No.
Part name
1. Detachment
9
Float switch
assembly
1) Carry out works of item 1 of 7 and works
from 1) to 5).
2) Remove the fixing screw and then remove
the float switch assembly. (Ø4 × 25, 1 pc.)
2. Attachment
1) Mount the float switch assembly as before
with the fixing screw.
NOTE :
When mounting, match hole of the float switch
assembly with projection of the drain pan.
2) Mount the bell mouth as before.
(Ø4 × 10, 8 pcs.)
3) Following to works of item 2 of 7 and
works from 2) to 5), attach the parts as
before.
1. Detachment
10
Drain pan
1) Carry out works of item 1 of 4 , item 1 of
2) Remove the fixing screws to remove the
drain pan. (Ø4 × 8, 4 pcs.)
2. Attachment
1) Fix parts as before in order of drain cap
→ drain pan → bell mouth.
2) Following to works of item 2 of 7 and
works from 2) to 5), attach parts as before.
Procedure
6 , item 1 of 7 and works from 2) to 5).
- 176 -
Remarks
Float switch assembly
Float switch assembly
Fixing screw (Ø4 × 25)
Fixing screw (Ø4 × 25)
Hole of float switch assembly
Projection of drain pan
Projection of drain pan
Fixing screws (Ø4 × 8)
Fixing screws (Ø4 ×8)
Fixing screws (Ø4 ×