No.
Item
19
Louver control
<<Selection of Swing mode>>
(Continued):
• For the Swing mode, the following three types of modes
1) Standard (4 pieces: same phase) swing
2) Dual swing → Data: [0002]
3) Cycle swing → Data: [0003]
<<Louver lock (Louver fix)>>
• For the air direction setup for each discharge port, the louver
• An arbitrary air direction of an arbitrary louver can be
• The louver lock can be set by registering the setup data to
Outline of specifications
are selectable and settable by keeping Swing/Direction
SWING/FIX
button pushed for 4 seconds or more on the remote
controller.
→ Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align at
the horizontal discharge position and then start the
Swing operation at the same time.
When operation is selected, the louvers of louver No.
[01] and [03] move to the horizontal discharge position,
the louvers of louver No. [02] and [04] move to the
downward discharge position and then start the Swing
operation at the same time.
When operation is selected, the louver No. [01] moves to
the horizontal discharge position, [03] to the downward
discharge position, [02] and [04] to the middle position
and then start the Swing operation at the same time.
• Three types of the swing modes can be also selected
and set by the setup data of Item code (DN) [F0].
• In case of selecting the Swing mode, "Dual swing" or
"Cycle swing", the following numerals is displayed at
the center of the remote controller screen for approx.
SWING/FIX
3 seconds when
[SWING]. (No display for the standard swing)
Alternate lighting
(0.5 sec.)
Dual swing
position can be locked during the normal operation.
registered and set by keeping
4 seconds or more on the remote controller.
Item code (DN) [F1] to [F4] according to the following table.
CODE No.
Objective louver No.
F1
01
F2
02
F3
03
F4
04
button was pushed to select
Alternate lighting
(0.5 sec.)
Cycle swing
UNIT
LOUVER
button pushed for
Setup data
0000: Release (At shipment)
0001: Horizontal discharge position
~
0005: Downward discharge position
- 76 -
Remarks
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.
For the setting operation,
refer to [How to set up type
of the swings] in Item
"7 APPLIED CONTROL "
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.