Run time measurement
Hide thumbs Also See for Fieldbus Levelflex M FMP45:
Table of Contents

Advertisement

Quick Links

Operating Instructions
Levelflex M FMP45
Run Time Measurement
9
BA281F/00/en/03.09
No. 71074933
Valid as of software version:
01.04.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Fieldbus Levelflex M FMP45

  • Page 1 Operating Instructions Levelflex M FMP45 Run Time Measurement BA281F/00/en/03.09 No. 71074933 Valid as of software version: 01.04.zz...
  • Page 2 Commissioning via Endress+Hauser operating program In the "Commissioning" section, you learn how to switch on the device and check the functioning. Additional information on the operation via the Endress+Hauser operating program (FieldCare) can be found in Operating Instruction BA027S/04. Æ...
  • Page 3 Levelflex M FMP45 with FOUNDATION Fieldbus Brief overview Brief operating instructions Levelflex M - Brief operating instructions KA189F/00/a2/03.07 52012501 Contrast: measured value dist./ meas value Group selection basic setup tank medium process empty full dist./ check range of start properties property cond.
  • Page 4 Brief overview Levelflex M FMP45 with FOUNDATION Fieldbus Endress + Hauser...
  • Page 5: Table Of Contents

    Quick wiring guide ......26 Contact addresses of Endress+Hauser ... 88 Connecting the measuring unit .
  • Page 6: Safety Instructions

    Safety instructions Levelflex M FMP45 with FOUNDATION Fieldbus Safety instructions Designated use The Levelflex M FMP45 is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry. Installation, commissioning and operation The Levelflex M has been designed to operate safely in accordance with current technical, safety and EU standards.
  • Page 7: Notes On Safety Conventions And Icons

    Levelflex M FMP45 with FOUNDATION Fieldbus Safety instructions Notes on safety conventions and icons In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin. Safety conventions Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal...
  • Page 8: Identification

    2.1.1 Nameplate The following technical data are given on the instrument nameplate: Order No Designation according to Directive 94/9/EC (see Order Information) and designation of protection ENDRESS+HAUSER Made in Germany Serial number LEVELFLEX-M D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P...
  • Page 9 Levelflex M FMP45 with FOUNDATION Fieldbus Identification Process temperature: Special version, to be specified Probe: A ..mm, rope 4mm, 316 C ..inch, rope 1/6", 316 K ..mm, rod 16 mm, 316L ..mm, coax, 316L M ..inch, rod 16 mm, 316L N ..
  • Page 10 Identification Levelflex M FMP45 with FOUNDATION Fieldbus Type of probe: H *Remote, cable 3m, side, center d=45 mm, centering disk d=45 mm, 316L, pipe diamter DN50/2" + DN65/2-1/2" *Remote, cable 3m, side, center d=75 mm, centering disc d=75 mm, 316L, pipe diamter DN80/3"...
  • Page 11: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 12: Installation

    Installation Levelflex M FMP45 with FOUNDATION Fieldbus Installation Quick installation guide Mounting with threaded boss F12 or T12 housing Turn housing The housing can be turned 350° in order to simplify access to the display and the terminal compartment ½ "...
  • Page 13: Installation Conditions

    Levelflex M FMP45 with FOUNDATION Fieldbus Installation Installation conditions 3.3.1 Dimensions Housing dimensions Dimensions for the process connection and the probe type → ä 14. max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing (Aluminium) L00-T12xxxx-06-00-00-en-001 max. 94...
  • Page 14 Installation Levelflex M FMP45 with FOUNDATION Fieldbus Levelflex M FMP45 - process connection, type of probe Housing dimensions → ä 13. F12 / T12 / F23 housing Variant “3” / “4” remote electronic top entry 4 x Ø 8,5 Variant “4”: remote electronic side entry Ø...
  • Page 15: Installation

    Levelflex M FMP45 with FOUNDATION Fieldbus Installation Installation 3.4.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • For the mounting of threaded connection: 60 mm Open-end spanner for 1½", 50 mm Open-end spanner for ¾".
  • Page 16 Installation Levelflex M FMP45 with FOUNDATION Fieldbus 3.4.3 Mounting probes in an empty silo " Caution! If there is a risk of electrostatic discharge from the product, then both processconnection and rope must be earthed before the probe is lowered into the silo. Levelflex can be screwed into a threaded socket or flange.
  • Page 17 Levelflex M FMP45 with FOUNDATION Fieldbus Installation 3.4.4 Mounting rope probes in a partially full silo It is not always possible to empty a silo which is already in operation. Because the probe can be turned in the threaded boss, it can also be mounted when the silo is only partially filled. In order to avoid problems when Levelflex is mounted into a partially full silo, the following measures should be taken: •...
  • Page 18 Installation Levelflex M FMP45 with FOUNDATION Fieldbus 3.4.5 General instructions Normally use rod probes. Rope probes are used in liquids for measuring ranges > 4m and with restricted ceiling clearance which does not allow the installation of rigid probes. Coax probes are not influenced by the installation conditions. They may also be operated •...
  • Page 19 Levelflex M FMP45 with FOUNDATION Fieldbus Installation Other installations • Select the mounting location such that the distance to internals (5) (e.g. limit switch, struts) > is 300 mm over the entire length of the probe, also during operation. • Probe must within the measuring span not touch any internals during operation.
  • Page 20 Installation Levelflex M FMP45 with FOUNDATION Fieldbus Supporting probes against warping For WHG or Ex approval: For probe lengths ≥ 3 m a support is required (see figure). Rod probes Probe rod Sleeve bored tight to ensure electrical contact between the rod and sleeve! Short metal pipe e.g.
  • Page 21 Levelflex M FMP45 with FOUNDATION Fieldbus Installation Installing with heat insulation • If process temperatures are high (≥ 200 °C), FMP45 must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection. •...
  • Page 22 In vacuum applications and in applications where extremely condensate fermation may occur, there is the danger that the vessel is completely flooded. For media groups with high DC values, this may result in a measuring value lower than the actual level. Please contact your local Endress+Hauser representative for remedial actions.
  • Page 23 Levelflex M FMP45 with FOUNDATION Fieldbus Installation 3.4.7 Notes on special installation situations Welding the probe into the vessel " Caution! Before welding the probe into the vessel, it must be grounded by a low-resistive connection. If this is not possible, the electronics as well as the HF module must be disconnected. Otherwise the electronics may be damaged.
  • Page 24 Installation for difficult to access process connections Installation with remote electronic • Follow installation instructions on → ä 18 • Mount housing on a wall or pipe as shown in the diagram. wall ENDRESS+HAUSER Levelflex M 4 x Ø 8,5 ENDRESS+HAUSER Levelflex M pipe Note min.
  • Page 25: Post-Installation Check

    Levelflex M FMP45 with FOUNDATION Fieldbus Installation 3.4.9 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
  • Page 26: Wiring

    Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the FOUNDATION Fieldbus Caution! ENDRESS+HAUSER Made in Germany standard and the desired safety concept. (e.g. FISCO). LEVELFLEX-M D-79689 Maulburg Order Code: Ser.-No.:...
  • Page 27 Wiring in T12 housing " Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M FOUNDATION Fieldbus standard and the desired safety D-79689 Maulburg Order Code: concept.
  • Page 28 Wiring Levelflex M FMP45 with FOUNDATION Fieldbus Wiring with FOUNADTION Fieldbus connector " Before connection please note the following: ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Foundation Fieldbus devices are marked on the Order Code: Ser.-No.: IP68 / NEMA 6P nameplate (1).
  • Page 29: Connecting The Measuring Unit

    Levelflex M FMP45 with FOUNDATION Fieldbus Wiring Connecting the measuring unit Ground connection It is necessary to make a good ground connection to the ground terminal on the outside of the housing, in order to achieve EMC security. Cable gland Type Clamping area Standard, Ex ia, IS...
  • Page 30: Recommended Connection

    Wiring Levelflex M FMP45 with FOUNDATION Fieldbus Overvoltage protection If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to DIN EN 60079-14, standard for testprocedures DIN IEC 60060-1 (10 kA, Puls 8/20 μs) it has to be ensured that •...
  • Page 31: Operation

    • Chap. 5.1 Quick operation guide • Chap. 5.2 Operation with the display and operating module VU331 • Chap. 5.3 Operation with an Endress+Hauser operating program • Chap. 5.4 Operation with a FOUNDATION Fieldbus configuration program • Chap. 5.5 Operation with the handheld terminal Field Communicator 375/FC375...
  • Page 32 On-site operation Options for on-site operation • Display and operating module VU331 • Endress+Hauser operating software ("FieldCare") Parameter access by on-site operation The following parameters can be accessed by on-site operation: • Parameters of the instrument specific blocks (Sensor Block, Diagnostic Block, Display Block) •...
  • Page 33: Operation With The Display And Operating Module Vu331

    Levelflex M FMP45 with FOUNDATION Fieldbus Operation Operation with the display and operating module VU331 The LCD module VU 331 for display and operation is located beneath the housing cover. The measured value is legible through the glass in the cover. Open the cover to operate the instrument. (liquid crystal display) Orde Orde...
  • Page 34 Operation Levelflex M FMP45 with FOUNDATION Fieldbus 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning.
  • Page 35 Levelflex M FMP45 with FOUNDATION Fieldbus Operation 5.2.4 The operating menu Function codes For easy orientation within the function menus, for each function a position is shown on the display. L00-FMRxxxxx-07-00-00-de-005 The first two digits identify the function group: • basic setup •...
  • Page 36 Operation Levelflex M FMP45 with FOUNDATION Fieldbus Navigation within the menu ENDRESS + HAUSER – >3 s Return to basic setup medium property tank shape Group Selection safety settings Standard aluminium tank length calibr. plastic tank bypass / pipe linearisation coax probe concrete wall L00-FMU4xxxx-19-00-00-en-020...
  • Page 37: Operation With An Endress+Hauser Operating Program

    Operation with an Endress+Hauser operating program 5.3.1 FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser instruments as well as instruments from other manufacturers that support the FDT standard. The following operating systems are supported: Win2000, Windows XP and Windows Vista.
  • Page 38 Operation Levelflex M FMP45 with FOUNDATION Fieldbus Menu-guided commissioning L00-FMP4xxxx-20-00-00-en-001 Signal analysis via envelope curve L00-FMP4xxxx-20-00-00-en-007 Endress + Hauser...
  • Page 39 Levelflex M FMP45 with FOUNDATION Fieldbus Operation Tank linearisation L00-fmp-Ixxx-20-00-00-en-041 Endress + Hauser...
  • Page 40: Operation With A Foundation Fieldbus Configuration Program

    *.cff The directory names have the following meaning: • 452B48: manufacturer ID of Endress+Hauser • 1012: ID-Code of Levelflex M "Instrument Revision" (0C3) and "DD Revision" (0C4) can be obtained through the display and operating module VU331. For details refer to section 5.2: "Ope- ration with the display and operating module VU331"...
  • Page 41: Operation With The Handheld Terminal Field Communicator 375/Fc375

    • Representation by parameter name Examples: "PAROPERATIONCODE", "PARRESET" • Representation by parameter label (identical to the labels on the display module VU331 and in an Endress+Hauser operation tool) Examples: "unlock parameter", "reset" Operation with the handheld terminal Field Communicator 375/FC375 5.5.1...
  • Page 42 CANCEL HELP Page Delete dsdmdm df das. asdas fa asas la. basic setup Levelflex M E+H_LEVELFLEX_M_XXXXXX tank properties: standard Endress+Hauser Device Revision 4 standard Block Tag Block Type Actual Mode aluminium tank RESOURCE... RES_BL... Auto plastic tank SENSOR_B... Custom bypass / pipe DIAGNOSTI...
  • Page 43: Commissioning

    • Chap. 6.6 "Blocking distance" • Chap. 6.7 "Envelope curve" • Chap. 6.8 "Basic setup with the Endress+Hauser operating program" • Chap. 6.9 "Commissioning with a FOUNDATION Fieldbus configuration tool" • Chap. 6.10 "Commissioning with the handheld terminal Field Communicator 375/FC375"...
  • Page 44 Enter "2457". Now parameters can be changed. Parameters affected Locking by the key combination affects the following parameters: • Parameters of the instrument specific blocks (Sensor Block, Diagnostic Block, Display Block) • Endress+Hauser service parameters 6.2.3 Locking parameter Locking Enter a number other than "2457" into the "unlock parameter" (0A4) function.
  • Page 45: Resetting The Instrument

    Sensorblock AI-Block 1 Input-Selector-Block Diagnoseblock AI-Block 2 Signal-Charact.-Block Display-Block PID Block Integrator-Block Endress+Hauser Service-Parameter L00-FMU4XXXX-02-00-00-YY-007 Performing the reset Resource Block, parameter RESTART; select the option "defaults". 6.3.2 Resetting the parameters of the transducer blocks " Caution! A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after a reset.
  • Page 46 – "inactive": deactivates the tank map but does not delete it. It can be re-activated when required. – "active": activates the tank map. Resetting the tank map with an Endress+Hauser operating program In the function group "extended calibr." select the "cust. tank map" (055) function. Select the required option ("reset", "inactive" or "active") Resetting the tank map with a FOUNDATION Fieldbus configuration tool In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).
  • Page 47: Basic Setup

    Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Basic setup FMP40 FMP41C FMP43 FMP45 tank shape Standard reference point of measurement measuring cond. Unknown measuring cond. Standard empty calibr. full calibr. mapping E = empty calibr. (= zero) LN = probe length setting in 005 setting in 033 safety settings...
  • Page 48 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus The Levelflex is precalibrated at the factory to the probe length ordered so that in most cases only the application parameters, which automatically adapt the instrument to the measuring conditions, need the entered. For models with a current output, the factory calibration for zero point and span F is 4 mA and 20 mA, for digital outputs and the display module 0 % and 100 %.
  • Page 49: Commissioning By The Display And Operating Module Vu331

    Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Commissioning by the display and operating module VU331 6.5.1 Power up instrument When the instrument is switched on for the first time, the following messages appear in a sequence of 5 s on the display: software version, communication protocoll and language selection ⇒...
  • Page 50 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus 6.5.2 Function group "basic setup" (00) ⇒ ENDRESS + HAUSER – Function "tank properties" (002) ⇒ ENDRESS + HAUSER – This function is used to select the tank properties. Selection: • standard • aluminium tank •...
  • Page 51 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning concrete wall The "concrete wall" option takes into account the signal-damping property of concrete walls when mounting with < 1 m distance to the wall. Function "medium property" (003) ⇒ ENDRESS + HAUSER –...
  • Page 52 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Function "process propert" (004) ⇒ ENDRESS + HAUSER – Use this funtcion to adapt the instrument to the filling speed in the tank. The setting impacts on an intelligent filter. Selection: • standard •...
  • Page 53 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Function "probe length" (031) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length. Selection: •...
  • Page 54 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Function "determine length" (034) ⇒ ENDRESS + HAUSER – Use this function, the probe length can be determined automatically. Due to the mounting conditions, the automatically determined probe length may be larger than the actual probe ( typically 20 ...
  • Page 55 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (=span). 100% F = full calibration (= span) F max = E –...
  • Page 56 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Function "check distance" (051) ⇒ ENDRESS + HAUSER – This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available: Options: •...
  • Page 57 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Distance = ok Use this function for partially covered probes. Choose "manual" or "probe free" if the probe is free. • Mapping is carried out up to the currently measured echo • The range to be suppressed is suggested in the "range of mapping" (052) function It is wise to carry out a mapping even in this instance.
  • Page 58 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Function "dist./meas.value" (008) ⇒ ENDRESS + HAUSER – The distance measured from the reference point to the product surface and the measured value calculated with the aid of the empty calibration are displayed again. Check whether the values correspond to the actual meas.
  • Page 59: Blocking Distance

    Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is set to 0.2 m at the factory.
  • Page 60 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Maximum measured error Typical statements for reference conditions: DIN EN 61298-2, percentage of the span. Output: Digital Analogue sum of non-linearity, measurig range: ± 0.06 % non-repeatability – up to 10 m: ±3 mm and hysteresis –...
  • Page 61: Envelope Curve

    Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Envelope curve After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended. 6.7.1 Funxtion "plot settings" (0E1) In this function, select whether you want to display •...
  • Page 62 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Check that the following conditions are fulfilled: • The echo quality at the end of measuring range should be at least 10dB. • There should be practically no interference echoes in front of the level signal. Note! If the cyclical envelope curve display is still active on the display, the measured value is updated at a slower cycle time.
  • Page 63 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning 6.7.8 Navigation in the envelope curve display Using navigation, the envelope curve can be scaled horizontally and vertically and shifted to the left or the right. The active navigation mode is indicated by a symbol in the top left hand corner of the display.
  • Page 64: Basic Setup With The Endress+Hauser Operating Program

    The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function the display settings return to their standard values. Basic setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: •...
  • Page 65 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Basic setup step 2/6: • Enter the application parameters (see chapter basic setup with "VU331"): – tank properties – medium properties – process properties l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
  • Page 66 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Basic setup step 4/6: • Enter the application parameters (see chapter basic setup with "VU331"): – probe length – probe – probe length – determine length l00-fmp4xxxx-20-00-00-en-004 Basic setup step 5/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
  • Page 67 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Basic setup step 6/6: • Interference echo suppression takes place in this step • The measured distance and the current measured value are always displayed in the header l00-fmp4xxxx-20-00-00-en-006.gif 6.8.1 Signal analysis via envelope curve After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve.
  • Page 68 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus Evaluating the measurement with the aid of the envelope curve Typical curve shapes: The following examples display typical curve shapes for a rope or rod probe in an empty tank. For all probe types, a negative probe end signal is shown. For rope probes, the end weight causes an additional preliminary positive echo (see rope probe diagram).
  • Page 69 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning Evaluating the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty. •...
  • Page 70: Commissioning With A Foundation Fieldbus Configuration Tool

    For commissioning of the instrument with a FOUNDATION Fieldbus configuration tool you need to know the INSTRUMENT_ID, which consists of the following parts: Instrument_ID = 452B481012-XXXXXXXX whereby: 452B48 ID code for Endress+Hauser 1012 ID code for Levelflex M XXXXXXXX Instrument serial number, as printed on the nameplate 6.9.1 Fist setup Open the configuration tool and load the Instrument Descriptions (*.ffo, *.sym and - if...
  • Page 71 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning 6.9.2 Parametrization of the Resource Block (Start Index: 400) Enter the desired block name (optional). Factory setting: RESOURCE_XXXXXXXX Opern the Resource Block On delivery, write protection is disabled so that you can access the write parameters via FOUNDATION Fieldbus.
  • Page 72 – by the display and operating module VU331 (see section 6.4.5) – by an Endress+Hauser operating program (see section 6.5.1) In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display: - parameter names (e.g. "PARTANKSHAPE") - label texts (e.g.
  • Page 73 Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning 6.9.4 Parametrization of the Analog Input Blocks Levelflex M has two Analog Input Blocks that can be assigned to the various process variables. The following descripiton provides an example for the Analog Input Block 1 (Start Index 500). Enter the desired block name (optional).
  • Page 74 Commissioning Levelflex M FMP45 with FOUNDATION Fieldbus In addition to the limit values you must also specify the action taken if a limit value is exceeded using the alarm priorities (parameters HI_HI_PRI, HI_PRI, LO_PRI, LO_LO_PRI). Reporting to the the fieldbus host system only takes place if the alarm priority is higher than 2. For details refer to section 11.7 in the Appendix.
  • Page 75: Commissioning With The Handheld Terminal Field Communicator 375/Fc375

    Levelflex M FMP45 with FOUNDATION Fieldbus Commissioning 6.10 Commissioning with the handheld terminal Field Communicator 375/FC375 The steps of the commissioning procedure are the same as with a FOUNDATION Fieldbus configuration tool (→ Chap. 6.9). The blocks should be parametrized in the following order: •...
  • Page 76: Maintenance

    Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves (see Chap. 9.4 "Spare Parts" → ä 86). Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 77: Accessories

    Levelflex M FMP45 with FOUNDATION Fieldbus Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001).
  • Page 78: Remote Display And Operation Fhx40

    Accessories Levelflex M FMP45 with FOUNDATION Fieldbus Remote display and operation FHX40 Micropilot M Wall-mounting Pipe-mounting Levelflex M (without mounting bracket) (mounting bracket and plate Prosonic M e r . e r . supplied optionally, s. product structure) o . : o .
  • Page 79: Centering Disks

    Levelflex M FMP45 with FOUNDATION Fieldbus Accessories Centering disks If the probes with rod version are used in stilling well or bypass, it must be ensured that the probe does not come into contact with the wall. The centering disk fixes the rod probe in the middle of the pipe.
  • Page 80: Commubox Fxa291

    Levelflex M FMP45 with FOUNDATION Fieldbus Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291"...
  • Page 81: Trouble-Shooting

    Connect the plug Ready Display works? of the display. correctly The display is possibly defective. Output current between 3.6 …22mA ? Contact Endress+Hauser Service Communication via Service adapter Not ok Check configuration Correct configuration Ready Communication ok? does not function...
  • Page 82: System Error Messages

    Trouble-shooting Levelflex M FMP45 with FOUNDATION Fieldbus System error messages Code Description Possible cause Remedy A102 checksum error device has been powered off before data reset general reset & new calibr. could be stored; avoid emc problem; required emc problem; if alarm prevails after reset, PROM defect exchange electronics...
  • Page 83 Levelflex M FMP45 with FOUNDATION Fieldbus Trouble-shooting Code Description Possible cause Remedy W601 linearisation ch1 curve not linearization not monotonously increasing correct linearisation table monotone W611 less than 2 linearisation number of entered linearization points < 2 correct linearisation table points for channel 1 W621 simulation ch.
  • Page 84: Application Errors

    Trouble-shooting Levelflex M FMP45 with FOUNDATION Fieldbus Application errors Error Output Possible cause Remedy A warning or alarm Depending on the configuration See table of 1. See table of error messages (→ ä 82) has occurred. error messages (→ ä 82) →...
  • Page 85 Levelflex M FMP45 with FOUNDATION Fieldbus Trouble-shooting Device displays a Incorrect probe length 1. Carry out automatic probe length level when the detection when the tank is tank is empty. 100% empty. 2. Carry out mapping over entire probe when the tank is empty (probe free!).
  • Page 86: Spare Parts

    Trouble-shooting Levelflex M FMP45 with FOUNDATION Fieldbus Spare Parts An overview of the spare parts for your device is available in the internet at www.endress.com. To obtain information on the spare parts, proceed as follows: Go to "www.endress.com" and select your country. Click "Instruments".
  • Page 87: Return

    Levelflex M FMP45 with FOUNDATION Fieldbus Trouble-shooting Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 88: Contact Addresses Of Endress+Hauser

    Trouble-shooting Levelflex M FMP45 with FOUNDATION Fieldbus Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress + Hauser...
  • Page 89: Technical Data

    Levelflex M FMP45 with FOUNDATION Fieldbus Technical data Technical data 10.1 Additional technical data 10.1.1 Input The measured variable is the distance between a reference point (see Fig. on → ä 14) and the Measured variable product surface. Subject to the input empty distance (E, see Fig. on → ä 103), the level is calculated. Alternatively, the level can be converted by means of linearisation (32 points) into other variables (volume, mass).
  • Page 90 Technical data Levelflex M FMP45 with FOUNDATION Fieldbus Source VCRs Sink VCRs Subscriber VCRs Publisher VCRs Link Settings Slot time Min. Inter PDU delay Max. response delay Transducer Blocks Block Content Output values Sensor Block contains all parameters related to the measurement •...
  • Page 91 Levelflex M FMP45 with FOUNDATION Fieldbus Technical data Block Content Execution time Functionality Integrator Block The Integrator Function Block integrates a variable as a 60 ms standard function of the time or accumulates the counts from a Pulse Input block. The block may be used as a totalizer that counts up until reset or as a batch totalizer that has a setpoint, where the integrated or accumulated value is compared to pre-trip and trip settings, generating discrete...
  • Page 92 Technical data Levelflex M FMP45 with FOUNDATION Fieldbus 10.1.4 Performance characteristics Reference operating • Temperature = +20 °C (68 °F) ±5 °C (9 °F) conditions • Pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi) • Humidity = 65 % ±20% •...
  • Page 93 Levelflex M FMP45 with FOUNDATION Fieldbus Technical data Installing FMP45 with Application Gasphase Compensation For level measurement in steam applications at high pressures and temperatures. (Coax only) At high pressures and temperatures, the speed at which microwave signals are propagated in steam (polar media) is reduced above the liquid being measured.
  • Page 94 Technical data Levelflex M FMP45 with FOUNDATION Fieldbus Installation This version of Levelflex M generates a reference reflection in the distance Lref from the flange (see → ä 8 "Ordering structure" option U: 300 mm/11"; option V: 550 mm/21"). The reference reflection must be at least 150 mm above the highest level.
  • Page 95 Levelflex M FMP45 with FOUNDATION Fieldbus Technical data 10.1.5 Operating conditions: Environment Ambient temperature range Ambient temperature for the transmitter: -40 °C ... +80 °C (-40 °F … +176 °F) The functionality of the LCD display may be limited for temperatures Ta<-20 °C and Ta>+60 °C.
  • Page 96 Technical data Levelflex M FMP45 with FOUNDATION Fieldbus Storage temperature -40 °C … +80 °C (-40 °F … +176°F) Climate class DIN EN 60068-2-38 (test Z/AD) Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 1 (m/s Cleaning the probe Depending on the application, soilings or sediments can accumulate on the probe.
  • Page 97 Stainless steel 1.4401/316 DIN/EN flanges Endress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L with the material number 1.4435 or 1.4404. With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13E0 in EN1092-1 Tab.18.
  • Page 98 Technical data Levelflex M FMP45 with FOUNDATION Fieldbus 10.1.7 Mechanical construction Tolerance of probe length Rod probes over 1 m / 3.2 ft 3 m / 9.8 ft 6 m / 20 ft up to 1 m / 3.2 ft 3 m / 9.8 ft 6 m / 20 ft admissible tolerance (mm / inch)
  • Page 99 The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Manufacturer declaration Permitted pressures, temperatures and load cycles as per EN 13445 and AD- data sheet S2 (for FMP45).
  • Page 100 Technical data Levelflex M FMP45 with FOUNDATION Fieldbus WHG. See "Ordering structure" on → ä 8 (see ZE256F/00/de) Overspill protection SIL 2, for 4...20 mA output (see SD174F/00/en "Functional safety manual"). Telecommunication Fulfils "Part 15" of the FCC regulations for an "Unintentional Radiator". All probes meet the requirements for a "Class A Digital Device".
  • Page 101 Levelflex M FMP45 with FOUNDATION Fieldbus Technical data Endress + Hauser...
  • Page 102: Appendix

    Appendix Levelflex M FMP45 with FOUNDATION Fieldbus Appendix 11.1 Operating menu FOUNDATION Fieldbus basic setup tank properties medium cond. process proper. empty calibr. end of probe 030 determine length see Function group “leghth adjustment 03” enter value standard unknown standard aluminium tank DC: 1.4 …...
  • Page 103 Levelflex M FMP45 with FOUNDATION Fieldbus Appendix full calibr. dist./meas.value check distance range of mapping start mapping dist./meas.value enter value distance = ok input of D and L dist. too small mapping range are displayed D and L manual are displayed probe free dist.
  • Page 104: Description Of Functions

    Appendix Levelflex M FMP45 with FOUNDATION Fieldbus 11.2 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA245F – "Description of the instrument functions" on the enclosed CD-ROM. 11.3 Function and system design 11.3.1 Measuring principle The Levelflex is a "downward-looking"...
  • Page 105 • with a Personal Computer, FXA291 and ToF Adapter FXA291 (USB) and the operating software "FieldCare". The FieldCare is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
  • Page 106 Appendix Levelflex M FMP45 with FOUNDATION Fieldbus Endress + Hauser...
  • Page 107: Index

    Levelflex M FMP45 with FOUNDATION Fieldbus Index Index Messbedingungen ....... 52 Mounting .
  • Page 108 Levelflex M FMP45 with FOUNDATION Fieldbus Index Endress + Hauser...
  • Page 109 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 110 www.endress.com/worldwide BA281F/00/en/03.09 No. 71074933 CCS/FM+SGML 6.0/ProMoDo 71074933...