Low Voltage Connections; Figure 13 Low Voltage Wire Harness Plug - Bard QW Series Installation Instructions Manual

Geothermal r-410a staged capacity packaged heat pump
Hide thumbs Also See for QW Series:
Table of Contents

Advertisement

LOW VOLTAGE CONNECTIONS

The "R" terminal is the 24 VAC hot terminal and is
supplied through Pin #10 of Plug P2.
The "C" terminal is the 24 VAC common/grounded
terminal and feeds through Pin #11 of Plug P2.
The "G" terminal is the indoor blower input signal and
feeds through Pin #6 of Plug P2.
The "Y1" terminal is the compressor starting signal and
feeds through Pin #7 of Plug P2.
The "Y2" terminal is the compressor staging solenoid
signal and feeds through Pin #4 of Plug P2.
The "O" terminal is the reversing valve signal and feeds
through Pin #8 of Plug P2.
The "A" terminal is the ventilation demand signal
and outputs a signal for ventilation during occupied
programming conditions, and feeds through Pin #5 of
Plug P2.
The "W2" terminal is the electric heat signal and feeds
through Pin #9 of Plug P2.
The "W1/E" terminal is the emergency heat signal and
feeds through Pin #3 of Plug P2.
The "L" terminal is used as an input terminal when a
CS2000 infrared occupancy device is used. It feeds
through Pin #12 of Plug P2.
The "D" terminal is used only of dehumidification
models and feeds through Pin #1 of Plug P2.
LOW VOLTAGE CONNECTIONS FOR
Fan Only
Ventilation
Part Load Cooling
Full Load Cooling
Part Load HP Heating
Full Load HP Heating
Electric Heat
Dehumidification
FIGURE 13
Blower Motor Low Voltage
Wire Harness Plug
MIS-1285
DDC CONTROL
Energize G
Energize G, A (any mode of operation)
Energize G, Y1, O
Energize G, Y1, Y2, O
Energize G, Y1
Energize G, Y1, Y2
Energize G, W2
Energize G, D, O
Manual 2100-577C