Modes : AS-W1838RH1(LA186HV), AS-W2438RH1(LA246HV), AS-W2435SZ1(LS246HV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for indoor air temperature CN_TH1(INDOOR) CN_TH2(INDOOR) Thermistor for evaporating temperature...
  • Page 37 Refrigerant cycle diagram 6RMI0-02A Models : AS-W303DGH1(LS306HV) INDOOR UNIT OUTDOOR UNIT LIQUID SIDE 3-WAY VALVE HEAT HEAT EXCHANGE EXCHANGE (EVAPORATOR) (CONDENSER) GAS SIDE REVERSING 3-WAY VALVE ACCUMU VALVE LATOR COOLING Constant Inverter HEATING COMPRESSOR LOC. Description PCB Connector Thermister for indoor air temperature CN-TH1(Indoor) Thermister for indoor pipe(in) temperature Thermister for Indoor pipe(out) temperature...
  • Page 38: Capacity Tables

    6RMI0-02A Capacity tables 7. Capacity tables 7.1 Cooling Capacity AS-W093B1U1(LS091HSV) Outdoor Air Temperature : DB°C(℉) Indoor Air Temperature 20(68) 25(77) 32(89.6) 35(95) WB°C(°F) DB°C(°F) 14(57.2) 20(68) 2.59 2.33 0.37 2.48 2.36 0.39 2.32 2.41 0.52 2.25 2.45 0.58 16(60.8) 22(71.6) 2.75 2.29 0.50...
  • Page 39 Capacity tables 6RMI0-02A AS-W163C2U1(LS161HSV) Outdoor Air Temperature : DB°C(℉) Indoor Air Temperature 20(68) 25(77) 32(89.6) 35(95) WB°C(°F) DB°C(°F) 14(57.2) 20(68) 4.69 3.98 0.72 4.48 4.03 0.75 4.21 4.12 1.01 4.08 4.18 1.12 16(60.8) 22(71.6) 4.98 3.91 0.97 4.77 3.96 0.98 4.49 4.04 1.19...
  • Page 40 6RMI0-02A Capacity tables AS-W243DGU1(LS240HSV) Outdoor Air Temperature : DB°C(℉) Indoor Air Temperature 20(68) 25(77) 32(89.6) 35(95) WB°C(°F) DB°C(°F) 14(57.2) 20(68) 6.32 5.32 0.97 6.05 5.38 1.02 5.68 5.50 1.36 5.51 5.59 1.52 16(60.8) 22(71.6) 6.71 5.23 1.32 6.44 5.29 1.33 6.07 5.40 1.61...
  • Page 41 Capacity tables 6RMI0-02A AS-W123ERH1(LA126HV) Outdoor Air Temperature : DB°C(℉) Indoor Air Temperature 20(68) 25(77) 32(89.6) 35(95) WB°C(°F) DB°C(°F) 14(57.2) 20(68) 3.39 2.37 0.64 3.25 2.40 0.67 3.05 2.45 0.90 2.95 2.49 1.00 16(60.8) 22(71.6) 3.60 2.33 0.87 3.45 2.36 0.88 3.25 2.41 1.06...
  • Page 42 6RMI0-02A Capacity tables AS-W2438RH1(LA246HV) Outdoor Air Temperature : DB°C(℉) Indoor Air Temperature 20(68) 25(77) 32(89.6) 35(95) WB°C(°F) DB°C(°F) 14(57.2) 20(68) 6.95 4.87 1.44 6.65 4.92 1.50 6.24 5.03 2.01 6.05 5.11 2.25 16(60.8) 22(71.6) 7.38 4.78 1.95 7.08 4.83 1.96 6.67 4.94 2.38...
  • Page 43 Capacity tables 6RMI0-02A AS-W303DGH1(LS306HV) Outdoor Air Temperature : DB°C(℉) Indoor Air Temperature 20(68) 25(77) 32(89.6) 35(95) WB°C(°F) DB°C(°F) 14(57.2) 20(68) 7.59 5.70 1.76 7.26 5.77 1.83 6.82 5.89 2.46 6.61 5.99 2.75 16(60.8) 22(71.6) 8.06 5.60 2.38 7.72 5.66 2.40 7.28 5.79 2.91...
  • Page 44: Heating Capacity

    6RMI0-02A Capacity tables 7.2 Heating Capacity AS-W093B1U1(LS091HSV) Outdoor Air Temperature : WB°C(℉) Indoor Air Temperature -15(5) -10(14) -5(23) 0(32) 6(42.8) 10(50) 15(59) DB°C(℉) 16(60.8) 2.38 0.67 2.51 0.65 2.72 0.68 2.90 0.73 3.22 0.78 3.41 0.82 3.70 0.87 18(64.4) 2.36 0.68 2.50 0.67...
  • Page 45 Capacity tables 6RMI0-02A AS-W243DGU1(LS240HSV) Outdoor Air Temperature : WB°C(℉) Indoor Air Temperature -15(5) -10(14) -5(23) 0(32) 6(42.8) 10(50) 15(59) DB°C(℉) 16(60.8) 6.08 1.63 6.40 1.59 6.94 1.66 7.41 1.79 8.22 1.91 8.69 1.99 9.43 2.12 18(64.4) 6.02 1.65 6.39 1.63 6.95 1.71 7.40...
  • Page 46 6RMI0-02A Capacity tables AS-W2438RH1(LA246HV) Outdoor Air Temperature : WB°C(℉) Indoor Air Temperature -15(5) -10(14) -5(23) 0(32) 6(42.8) 10(50) 15(59) DB°C(℉) 16(60.8) 5.95 2.36 6.26 2.31 6.78 2.41 7.24 2.59 8.04 2.78 8.50 2.89 9.22 3.08 18(64.4) 5.89 2.40 6.25 2.36 6.79 2.48 7.24...
  • Page 47: Capacity Coefficient Factor

    Capacity coefficient factor 6RMI0-02A 8. Capacity coefficient factor Cooling 24K,30K 9K,12K 7.5(24.6) 15(49.2) 30(98.4) 50(164) Total Pipe Length[m(ft)] Heating 24K,30K 9K,12K 7.5(24.6) 15(49.2) 30(98.4) 50(164) Total Pipe Length[m(ft)] Inverter Single Inverter Single Inverter Single...
  • Page 48 6RMI0-02A Capacity coefficient factor High Efficiency models Cooling 2(6.6) 7.5(24.6) 20(65.6) Total Pipe Length[m(ft)] Heating 2(6.6) 7.5(24.6) 20(65.6) Total Pipe Length[m(ft)] Inverter Single Inverter Single Inverter Single...
  • Page 49 Capacity coefficient factor 6RMI0-02A Additional Models Max. Pipe Length[m(ft)] Max. Elevation[m(ft)] Refrigerant[g/m(oz/ft)] AS-W093B1U1(LS091HSV) 20(65.6) 10(32.8) 20(0.22) AS-W123B1U1(LS121HSV) 20(65.6) 10(32.8) 20(0.22) AS-W163C2U1(LS161HSV) 20(65.6) 15(49.2) 20(0.22) AS-W183C2U2(LS181HSV) 30(98.4) 15(49.2) 35(0.38) AS-W243DGU1(LS240HSV) 30(98.4) 15(49.2) 35(0.38) AS-W093ERH1(LA096HV) 15(49.2) 7.5(24.6) 20(0.22) AS-W123ERH1(LA126HV) 15(49.2) 7.5(24.6) 20(0.22) AS-W1838RH1(LA186HV) 15(49.2) 7.5(24.6)
  • Page 50: Operation Range

    6RMI0-02A Operation range 9. Operation range Cooling Heating 46(115°F) Operative 43(109°F) Outdoor Unit [°C DB] 24(75°F) Continuous operation Continuous Outdoor Unit operation [°C DB] 18(64°F) Low Ambient Operation -5(23°F) -10(14°F) Operative Operative -10(14°F) -15(5°F) 18(64°F) 32(90°F) 16(61°F) 30(86°F) Indoor Unit [°C DB] Indoor Unit [°C DB] Operative: Intermittent operation due to the operational conditions (indoor/outdoor...
  • Page 51 Operation range 6RMI0-02A Cooling Heating 46(115°F) Operative 43(109°F) Outdoor Unit [°C DB] 24(75°F) Continuous operation Continuous Outdoor Unit operation [°C DB] 18(64°F) Low Ambient -10(14°F) Operation Operative -10(14°F) -15(5°F) 18(64°F) 32(90°F) 16(61°F) 30(86°F) Indoor Unit [°C DB] Indoor Unit [°C DB] Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease.
  • Page 52: Air Flow And Temperature Distributions(Reference Data)

    6RMI0-02A Air flow and temperature distributions(reference data) 10. Air flow and temperature distributions(reference data) 2.63 kW (9kBtu/h) Cooling Heating Discharge angle:45° Discharge angle:50° Air velocity [ft/s] Air velocity [ft/s] 8.9ft 8.9ft 6.6ft 6.6ft 3.3ft 3.3ft 16.4ft 13.1ft 9.8ft 6.6ft 3.3ft 16.4ft 13.1ft 9.8ft...
  • Page 53 Air flow and temperature distributions(reference data) 6RMI0-02A High Efficiency 2.63 kW (9kBtu/h) Cooling Heating Discharge angle:45° Discharge angle:50° Air Velocity [ft/s] Air Velocity [ft/s] 8.9ft 8.9ft 6.6ft 6.6ft 1.2 1.2 1.0 1.0 3.3ft 3.3ft 0.75 0.75 0.75 0.75 0.75 0.75 0.5 0.5 16.4ft 13.1ft...
  • Page 54: Sound Levels

    ASNW093B1U1 (LSN091HSV) ASNW093ERH1 (LAN096HV) ASNW123B1U1 (LSN121HSV) ASNW123ERH1 (LAN126HV) ASNW163C2U1 (LSN161HSV) ASNW1838RH1 (LAN186HV) ASNW183C2U2 (LSN181HSV) ASNW2438RH1 (LAN246HV) ASNW243DGU1 (LSN240HSV) ASNW2435SZ1 (LSN246HV) ASNW093BRU1 (LAN090HSV) ASNW303DGH1 (LSN306HV) ASNW123BRU1 (LAN120HSV) ASNW303DGU1 (LSN307HV) ASNW183CRU1 (LAN180HSV) ASNW363DGU1 (LSN360HV) ASNW243CRU1 (LAN240HSV) Sound Pressure Level ASNW093B1U1(LSN091HSV) ASNW123B1U1(LSN121HSV) ASNW093BRU1(LAN090HSV)
  • Page 55: Sound Level

    Sound level 6RMI0-02A ASNW2438RH1(LAN246HV) ASNW123ERH1(LAN126HV) ASNW2435SZ1(LSN246HV) ASNW1838RH1(LAN186HV) Approximate Hearing Threshold 1000 2000 4000 8000 1000 2000 4000 8000 1000 2000 4000 8000 Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) ASNW303DGH1(LSN306HV) ASNW363DGU1(LSN360HV) ASNW303DGU1(LSN307HV) NC-65 NC-65 NC-65...
  • Page 56: Sound Pressure Level

    6RMI0-02A Sound level 11.2 Outdoor Units Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. Center of - Data is valid at nominal operation condition. Outdoor Unit - Reference accoustic pressure 0dB=20Pa.
  • Page 57 Sound level 6RMI0-02A ASUW2438UH1(LAU246HV) ASUW2435SZ1(LSU246HV) ASUW1838UH1(LAU186HV) ASUW303DGH1(LSU306HV) NC-65 NC-65 NC-65 NC-60 NC-60 NC-60 NC-55 NC-55 NC-55 NC-50 NC-50 NC-50 NC-45 NC-45 NC-45 NC-40 NC-40 NC-40 NC-35 NC-35 NC-35 NC-30 NC-30 NC-30 NC-25 NC-25 NC-25 Approximate Approximate Approximate NC-20 NC-20 NC-20 Hearing Hearing Hearing...
  • Page 58: Remote Controller

    6RMI0-02A Remote controller 12. Remote controller Wireless Remote Controller The controls will look like the following. ON/OFF BUTTON Used to turn off/on the unit. Signal transmitter OPERATION MODE SELECTION BUTTON Used to select the operation mode. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature.
  • Page 59 Remote controller 6RMI0-02A The controls will look like the following. Signal transmitter - Optional1 SLEEP MODE AUTO BUTTON Used to set sleep mode auto operation. - Optional2 JET COOL BUTTON Used to start or stop the speed cooling. The Jet Cool operates fan in super high speed in cooling mode.
  • Page 60 6RMI0-02A Remote controller Wireless Remote Controller Control Display Description panel screen Plasma button*: Purifies the air by removing particles that enter the indoor unit. Display Sleep mode auto button*: Sets the sleep screen mode auto operation. Temperature adjustment buttons: Adjusts the room temperature when cooling and heating.
  • Page 61 Remote controller 6RMI0-02A 1. START/STOP BUTTON The controls will look like the following. Used to turn off/on the unit. 2. OPERATION MODE SELECTION BUTTON Signal transmitter Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4.
  • Page 62: Installation

    6RMI0-02A Installation 13. Installation Installation Map Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Vinyl tape (Wide) • Apply after carrying out a drainage test. •...
  • Page 63: Select The Best Location

    Installation 6RMI0-02A Select the best Location Indoor unit More than 1. There should not be any heat or steam near the unit. 10cm(3.9in) 2. Select a place where there are no obstacles around More than of the unit. 20cm(7.9in) 3. Make sure that condensation drainage can be conveniently routed away.
  • Page 64: Fixing Installation Plate

    6RMI0-02A Installation Fixing Installation Plate The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with Installation Plate type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
  • Page 65: Cut The Pipes And The Cable

    Installation 6RMI0-02A Flaring Work Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure. Cut the pipes and the cable. 1. Use the piping kit accessory or the pipes purchased locally.
  • Page 66: Connecting The Piping

    6RMI0-02A Installation Check Smooth all round 1. Compare the flared work with the figure by. Inside is shiny without scratches 2. If a flared section is defective, cut it off and do flaring work again. = Improper flaring = Inclined Surface Cracked Uneven damaged...
  • Page 67: Good Case

    Installation 6RMI0-02A Installation Information. For right piping. Follow the instruction below. Good case • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. Bad case • Following bending case from right to left directly may cause damage to the tubing. Inverter Single Inverter Single Inverter Single...
  • Page 68: Installation Of Indoor Unit

    6RMI0-02A Installation Installation of Indoor Unit 1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right Installation plate...
  • Page 69: Connecting The Installation Pipe And

    Installation 6RMI0-02A If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from sweating (condensation) will not damage furniture or floors. Be sure to install in the sequence of Connecting cable (Conduit), Drain hose and Connecting pipe as the picture below describes.
  • Page 70 6RMI0-02A Installation Wrap the insulation material around the connecting Insulation material portion. 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap. Cutting Line 2.
  • Page 71 Installation 6RMI0-02A Outdoor unit 1. Remove the tubing cover from the unit by loosening the screw. Tubing cover 2. Align the center of the pipings and sufficiently tighten the flare nut by hand. 3. Finally, tighten the flare nut with torque wrench until the wrench clicks.
  • Page 72: Connecting The Cables

    6RMI0-02A Installation Connecting the Cables Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No.
  • Page 73 Installation 6RMI0-02A Outdoor 1. Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control Terminal block board individually as the following. Over 5mm 2. Secure the cable onto the control board with the (0.2") holder (clamper).
  • Page 74: Wiring Diagram

    6RMI0-02A Installation Wiring Diagram AS-W186C2U1(LS161HSV) AS-W093B1U1(LS091HSV) AS-W183C2U2(LS181HSV) AS-W123B1U1(LS121HSV) AS-W243DGU1(LS240HSV) AS-W363DGU1(LS360HV) 208/230 VAC AS-W093ERH1(LA096HV), AS-W123ERH1(LA126HV) AS-W1838RH1(LA186HV), AS-W2438RH1(LA246HV) AS-W2435SZ1(LS246HV), AS-W303DGH1(LS306HV) Inverter Single Inverter Single Inverter Single Inverter Single...
  • Page 75 Installation 6RMI0-02A Power supply cable How to connect wiring to the terminals Strand wire ◼ For strand wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the strand Round terminal wiring about 10mm(3/8in).
  • Page 76: Checking The Drainage

    6RMI0-02A Installation Checking the Drainage To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain Connecting area drain hose hose of the indoor unit without any leakage and goes out the drain exit. Leakage checking Drain pan...
  • Page 77: Forming The Piping

    Installation 6RMI0-02A Forming the Piping In cases where the outdoor unit is Seal small openings installed below the indoor unit around pipings with a perform the following. gum type sealant. 1. Tape the piping, drain hose and connecting cable Connecting cable from down to up.
  • Page 78: Air Purging

    6RMI0-02A Installation Air Purging The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5.
  • Page 79: Finishing The Job

    Installation 6RMI0-02A Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. Liquid side 3. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft Gas side brush to check for leakage of the connecting points of the piping.
  • Page 80: Test Running

    6RMI0-02A Installation Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction.
  • Page 81: Pump Down

    Installation 6RMI0-02A Settlement of outdoor unit Bolt 1. Fix the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount. 2. When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
  • Page 82: Installation Guide At The Seaside

    3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water...
  • Page 83 Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com All rights reserved The air conditioners manufactured by LG have received ISO9001 certificate for Printed in Korea February/2011 quality assurance and ISO14001 certificate for environmental management system. The specifications, designs, and information in this brochure are subject to...