7.10 Terminal for a Type E self-protected combination motor controller (UL 508)

7.10
Terminal for a Type E self-protected combination motor controller
(UL 508)
7.10.1

Scope of supply

Scope of supply of the terminal for Type E
System component
Terminal for self-protected
combination motor controller
(Type E) to UL 508
7.10.2

Installing/removal

According to UL 508 (Type E), line-side clearances of 1 and 2 inches are required for Type E
combination motor controllers. If parallel wiring is used for the compact starter, the terminal
for the self-protected combination motor controller (Type E) (3RV2928-1H) must be used.
Note
According to C22.2-14, terminal blocks are not required for installation in accordance with
CSA requirements.
Note
Supply options in accordance with UL 508 (Type E) are still available when compact starters
are installed with a 3RV19 3-phase busbar and the infeed system for 3RA6. For additional
information, please refer to "Infeed in accordance with UL 508 (Type E) (Page 38)".