(6) Dual power feed for use in Europe
Figure 2.22 shows the input power system diagram of PCI_Boxes in a dual power
feed configuration for use in Europe.
Outlet group: Up to 12 A
Number of PCI_Boxes that can be
connected
PRIMEQUEST 480: Up to eight units
PRIMEQUEST 440: Up to four units
CB:
Note1: For high reliability of the redundant configuration, connect Input #0 and
Note2: For information about the circuit breakers on the customer's distribution
Figure 2.22 Input power system diagram of PCI_Boxes in a dual power feed
C122-H001-02EN
Outlet group: Up to 12 A
(*1)
Input#0
Input#1
PCI_Box
#0
Input#0
Input#1
PCI_Box
#1
Input#0
Input#1
PCI_Box
#2
Input#0
Input#1
PCI_Box
#3
Input#0
Input#1
PCI_Box
#4
Input#0
Input#1
PCI_Box
#5
Input#0
Input#1
PCI_Box
#6
Input#0
Input#1
PCI_Box
#7
Circuit Breaker
Input #1 of each PCI_Box to the ACSs on the different system.
panel, see Section 2.6, "Circuit Breaking Characteristics."
configuration for use in Europe
2.3 Power Cable Connections
Power distribution board
(200 VAC) (*2)
ACS#20
#1
16A
#2
ACS#21
#1
16A
#2
Power distribution board
(200 VAC) (*2)
ACS#22
#1
16A
#2
ACS#23
#1
16A
#2
CB
CB
AC power
(system #0)
CB
CB
AC power
(system #1)
2-31