3RA61/3RA62 compact starter
5.3 Functions
Resetting the short circuit trip
Short-circuit hazard!
If you restart the compact starter after an overload trip and the cause of the short circuit has
not been eliminated, a new short-circuit trip will occur. A short circuit can cause burns and
plant damage.
Eliminate the cause of the short circuit before you restart the compact starter after a short-
circuit trip.
To reset a short circuit trip, turn the actuator to the
Function test
To test the short-circuit protection function, press the "TEST I>>" button ("Short-circuit
protection" test button). This can be done when the compact starter is de-energized.
After the "short-circuit protection" test button has been pressed, the breaker latching
mechanism trips and the actuator of the compact starter changes to the TRIPPED position.
The "Fault" signaling contact (terminals 77/78) opens.
The test can be terminated by turning the actuator first to the
READY position.
60
WARNING
OFF position.
OFF position and then to the
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006