Advertisement

6.10

Commissioning

6.10.1

Settings on the 3RA64/3RA65 compact starter with IO-Link

All the settings are made on the 3RA64/3RA65 compact starter with IO-Link.
CLASS 10E / 20E
The CLASS (overload trip class) indicates the tripping time t
cold) at 7.2 times the current setting I
state overload relay, the trip class corresponds to the narrow tolerance band E
(IEC / EN 60947-6-2):
● CLASS 10E: 5 s < t
● CLASS 20E: 10 s < t
You can use a slide switch to set the trip class to CLASS 10E or CLASS 20E.
Figure 6-6
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
< 10 s
A
< 20 s (for heavy starting)
A
Setting CLASS 10E/20E on the compact starter with IO-Link
3RA64/3RA65 compact starter with IO-Link
A
. As the compact starter has the functionality of a solid-
e
6.10 Commissioning
of the compact starter (from
133