Table 4-2 External Output Functions - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

Code
Function
0
NONE
1 *
TOTAL ALARM
2 *
MINOR FAULT
3
ALARM
4
AC INPUT ABNORMAL
5
BYPASS ABNORMAL
6
BATTERY ABNORMAL
7
BATTERY LOW VOL.1
8 *
BATTERY LOW VOL.2
9
BATTERY DEPLETION
10 *
OVERLOAD
11
OVERLOAD PREALARM
12
FAULT GROUP 1
13
FAULT GROUP 2
14
BYPS.SYNCHRONOUS
15
BYPS.ASYNCHRONOUS
16
REMOTE OPE.ENABLE
17 *
LOAD ON INVERTER
18 *
LOAD ON BYASS
19
LOAD ON AC
20 *
BATTERY OPERATION
21 *
CONVERTER OPERATION
22
INVERTER OPERATION
23
CB1 CLOSE
24
CB2 CLOSE
25
52S CLOSE
26
POWER DEMAND ON
27
EQUALIZING CHARGE
28
ANOTHER BUS SYNC.OK
*Default output settings
36
Table 4–2 External Output Functions
Summary alarm; activated when any minor, major, fault or alarm has occurred with the
system. This is the default setting on OUT8.
Activated when a minor fault has occurred with the system.
Activated when an alarm has occurred with the system.
Activated when the input voltage or frequency is abnormal.
Activated when the bypass voltage or frequency is abnormal.
Activated when the battery is abnormal.
Activated when the battery voltage drops below Discharge Warning Voltage Level 1
during inverter operation. This level is set in the TEST MENU by an Authorized Toshiba
Service Provider.
Activated when the battery voltage drops below Discharge Warning Voltage Level 2
during inverter operation. This level is set in the TEST MENU by an Authorized Toshiba
Service Provider. This is the default setting for OUT5.
Activated when the battery voltage drops below discharge end voltage level during
inverter operation.
Activated when an overload of 105% or more had occurred to the system. This is the
default setting on OUT6.
Activated when the load goes over 100%. This level is adjustable by an Authorized
Toshiba Service Provider.
Activated when the preset group of alarms (Fault Group 1) all occur to the system at
once. These groups are set in the TEST MENU by an Authorized Toshiba Service
Provider.
Activated when the preset group of alarms (Fault Group 2) all occur to the system at
once. These groups are set in the TEST MENU by an Authorized Toshiba Service
Provider.
Activated when the inverter voltage and bypass voltage are synchronous.
Activated when the inverter voltage and bypass voltage are asynchronous.
Activated when any remote operation occurs (Stop/Start Inverter, etc.)
Activated when the power is supplied from the inverter. This is the default setting on
OUT2.
Activated when the power is supplied by the bypass. This is the default setting on
OUT1.
Activated when the power is supplied from the input via the UPS's rectifier/converter -
inverter.
Activated when the battery is operating following an AC power failure. This is the
default setting on OUT3.
Activated when the converter is operating. This is the default setting on OUT4
Activated when the inverter is operating.
Activated when CB1 (Input Contactor) is closed.
Activated when CB2 (Battery Breaker) is closed.
Activated when 52S (Bypass Contactor) is closed.
Activated when a Power Demand is activated by one of the Inputs.
Activated when the UPS is charging the batteries at the equalizing charge level. This
command boosts the charge voltage (500-640 V) for a preset duration (0-100 hr.)
Annunciates that the UPS is successfully synchronized to an external source
G9000 Series UPS 300-750kVA Installation and Operation Manual – 61480-017