Fujitsu PRIMEQUEST 580A Installation Planning Manual

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

Quick Links

PRIMEQUEST 580A/540A/580/540/480/440
Installation Planning Manual
(errata 2008/09/19 incorporated)
Edition April 2008

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu PRIMEQUEST 580A

  • Page 1 PRIMEQUEST 580A/540A/580/540/480/440 Installation Planning Manual (errata 2008/09/19 incorporated) Edition April 2008...
  • Page 2: Copyright And Trademarks

    There you will also find the addresses of the relevant User Documentation Department. Copyright and Trademarks Copyright © FUJITSU LIMITED and Fujitsu Technology Solutions GmbH 2005 -2009. All rights reserved. Delivery subject to availability; right of technical modifications reserved. All hardware and software names used are trademarks of their respective manufacturers.
  • Page 3 Recycling old computer equipment is already a tradition at Fujitsu Technology Solutions: We have been redeeming and reusing old computer systems for many years now. Even at the design stage, particular emphasis is placed on the reusability of components and materials.
  • Page 4 You can also submit complaints via the internet: http://abgadwda.abg.fsc.net/RLC/ Email: RLC@ts.fujitsu.com In case of a technical problem with Fujitsu Technology Solutions products, or If you have questions on setup or operation: our technical support specialists can offer fast and competent assistance: http://www.ts.fujitsu.com/support/helpdesk.html...
  • Page 5 Dieses Gerät ist entsprechend der europäischen Richtlinie 2002/96/EG über Elektro- und Elektronikaltgeräte (waste electrical and electronic equipment - WEEE) gekennzeichnet. Die Richtlinie gibt den Rahmen für eine EU-weit gültige Rücknahme und Verwertung der Altgeräte vor. This appliance is labelled in accordance with European Directive 2002/96/EG concerning used electrical and electronic appliances (waste electrical and electronic equipment - WEEE).
  • Page 6 2002/96/ (waste electrical and electronic equipment – WEEE). Alat ini bersesuaian dengan garis panduan Eropa 2002/96/EG tentang alat-alat tua elektrik dan elektronik (waste electrical and electronic equipment - WEEE) . Garis panduan tersebut memberi rangka rujukan yang berlaku di seluruh Eropa untuk penerimaan balik dan penggunaan alat-alat tua.
  • Page 7 The effect of temperature on the reliability of IT installations High ambient temperatures and the associated high component temperatures have a deleterious effect on all technical products and thus also on IT installations. The following areas are particularly affected: • Functionality The propagation time of electrical signals increases with temperature.
  • Page 8 The effect of temperature on the reliability of IT installations Installation instructions IT installations are generally designed in such a way that cooling air is drawn in through the door at the front and the warmed air expelled through the back of the system cabi- net.
  • Page 9 The effect of temperature on the reliability of IT installations Sketch of the cooling function Air outlet Ceiling Air intake Floor ( false floor ) U41631-J-Z816-5-76 TEMPERATURE 3...
  • Page 10 The effect of temperature on the reliability of IT installations Checklist for cooling-related malfunctions Temperature of the input air (room temperature) is too high (desired temperature < 25 °C, maximum value < 32 °C) Measuring points The temperature should be measured at two places within the air intake area at the front of the system: 1.
  • Page 11: About This Product

    Keep this manual handy for further reference. Fujitsu and Fujitsu Technology Solutions make every effort to prevent users and bystanders from being injured or from suffering damage to their property. Use the product according to this manual.
  • Page 12 RADIO FREQUENCY INTERFERENCE STATEMENT The following notice is for EU users only. WARNING: This is a product which meets Class A of EN55022. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
  • Page 13 (™) or registered trademark (®) symbols. The contents of this manual shall not be disclosed in any way or reproduced in any media without the express written permission of Fujitsu Limited or Fujitsu Technology Solutions GmbH. All Rights Reserved, Copyright FUJITSU LIMITED and Fujitsu Technology...
  • Page 15: Revision History

    Revision History (1/3) Revised section Edition Date Details (Added/ Deleted/ Altered) ⎯ ⎯ 2005-07-11 2005-09-15 Entire manual (Altered) • Technical brush-up • Modification of the manual title • Addition of PRIMEQUEST series Section 2.2.1 (1) • Modification of the concept (Altered/Added) of units operational grouping •...
  • Page 16 (2/3) Revised section Edition Date Details (Added/ Deleted/ Altered) 2006-04-17 Section 1.3 (Altered) • Modification of model names and addition of remarks for model names Section 2.2.2 (Altered) • Modification of the connector type of Gigabit Ethernet card (optical) in Figure 2.3 Section 2.2.3 (Altered)
  • Page 17 • Correction of the order codes of UPS cables Fujitsu Technology Solutions adapts text and figures, substitutes the order number of the manual, adds Fujitsu Technology Solutions’ order numbers in manual references, changes the description where the PRIMEQUEST manuals are available, substitutes the...
  • Page 19 Preface This manual describes requirements and concepts for installation and facility planning for the PRIMEQUEST 580A, 540A*, 580, 540, 480, and 440. Installation and facility planning should be performed together with your assigned Fujitsu or Fujitsu Technology Solutions representatives according to the instructions provided in this manual.
  • Page 20: Conventions For Alert Messages

    The manuals listed below are related to this manual. Before installing the equipment, first read the supplied printed manual PRIMEQUEST 500A/500/400 Series Installation Manual (U41632-J-Z816-x-76, adapted Fujitsu manual C122-E001EN) and see the related manuals: SPARC Enterprise/PRIMEQUEST Series Common Installation Planning Manual...
  • Page 21: Table Of Contents

    2.4 Input Power Supply Unit Connections ......2-38 2.4.1 PRIMEQUEST 580A/540A/580/540/480/440 main unit ..2-38 2.4.2 Cables between PCI_Box and ACS in the Extended I/O Cabinet .
  • Page 22 Contents CHAPTER 3 Precautions Pertaining to Delivery and Installation ..3.1 Elevator Load Requirements ........3.2 Earthquake Preparedness Measures .
  • Page 23 1-10 Figure 1.9 PRIMEQUEST 580A/540A/580/540/480/440 floor plan ..1-34 Figure 1.10 Extended Power Cabinet floor plan ..... . .
  • Page 24 Figure 2.5 External interface connection ports in the PRIMEQUEST 580A/580/480 main unit ....2-14 Figure 2.6 External interface ports in the KVMH ..... . 2-15 Figure 2.7...
  • Page 25 ......2-28 Figure 2.23 Input power system diagram for the PRIMEQUEST 580A/580/480 and Extended Power Cabinet (dual power feed configuration) . .
  • Page 26 Contents Figure 3.7 Opening on the free-access floor when a seismic-isolation leveling foot is used ......... . viii U41631-J-Z816-5-76...
  • Page 27 Cable list (LAN and other device connections) ....Table 2.3 AC cable specifications for the PRIMEQUEST 580A/540A/580/540/480/440 main unit ..2-38 Table 2.4 Specifications of the AC cables used between a PCI_Box and ACS in the Extended I/O Cabinet .
  • Page 29: Chapter 1 Installation Reference

    (maximum of 16 CPUs) and up to four IO Units Extended Power Power supply cabinet that is connected to Cabinet the PRIMEQUEST 580A/540A/580/540/ 480/440 main unit for dual power feed configuration Extended I/O Cabinet Cabinet that contains PCI_Boxes and that is connected to the PRIMEQUEST 580/...
  • Page 30 PCI Express unit has two PCI Express slots. PCI Express units can be connected to only the PRIMEQUEST 580A/540A/ 580/540 main unit. Up to 16 units can be connected to the PRIMEQUEST 580A/580 main unit, and up to 8 units can be connected to the PRIMEQUEST 540A/540 main unit.
  • Page 31: Figure 1.1 Configuration Of The Primequest 580A/540A/580/540/480/440

    1.1 Equipment Configuration Figure 1.1 Configuration of the PRIMEQUEST 580A/540A/580/540/480/440 main unit U41631-J-Z816-5-76...
  • Page 32: Figure 1.2 Configuration Of The Primequest 580A/540A/580/540/480/440

    CHAPTER 1 Installation Reference Figure 1.2 Configuration of the PRIMEQUEST 580A/540A/580/540/480/440 main unit and the Extended I/O Cabinet U41631-J-Z816-5-76...
  • Page 33: Figure 1.3 Configuration Of The Primequest 580/480 Main Unit And The Extended Power Cabinet

    1.1 Equipment Configuration Figure 1.3 Configuration of the PRIMEQUEST 580/480 main unit and the Extended Power Cabinet U41631-J-Z816-5-76...
  • Page 34: Figure 1.4 Configuration Of The Primequest 580/480 Main Unit, The Extended I/O Cabinet, And The Extended Power Cabinet

    CHAPTER 1 Installation Reference Figure 1.4 Configuration of the PRIMEQUEST 580/480 main unit, the Extended I/O Cabinet, and the Extended Power Cabinet U41631-J-Z816-5-76...
  • Page 35: Figure 1.5 External View Of The Primequest 580A/540A/580/540/480/440

    1.2 Views of the Units Views of the Units The following figures show different views of the units: External view of the PRIMEQUEST 580A/540A/580/540/480/440 main unit (Figure 1.5) External view of the Extended Power Cabinet (Figure 1.6) External view of the Extended I/O Cabinet (Figure 1.7)
  • Page 36: Figure 1.6 External View Of The Extended Power Cabinet

    CHAPTER 1 Installation Reference Figure 1.6 External view of the Extended Power Cabinet U41631-J-Z816-5-76...
  • Page 37: Figure 1.7 External View Of The Extended I/O Cabinet

    1.2 Views of the Units Figure 1.7 External view of the Extended I/O Cabinet U41631-J-Z816-5-76...
  • Page 38: Figure 1.8 External View Of The Pci_Box

    CHAPTER 1 Installation Reference Figure 1.8 External view of the PCI_Box 1-10 U41631-J-Z816-5-76...
  • Page 39: Installation Specifications

    1.3 Installation Specifications Installation Specifications The following tables list the installation specifications for the units: PRIMEQUEST 580A main unit installation specifications (Model name: MC5C0P3a1x) (Table 1.2) PRIMEQUEST 540A main unit installation specifications (Model name: MC4C0P3a1x) (Table 1.3) PRIMEQUEST 580 main unit installation specifications (Model name: MC5B0P2a1x) (Table 1.4)
  • Page 40: Table 1.2 Primequest 580A Main Unit Installation Specifications (Model Name: Mc5C0P3A1X)

    CHAPTER 1 Installation Reference Table 1.2 PRIMEQUEST 580A main unit installation specifications (Model name: MC5C0P3a1x) Item Value Dimensions Width 738 (29.06) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 730 (1608) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] (*3)
  • Page 41 1.3 Installation Specifications Item Value 200 to 240 VAC ± 10 % Power supply Input voltage tolerance and No. of phases 1φ Frequency and tolerance 50/60 Hz +2/-4 Hz Maximum Operating Five SBs or five IO 10,900 W/ power Units or more 11,000 VA consumption/ Four SBs or less and...
  • Page 42 CHAPTER 1 Installation Reference There must be no condensation. The temperature requirement depends on the installation altitude. - 5 to 35 °C (41 to 95.0 °F) [if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)] - 5 to 33 °C (41 to 91.4 °F) [if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)] - 5 to 32 °C (41 to 89.6 °F)
  • Page 43: Table 1.3 Primequest 540A Main Unit Installation Specifications

    1.3 Installation Specifications Table 1.3 PRIMEQUEST 540A main unit installation specifications (Model name: MC4C0P3a1x) Item Value Dimensions Width 738 (29.06) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 605 (1332) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] (*3) 22680 (21496) Exhaust air flow (*10) With fans operating at...
  • Page 44 CHAPTER 1 Installation Reference This value does not include any projection. Value for the case with the maximum number of optional units allowed installed. The weight of the unit based on the equipment configuration can be calculated from the following formula: Unit weight = 464 + (12 x E) + (15 x F) + (1 x G) + (26 x H) When 32-GB memory is mounted, the formula is as follows: Unit weight = 464 + (13 x E) + (15 x F) + (1 x G) + (10 x H)
  • Page 45: Table 1.4 Primequest 580 Main Unit Installation Specifications (Model Name: Mc5B0P2A1X)

    1.3 Installation Specifications Table 1.4 PRIMEQUEST 580 main unit installation specifications (Model name: MC5B0P2a1x) Item Value Dimensions Width 738 (29.06) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 730 (1608) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] (*3) 39240 (37192) Exhaust air flow (*10) With fans operating at...
  • Page 46 CHAPTER 1 Installation Reference Item Value 200 to 240 VAC ± 10 % Power supply Input voltage tolerance and No. of phases 1φ Frequency and tolerance 50/60 Hz +2/-4 Hz Maximum Operating Five SBs or five IO 10,900 W/ power Units or more 11,000 VA consumption/...
  • Page 47 1.3 Installation Specifications There must be no condensation. The temperature requirement depends on the installation altitude. - 5 to 35 °C (41 to 95.0 °F) [if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)] - 5 to 33 °C (41 to 91.4 °F) [if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)] - 5 to 32 °C (41 to 89.6 °F) [if installed at an altitude of 2000 to 2500 m (6561.6 to 8202 ft)]...
  • Page 48: Table 1.5 Primequest 540 Main Unit Installation Specifications (Model Name: Mc4B0P2A1X)

    CHAPTER 1 Installation Reference Table 1.5 PRIMEQUEST 540 main unit installation specifications (Model name: MC4B0P2a1x) Item Value Dimensions Width 738 (29.06) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 605 (1332) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] (*3) 22680 (21496) Exhaust air flow (*10) With fans operating at...
  • Page 49 1.3 Installation Specifications This value does not include any projection. Value for the case with the maximum number of optional units allowed installed. The weight of the unit based on the equipment configuration can be calculated from the following formula: Unit weight = 464 + (12 x E) + (15 x F) + (1 x G) + (26 x H) When 32-GB memory is mounted, the formula is as follows: Unit weight = 464 + (13 x E) + (15 x F) + (1 x G) + (10 x H)
  • Page 50: Table 1.6 Primequest 480 Main Unit Installation Specifications (Model Name: Mc5A0P1A1X)

    CHAPTER 1 Installation Reference Table 1.6 PRIMEQUEST 480 main unit installation specifications (Model name: MC5A0P1a1x) Item Value Dimensions Width 738 (29.06) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 720 (1584) Air conditioning Maximum heat dissipation Five SBs or five IO 36600 (34689) (*9)
  • Page 51 1.3 Installation Specifications Item Value Power supply Maximum Operating Five SBs or five IO 10,600 W/ power Units or more 10,700 VA consumption/ Four SBs or less and 5,890 W/ apparent four IO Units or less 6,000 VA power (*7) Not operating Five SBs or five IO 300 VA Units or more...
  • Page 52 CHAPTER 1 Installation Reference The temperature requirement depends on the installation altitude. - 5 to 35 °C (41 to 95.0 °F) [if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)] - 5 to 33 °C (41 to 91.4 °F) [if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)] - 5 to 32 °C (41 to 89.6 °F) [if installed at an altitude of 2000 to 2500 m (6561.6 to 8202 ft)]...
  • Page 53: Table 1.7 Primequest 440 Main Unit Installation Specifications

    1.3 Installation Specifications Table 1.7 PRIMEQUEST 440 main unit installation specifications (Model name: MC4A0P1a1x) Item Value Dimensions Width 738 (29.06) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 600 (1320) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] (*8) 20500 (19430) Exhaust air flow With fans operating at...
  • Page 54 CHAPTER 1 Installation Reference This value does not include any projection. Value for the case the maximum allowable number of optional units is mounted. The weight of the unit based on the equipment configuration can be calculated from the following formula: Unit weight = 464 + (12 x E) + (15 x F) + (1 x G) + (26 x H) E = Number of SBs mounted: From a minimum of one to a...
  • Page 55: Table 1.8 Extended Power Cabinet Installation Specifications

    1.3 Installation Specifications Table 1.8 Extended Power Cabinet installation specifications (Model name: MC-57DPa1x, MC-77UGDax) Item Value Dimensions Width 300 (11.81) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 300 (660) Air conditioning Maximum heat dissipation Five SBs or five IO 5500 (5213) [kJ/Hr (BTU/h)]...
  • Page 56 CHAPTER 1 Installation Reference Item Value 200 to 240 VAC ± 10 % Power supply Input voltage tolerance and No. of phases 1φ Frequency and tolerance 50/60 Hz +2/-4 Hz Maximum Operating Five SBs or five IO 10,900 W/11,000 VA power Units or more (For PRIMEQUEST...
  • Page 57 1.3 Installation Specifications The temperature requirement depends on the installation altitude. - 5 to 35 °C (41 to 95.0 °F) [if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)] - 5 to 33 °C (41 to 91.4 °F) [if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)] - 5 to 32 °C (41 to 89.6 °F) [if installed at an altitude of 2000 to 2500 m (6561.6 to 8202 ft)]...
  • Page 58: Table 1.9 Extended I/O Cabinet Installation Specifications (Model Name: Mc-77Rka1X, Mc-87Rka1X)

    CHAPTER 1 Installation Reference Table 1.9 Extended I/O Cabinet installation specifications (Model name: MC-77RKa1x, MC-87RKa1x) Item Value Dimensions Width 680 (29.77) [mm (in.)] Depth (*1) 1100 (43.31) Height 1800 (70.87) Weight [kg (lb)] (*2) 600 (1320) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] 20500 (19430) Exhaust air flow (*8) With fans operating at...
  • Page 59 1.3 Installation Specifications Item Value 200 to 240 VAC ± 10 % Power supply Input voltage tolerance and No. of phases 1φ Frequency and tolerance 50/60 Hz +2/-4 Hz Maximum power Operating 5,890 W/6,000 VA consumption/apparent power Not operating 200 VA Power factor 0.9 or more Inrush current [A] [Inrush duration] (*7)
  • Page 60: Table 1.10 Pci_Box Installation Specifications (Model Name: Mc-07Pba1X)

    CHAPTER 1 Installation Reference Table 1.10 PCI_Box installation specifications (Model name: MC-07PBa1x) Item Value Dimensions Width 482 (18.98) [mm (in.)] Depth (*1) 768 (30.24) Height 174 (6.85) Weight [kg (lb)] (*2) 42 (92) Air conditioning Maximum heat dissipation [kJ/Hr (BTU/h)] 2550 (2416.9) Exhaust air flow (*8) With fans operating at...
  • Page 61 1.3 Installation Specifications This value does not include any projection. Value for the case the maximum allowable number of optional units is mounted. There must be no condensation. The temperature requirement depends on the installation altitude. - 5 to 35 °C (41 to 95.0 °F) [if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)] - 5 to 33 °C (41 to 91.4 °F) [if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)]...
  • Page 62: Equipment Floor Plan

    29 (1.1) 680 (26.8) 738 (29.0) Front [Legend] : Interface cable hole Unit: mm (in.) : Inlet air area : Leveling pad : Caster * This is a top view of the unit. Figure 1.9 PRIMEQUEST 580A/540A/580/540/480/440 floor plan 1-34 U41631-J-Z816-5-76...
  • Page 63: Figure 1.10 Extended Power Cabinet Floor Plan

    1.4 Equipment Floor Plan (3.5 (4.7) 250.75 (9.9) 255 (10.0) 300 (11.8) 29 (1.1) 329 (13.0) Front Unit: mm (in.) [Legend] : Interface cable hole : Inlet air area : Leveling pad : Caster * This is a top view of the unit. Figure 1.10 Extended Power Cabinet floor plan U41631-J-Z816-5-76 1-35...
  • Page 64: Figure 1.11 Extended I/O Cabinet Floor Plan

    CHAPTER 1 Installation Reference 590 (23.2) 45 (1.8) 519 (20.4) 101 (4.0) 478 (18.8) 680 (26.8) 709 (27.9) (1.1) [Legend] Front : Interface cable hole Unit: mm (in.) : Inlet air area : Leveling pad : Caster * This is a top view of the unit. Figure 1.11 Extended I/O Cabinet floor plan 1-36 U41631-J-Z816-5-76...
  • Page 65: Figure 1.12 Service Area For The Primequest 580A/540A/580/540/480/440

    Service area for the PRIMEQUEST 580A/540A/580/540/480/440 main unit (Figure 1.12) Service area for the PRIMEQUEST 580A/540A/580/540/480/440 main unit and the Extended I/O Cabinet (Figure 1.13) Service area for the PRIMEQUEST 580/480 main unit and the Extended Power Cabinet (Figure 1.14)
  • Page 66: Figure 1.13 Service Area For The Primequest 580A/540A/580/540/480/440

    Service area Front Unit: mm (in.) Installation area: 3.9 m (including service area) * This is a top view of the unit. Figure 1.13 Service area for the PRIMEQUEST 580A/540A/580/540/480/440 main unit and the Extended I/O Cabinet 1-38 U41631-J-Z816-5-76...
  • Page 67: Figure 1.14 Service Area For The Primequest 580/480 Main Unit

    1.5 Equipment Installation Patterns and Service Area 1080 (42.5) 38 (1.5) 1042 (41.6) Service area Extended PRIMEQUEST Power 580A/580/480 Cabinet main unit Service area Front Unit: mm (in.) Installation area: 2.9 m (including service area) * This is a top view of the unit. Figure 1.14 Service area for the PRIMEQUEST 580/480 main unit and the Extended Power Cabinet U41631-J-Z816-5-76...
  • Page 68: Figure 1.15 Service Area For The Primequest 580/480 Main Unit, The Extended I/O Cabinet, And The Extended Power Cabinet

    CHAPTER 1 Installation Reference 1726 (67.9) Service area Extended PRIMEQUEST Extended Power 580A/580/480 I/O Cabinet Cabinet main unit Service area Front Unit: mm (in.) Installation area: 4.7 m (including service area) * This is a top view of the unit. Figure 1.15 Service area for the PRIMEQUEST 580/480 main unit, the Extended I/O Cabinet, and the Extended Power Cabinet 1-40...
  • Page 69: Floor Plan Of Openings In Floor And Template

    1.6 Floor Plan of Openings in Floor and Template Floor Plan of Openings in Floor and Template This section provides the floor plan for openings in the floor. Templates are provided Section 1.6.2, "Templates" to allow you to plan your configuration before moving equipment.
  • Page 70: Figure 1.16 Symbols Used In Floor Plans And Templates

    CHAPTER 1 Installation Reference • Symbols used Figure 1.16 shows the symbols used in the figures for floor plan openings and in the template. Leveling pad Front Service area Figure 1.16 Symbols used in floor plans and templates 1-42 U41631-J-Z816-5-76...
  • Page 71: Figure 1.17 Floor Openings For The Primequest 580A/540A/580/540/480/440

    This section describes the floor plans for openings to accommodate each unit. Floor openings for the PRIMEQUEST 580A/540A/580/540/480/440 main unit (Figure 1.17) Floor openings for the PRIMEQUEST 580A/540A/580/540/480/440 main unit and the Extended I/O Cabinet (Figure 1.18) Floor openings for the PRIMEQUEST 580/480 main unit and the Extended Power Cabinet (Figure 1.19)
  • Page 72: Main Unit

    50% 450x450 (17.7x17.7) Front 81.25 (3.2) 575.5 (22.7) 81.25 (3.2) Unit: mm (in.) [Legend] : Interface cable hole : Inlet air area : Leveling pad : Caster Figure 1.17 Floor openings for the PRIMEQUEST 580A/540A/580/540/480/440 main unit 1-44 U41631-J-Z816-5-76...
  • Page 73: Main Unit And The Extended I/O Cabinet

    575.5 (22.7) 81.25 (3.2) 101.25 (4.0) [Legend] Unit: mm (in.) : Interface cable hole : Inlet air area : Leveling pad : Caster Figure 1.18 Floor openings for the PRIMEQUEST 580A/540A/580/540/480/440 main unit and the Extended I/O Cabinet U41631-J-Z816-5-76 1-45...
  • Page 74: Figure 1.19 Floor Openings For The Primequest 580/480 Main Unit And The Extended Power Cabinet

    CHAPTER 1 Installation Reference 1080 (42.5) 38 (1.5) 1042 (41.0) 299 (11.8) 69 (2.7) 600 (23.6) 74 (2.9) Floorboard with small holes 194 (7.6) 129 (5.1) and open are of 50% 450x450 (17.7x17.7) 120x350 (4.7x13.8) 100x100 (3.9x3.9) 200x350 (7.9x13.8) 150x350 (5.9x13.8) Front Floorboard with small holes and open are of 50%...
  • Page 75: Figure 1.20 Floor Openings For The Primequest 580/480 Main Unit, The Extended I/O Cabinet, And The Extended Power Cabinet

    1.6 Floor Plan of Openings in Floor and Template 1726 (68.0) 74 (2.9) 590 (23.2) 89 (3.5) 600 (23.6) 299 (11.8) 74 (2.9) 89 (3.5) 100 (3.9) 689 (27.1) 129 (5.1) Floorboard with small holes and open are of 50% 450x450 (17.7x17.7) 120x350 (4.7x13.8) 150x250 (5.9x9.8)
  • Page 76: Figure 1.21 Template For The Primequest 580A/540A/580/540/480/440

    Fit to page on the Print dialog box. Template for the PRIMEQUEST 580A/540A/580/540/480/440 main unit (Figure 1.21) Template for the PRIMEQUEST 580A/540A/580/540/480/440 main unit and the Extended I/O Cabinet (Figure 1.22) Template for the PRIMEQUEST 580/480 and the Extended Power Cabinet (Figure 1.23)
  • Page 77: Figure 1.23 Template For The Primequest 580/480 And The Extended Power

    1.6 Floor Plan of Openings in Floor and Template Front Figure 1.23 Template for the PRIMEQUEST 580/480 and the Extended Power Cabinet Front Figure 1.24 Template for the PRIMEQUEST 580/480 main unit, the Extended I/O Cabinet, and the Extended Power Cabinet U41631-J-Z816-5-76 1-49...
  • Page 78: Cooling Air And Exhaust Flows

    CHAPTER 1 Installation Reference Cooling Air and Exhaust Flows This section explains the cooling air and exhaust flows of each cabinet. Cooling air and exhaust flows of the PRIMEQUEST 580A/540A/580/540/480/440 main unit (Figure 1.25) Cooling air and exhaust flows of the Extended Power Cabinet (Figure 1.26)
  • Page 79: Figure 1.26 Cooling Air And Exhaust Flows Of The Extended Power Cabinet

    1.7 Cooling Air and Exhaust Flows Input section (Power supply section Front view Right-side view : Intake air : Exhaust air Figure 1.26 Cooling air and exhaust flows of the Extended Power Cabinet PCI_Box#7 PCI_Box#6 PCI_Box#5 PCI_Box#4 PCI_Box#3 PCI_Box#2 PCI_Box#1 PCI_Box#0 Left-side view Front view...
  • Page 80: Figure 1.28 Cooling Air And Exhaust Flows Of The Pci_Box

    CHAPTER 1 Installation Reference Figure 1.28 Cooling air and exhaust flows of the PCI_Box 1-52 U41631-J-Z816-5-76...
  • Page 81: Chapter 2 Connection Reference

    CHAPTER 2 Connection Reference This chapter provides cable connection diagrams and lists of the applicable cables. Connection Overview Figure 2.1 shows an overview of equipment cable connections: U41631-J-Z816-5-76...
  • Page 82: Figure 2.1 Equipment Cable Connections (1/2)

    CHAPTER 2 Connection Reference PRIMEQUEST 580A/540A/580/540/480/440 main unit IOU(Note 1) (x0-8:PRIMEQUEST 580A/580/480) (x0-4:PRIMEQUEST 540A/540/440) PCI card type: - LAN interface PCI-X card (x4) - SCSI interface - Fibre Channel BMC module (x2) USB1.1/2.0 equipment USB2.0 (x2) COM (x1) Console Ultra320 SCSI port (x2)
  • Page 83 Note 3: GTHB is supported only in the PRIMEQUEST 580A/540A/580/540. Note 4: GSWB and GTHB cannot be mounted together. Note 5: Up to 16 PEXUs can be connected to the PRIMEQUEST 580A/580 main unit. Up to eight PEXUs can be connected to the PRIMEQUEST 540A/540 main unit.
  • Page 84: Signal Cable Connections

    This section provides diagrams of signal-cable connections, lists of applicable cables, and notes on cabling. Basic interfaces and peripherals (Section 2.2.1) LAN and other device connections (Section 2.2.2) Notes on cabling PRIMEQUEST 580A/540A/580/540/480/440 (Section 2.2.3) Details of cable connection ports (Section 2.2.4) 2.2.1 Basic interfaces and peripherals Figure 2.2...
  • Page 85: Connections (Basic Interfaces And Peripherals)

    2.2 Signal Cable Connections (1) Cable connection diagram Remarks:The number in parenthesis corresponds to the number of the cables in Table 2.1. Figure 2.2 PRIMEQUEST 580A/540A*/580/540/480/440 interface cable connections (basic interfaces and peripherals) *: not supported by Fujitsu Technology Solutions U41631-J-Z816-5-76...
  • Page 86: Table 2.1 Cable List (Basic Interface And Peripherals)

    (2) Cable list When determining the total length of the external interface cable to be connected to the PRIMEQUEST 580A/540A/580/540/480/440, allow for an extra length of cable for pulling out the units. Table 2.1 Cable list (basic interface and peripherals)
  • Page 87 2.2 Signal Cable Connections Length Outside Name Order code Packaging Japan Japan [m (ft.)] (7) SCSI cable Optional: Select 5 or 10 m. 5 (16) DCBL-SCN05 VHDCI 68-pin, male to 10 (33) HIDEC 68-pin, male DCBL-SCN10 (8) RS232C cable (Dsub 9 Pin-9 Pin, cross FMV-CBL501 1.5 (5) cable)
  • Page 88: Lan And Other Device Connections

    Units or in PCI cassettes of PCI_Boxes. Remarks:The number in parenthesis corresponds to the number of the cables in Table 2.2. Figure 2.3 PRIMEQUEST 580A/540A*/580/540/480/440 cable connections (LAN and other device connections) *: not supported by Fujitsu Technology Solutions U41631-J-Z816-5-76...
  • Page 89: Table 2.2 Cable List (Lan And Other Device Connections)

    (2) Cable list When determining the total length of the external interface cable to be connected to the PRIMEQUEST 580A/540A/580/540/480/440, allow for an extra length of cable for pulling out the units. Table 2.2 Cable list (LAN and other device connections)
  • Page 90 CHAPTER 2 Connection Reference Outside Length Name Order code Japan Packaging Japan [m (ft.)] Twisted pair cable TPCBL-B005 Optional: Select 5, 10, 15, 5 (16) (category 5 UTP cable) 30, 50, or 100 m. TPCBL-B010 10 (33) This cable is required if TPCBL-B015 15 (49) 100Base-TX or 10Base-T...
  • Page 91: Notes On Cabling Primequest 580A/540A/580/540/480/440

    2.2 Signal Cable Connections 2.2.3 Notes on cabling PRIMEQUEST 580A/540A/580/540/480/440 When determining the total length of the cable to be connected to the PRIMEQUEST 580A/540A/580/540/480/440, allow for an extra length of cable for pulling out the units. Use a sheathless optical cable for the Fibre Channel cable. (If the sheath Fibre Channel cable has been laid, connect a sheathless optical Fibre Channel cable with an adapter (DCBL-FCE02 (SC-LC: 2m (6.6 ft.)), DCBL-FCE05 (SC-LC: 5m...
  • Page 92: Primequest 540A/540/440 Main Unit

    External interface connection ports in the PRIMEQUEST 540A/540/440 main unit (Figure 2.4) External interface connection ports in the PRIMEQUEST 580A/580/480 main unit (Figure 2.5) Units in the PRIMEQUEST 580A/540A/580/540/480/440 main unit (Figure 2.6...
  • Page 93 Note: GTHB is supported only in the PRIMEQUEST 540A*/540. Remark: The above unit contains a Dual Power Feed Option. Figure 2.4 External interface connection ports in the PRIMEQUEST 540A/540/440 main unit *: not supported by Fujitsu Technology Solutions U41631-J-Z816-5-76 2-13...
  • Page 94 Note: GTHB is supported only in the PRIMEQUEST 580A/580. Remarks: The figure shows an example of the PRIMEQUEST system with an additional power supply option mounted. Figure 2.5 External interface connection ports in the PRIMEQUEST 580A/580/480 main unit 2-14 U41631-J-Z816-5-76...
  • Page 95: Figure 2.6 External Interface Ports In The Kvmh

    2.2 Signal Cable Connections (3) Units in the PRIMEQUEST 580A/540A/580/540/480/440 main unit KVMH Figure 2.6 External interface ports in the KVMH CPCB Figure 2.7 External interface ports in the CPCB MMBH Figure 2.8 External interface ports in the MMBH U41631-J-Z816-5-76...
  • Page 96: Figure 2.9 External Interface Ports In The Gswb-1G

    CHAPTER 2 Connection Reference GSWB-1G Figure 2.9 External interface ports in the GSWB-1G GSWB-XG Figure 2.10 External interface ports in the GSWB-XG GTHB (PRIMEQUEST 580A/540A*/580/540) Figure 2.11 External interface ports in the GTHB *: not supported by Fujitsu Technology Solutions 2-16 U41631-J-Z816-5-76...
  • Page 97: Figure 2.12 External Interface Ports In The Iouh

    2.2 Signal Cable Connections IOUH USB (USB1.1/2.0) (2.4) (1.1) BMC module (BMM) (0.7) PCIU interface#3 PCIU interface#2 PCIU interface#1 (2.3) (1.1) RS-232C (COM) PCIU interface#0 PCI-X slot#2 PCI-X slot#3 PCI-X slot#0 PCI-X slot#1 VHDCI (Ultra320SCSI) 15.2 (0.6) (0.2) Unit: mm (in.) (2.2) (1.3) Figure 2.12 External interface ports in the IOUH...
  • Page 98: Figure 2.13 Input Cable Connection Ports In The Extended Power Cabinet

    CHAPTER 2 Connection Reference (4) Input cable connection ports in the Extended Power Cabinet 129 (5.1) Input#10 Input#11 Input#12 Input#13 Input#14 Front view (with the door open) Rear view (with the door open) Unit: mm (in.) Figure 2.13 Input cable connection ports in the Extended Power Cabinet 2-18 U41631-J-Z816-5-76...
  • Page 99: (Connected To Primequest 540A/540/440 Unit)

    2.2 Signal Cable Connections (5) Input cable connection ports in the Extended I/O Cabinet (connected to PRIMEQUEST 540A/540/440 unit) Notes: The 2U space at the bottom of the cabinet is required for use as cable processing space. Keep this space open. Do not mount any PCI_Box in it. A blank panel is installed where a PCI_Box is not mounted.
  • Page 100: (Connected To Primequest 580A/580/480 Unit)

    A blank panel is installed where a PCI_Box is not mounted. If a PCI_Box has not been added here, be sure to keep the blank panel installed to ensure normal cooling of the other PCI_Boxes. Figure 2.15 Input cable connection ports in the Extended I/O Cabinet (connected to PRIMEQUEST 580A/580/480 unit) 2-20 U41631-J-Z816-5-76...
  • Page 101: Figure 2.16 External Interface Ports In The Pci_Box

    2.2 Signal Cable Connections (7) External interface ports in the PCI_Box Figure 2.16 External interface ports in the PCI_Box U41631-J-Z816-5-76 2-21...
  • Page 102: Power Cable Connections

    This section provides diagrams of the input power circuit connection for the PRIMEQUEST 580A/540A/580/540/480/440 and the PCI_Box. Input power system diagram for the PRIMEQUEST 540A/540/440 (Section 2.3.1) Input power system diagram for the PRIMEQUEST 580A/580/480 (Section 2.3.2) Input power system diagram for the Extended I/O Cabinet and the PCI_Box (Section 2.3.3)
  • Page 103: Standard Configuration

    2.3 Power Cable Connections 2.3.1 Input power system diagram for the PRIMEQUEST 540A/540/440 The figures in this section show the input power system diagrams for the PRIMEQUEST 540A/540/440. Standard configuration (including single power feed system and redundant power supply unit) (Figure 2.17) Dual power feed configuration (Figure 2.19)
  • Page 104: Configuration (Including A Single Power Feed Option And Redundant Power Supply Unit)

    CHAPTER 2 Connection Reference b) PSU locations Figure 2.18 PSU locations in the standard PRIMEQUEST 540A/540/440 configuration (including a single power feed option and redundant power supply unit) 2-24 U41631-J-Z816-5-76...
  • Page 105 2.3 Power Cable Connections (2) Dual power feed configuration This section shows the input power system and PSU locations in the PRIMEQUEST 540A/540/440 containing a Dual Power Feed Option. a) Input power system diagram Main unit Dual Power Feed Option (Note 1) Input Input Input...
  • Page 106: Input Power System Diagram For The Primequest 580A/580/480

    (1) Standard configuration (including single power feed system and redundant power supply unit) This section shows the input power system and PSU locations in the standard PRIMEQUEST 580A/580/480 configuration (including a single power feed option and redundant power supply unit). 2-26...
  • Page 107 Note2: Connect the AC cables of this unit to their counterparts on the power distribution board on a one-to-one basis. Note3: For information about the circuit breakers on the customer's distribution panel, see Section 2.6, "Circuit Breaker Characteristics." Figure 2.21 Input power system diagram for the PRIMEQUEST 580A/580/480 (standard configuration) U41631-J-Z816-5-76 2-27...
  • Page 108 MC-57PSa1x, Additional Power Supply Unit needs to be prepared. When an Additional Power Supply Unit is not mounted, a dummy component is mounted in the relevant slot. Figure 2.22 PSU locations in the standard PRIMEQUEST 580A/580/480 configuration (including a single power feed option and redundant power supply unit)
  • Page 109: And Extended Power Cabinet (Dual Power Feed Configuration)

    Note4: For information about the circuit breakers on the customer’s distribution panel, see Section 2.6, "Circuit Breaker Characteristics." Figure 2.23 Input power system diagram for the PRIMEQUEST 580A/580/480 and Extended Power Cabinet (dual power feed configuration) U41631-J-Z816-5-76 2-29...
  • Page 110: Dual Power Feed Option

    MC-57PSa1x Additional Power Supply Units need to be prepared. When Additional Power Supply Units are not mounted, dummy components are mounted in the relevant slots. Figure 2.24 PSU locations in the PRIMEQUEST 580A/580/480 with a Dual Power Feed Option 2-30 U41631-J-Z816-5-76...
  • Page 111: Pci_Box

    2.3 Power Cable Connections 2.3.3 Input power system diagram for the Extended I/O Cabinet and the PCI_Box The figures in this section show the input power system diagrams for the PCI_Box. Input power system diagram of PCI_Boxes in a single power feed configuration (including a redundant PSU) for use in Japan (Figure 2.25) Input power system diagram of PCI_Boxes in a dual power feed configuration for...
  • Page 112: Configuration (Including A Redundant Psu) For Use In Japan

    CHAPTER 2 Connection Reference (1) Single power feed for use in Japan (including a redundant power supply unit) Figure 2.25 shows the input power system diagram of PCI_Boxes in a single power feed configuration (including a redundant PSU) for use in Japan. Circuit Breaker Note1: For high reliability of the redundant configuration, connect Input #0 and Input #1 of each PCI_Box to different ACSs.
  • Page 113: Configuration For Use In Japan

    2.3 Power Cable Connections (2) Dual power feed for use in Japan Figure 2.26 shows an input power system diagram of PCI_Boxes in a dual power feed configuration for use in Japan. Circuit Breaker Note1: For high reliability of the redundant configuration, connect Input #0 and Input #1 of each PCI_Box to the ACSs on the different system.
  • Page 114: Configuration (Including A Redundant Psu) For Use Outside Japan

    CHAPTER 2 Connection Reference (3) Single power feed (including a redundant PSU) for use outside Japan (general) Figure 2.27 shows the input power system diagram of PCI_Boxes in a single power feed configuration (including a redundant PSU) for use outside Japan (general). Circuit Breaker Note1: For high reliability of the redundant configuration, connect Input #0 and Input #1 of each PCI_Box to different ACSs.
  • Page 115: In A Dual Power Feed Configuration For Use Outside Japan (General)

    2.3 Power Cable Connections (4) Dual power feed for use outside Japan (general) Figure 2.28 shows the input power system diagram of PCI_Boxes in a dual power feed configuration for use outside Japan (general). Circuit Breaker Note1: For high reliability of the redundant configuration, connect Input #0 and Input #1 of each PCI_Box to the ACSs on the different system.
  • Page 116: Configuration (Including A Redundant Psu) For Use In Europe

    CHAPTER 2 Connection Reference (5) Single power feed (including a redundant PSU) for use in Europe Figure 2.29 shows the input power system diagram of PCI_Boxes in a single power feed configuration (including a redundant PSU) for use in Europe. Circuit Breaker Note1: For high reliability of the redundant configuration, connect Input #0 and Input #1 of each PCI_Box to different ACSs.
  • Page 117: Configuration For Use In Europe

    2.3 Power Cable Connections (6) Dual power feed for use in Europe Figure 2.30 shows the input power system diagram of PCI_Boxes in a dual power feed configuration for use in Europe. Circuit Breaker Note1: For high reliability of the redundant configuration, connect Input #0 and Input #1 of each PCI_Box to the ACSs on the different system.
  • Page 118: Input Power Supply Unit Connections

    2.4.1 PRIMEQUEST 580A/540A/580/540/480/440 main unit Table 2.3 lists the specifications for connecting the input power supply unit to the PRIMEQUEST 580A/540A/580/540/480/440 main unit. Table 2.3 AC cable specifications for the PRIMEQUEST 580A/540A/580/540/ 480/440 main unit Destination Plug type Remarks JAPAN...
  • Page 119: Cables Between Pci_Box And Acs In The Extended I/O Cabinet

    2.4 Input Power Supply Unit Connections 2.4.2 Cables between PCI_Box and ACS in the Extended I/O Cabinet Table 2.4 lists the specifications of the AC cables used between a PCI_Box and the ACS in the Extended I/O Cabinet. Table 2.4 Specifications of the AC cables used between a PCI_Box and ACS in the Extended I/O Cabinet Destination Plug type...
  • Page 120: Table 2.5 Specifications Of The Ac Cables Between Acs In The Extended I/O Cabinet And Power Distribution Board

    CHAPTER 2 Connection Reference 2.4.3 Cables between ACS in the Extended I/O Cabinet and power distribution board Table 2.5 lists the specifications of the AC cables between the ACS in the Extended I/O Cabinet and the power distribution board. Table 2.5 Specifications of the AC cables between ACS in the Extended I/O Cabinet and power distribution board Destination Plug type...
  • Page 121: (Only For Use Inside Japan And General Use Outside Japan)

    2.5 AC Cable Connection under a Free-Access Floor (Only for Use inside Japan and General Use outside Japan) AC Cable Connection under a Free-Access Floor (Only for Use inside Japan and General Use outside Japan) If AC cables are connected to the main unit, Extended I/O Cabinet, Extended Power Cabinet, or Dual Power Feed Option under a free-access floor, it is recommended that the underfloor height be 300 mm (11.8 in.) or more in consideration of the shape of the AC cable connector, cable bending radius (see...
  • Page 122: Circuit Breaker Characteristics

    Figure 2.32 shows the characteristics of the circuit breakers. Table 2.6 Requirements for circuit breakers in customers' distribution panels installed in Japan Main unit (PRIMEQUEST 580A/540A/580/ 540/480/440 base cabinet) Extended PCI_Box Power Cabinet The breaking capacity must be 30 A or The breaking capacity must be 20 A or greater.
  • Page 123: Customers' Distribution Panels Installed In Japan

    2.6 Circuit Breaker Characteristics Maximum 0.06 0.04 Minimum 0.02 0.01 5 6 7 8 10 30 40 50 80 100 Current (ratio to the rated current) Figure 2.32 Characteristics of circuit breakers in customers' distribution panels installed in Japan U41631-J-Z816-5-76 2-43...
  • Page 124: Installed Outside Japan

    Figure 2.33 shows the characteristics of such circuit breakers. Table 2.7 Requirements for circuit breakers in customers’ distribution panels installed outside Japan Main unit (PRIMEQUEST 580A/540A/580/ 540/480/440 base cabinet) Extended PCI_Box Power Cabinet The breaking capacity must be 32 A or The breaking capacity must be 16 A or greater.
  • Page 125: Chapter 3 Precautions Pertaining To Delivery And Installation

    2100 (83) Y (Note) (3520) 2150 (85) 1600 (63) *: not supported by Fujitsu Technology Solutions The equipment can be loaded. The equipment cannot be loaded. Note: These units can be loaded by removing the front and rear doors. U41631-J-Z816-5-76...
  • Page 126: Earthquake Preparedness Measures

    Earthquake preparedness measures are intended to prevent computers from falling over, to ensure the safety of operators, to prevent damage, and to enable the quick recovery of systems. Fujitsu has standardized the following techniques to prevent damage to computer systems resulting from an earthquake.
  • Page 127: Earthquake-Proofing Construction Method

    N-F6-WM12-121 N-F6-B12-***121 (*1) (Floor) Bolt length must be specified. *** = Bolt length (mm) The bolt length (mm) varies depending on the building structure. Consult with your Fujitsu engineer. Figure 3.1 Earthquake-proofing construction method (anchoring on the floor surface) U41631-J-Z816-5-76...
  • Page 128: (2) Through-Floor Anchoring

    CHAPTER 3 Precautions Pertaining to Delivery and Installation (2) Through-floor anchoring Special leveling feet must be prepared separately to anchor a unit by using this anchoring method. Each leveling foot of a unit must be replaced with F6-DA6G when it is bolted from the underside of the floor.
  • Page 129: Examples Of Installing Units Using Earthquake-Proofing Construction Methods

    738 (29.1) 680 (26.8) (1.1) (1.1) PRIMEQUEST 580A/540A/580/ 540/480/440 main unit 99 (3.9) (1.6) (3.9) (1.6) 600 (23.6) Front of unit Unit: mm (in.) Figure 3.3 Example of installing a PRIMEQUEST 580A/540A/580/540/480/440 system by using the earthquake-proofing construction method U41631-J-Z816-5-76...
  • Page 130: With An Extended Power Cabinet By Using The Earthquake-Proofing

    CHAPTER 3 Precautions Pertaining to Delivery and Installation (2) Example of installing the PRIMEQUEST 580A/540A/580/480 main unit with an Extended Power Cabinet 1042 (41.0) 680 (26.8) 300 (11.8) 29 (1.1) (1.1) 4 (0.2) PRIMEQUEST Extended 580A/540A/580/480 Power main unit Cabinet 40 (1.6)
  • Page 131: System With An Extended I/O Cabinet By Using The Earthquake-Proofing Construction Method

    99(3.9) (3.9) (1.6) 600 (23.6) (3.9) (3.9) 590 (23.2) 729 (28.7) Front of unit Unit: mm (in.) Figure 3.5 Example of installing a PRIMEQUEST 580A/540A/580/540/480/440 system with an Extended I/O Cabinet by using the earthquake-proofing construction method U41631-J-Z816-5-76...
  • Page 132: With An Extended Power Cabinet And Extended I/O Cabinet

    CHAPTER 3 Precautions Pertaining to Delivery and Installation (4) Example of installing the PRIMEQUEST 580A/580/480 main unit with an Extended Power Cabinet and Extended I/O Cabinet 1726 (68.0) 29 (1.1) 680 (26.8) 680 (26.8) 300 (16.8) 29 (1.1) 4 (0.2) 4 (0.2)
  • Page 133: Seismic Isolation

    3.2 Earthquake Preparedness Measures 3.2.3 Seismic isolation This section explains installing units using seismic isolation. When a unit is installed using seismic isolation, the leveling feet of the unit must be replaced with seismic-isolation leveling feet (CA82001-3000). If openings for cables or air conditioning are provided on the free-access floor, secure the following distances: 1 105 mm (4.1 in.) or more from the center of a seismic-isolation leveling foot 2 60 mm (2.4 in.) or more from the center of a caster...
  • Page 135: Acronyms & Abbreviations

    Acronyms & Abbreviations AC Section Peripheral Component Interconnect Power Supply Unit (AC to DC) Circuit Breaker Central Processing Unit System Board SCSI Small Computer System Interface Digital Linear Tape Uninterruptible Power Supply Unshielded Twisted Pair Fibre Channel VHDCI Very High Density Cable Interconnect International Electrotechnical Commission Wide Area Network...
  • Page 137: Index

    ......2-38 Fujitsu Technology Solutions ....ii .
  • Page 139 Comments Fujitsu Technology Solutions GmbH User Documentation 33094 Paderborn Suggestions Germany Corrections Fax: (++49) 700 / 372 00001 e-mail: manuals@ts.fujitsu.com http://manuals.ts.fujitsu.com Submitted by Comments on PRIMEQUEST 580A/540A/580/540/480/440 Installation Planning Manual U41631-J-Z816-5-76...
  • Page 141 Comments Fujitsu Technology Solutions GmbH User Documentation 33094 Paderborn Suggestions Germany Corrections Fax: (++49) 700 / 372 00001 e-mail: manuals@ts.fujitsu.com http://manuals.ts.fujitsu.com Submitted by Comments on PRIMEQUEST 580A/540A/580/540/480/440 Installation Planning Manual U41631-J-Z816-5-76...

Table of Contents