1.0
GENERAL
Furnish and install a self-contained, vertical, floor standing, heat pump to
be manufactured by Bard Manufacturing Company, Inc. The unit shall be
approved and Listed by Intertek ETL Listed (ETL US/C). Unit shall be
factory assembled, pre-charged, pre-wired, tested and ready to operate.
Unit performance shall be AHRI Certified in accordance with ISO Standard
13256-1:1998 "Water to Air and Brine to Air Heat Pumps", which includes
watt allowance for water pumping. Unit shall include 5 year parts warranty
covering compressor, parts, and heat exchange coils, subject to terms and
conditions of Bard Limited Warranty Agreement.
Unit efficiency shall be specified in terms of EER and COP.
Manufacturers: Capacities shall be as indicated on drawings and units
shall be manufactured by Bard Manufacturing Company, Inc. or prior
approved equal.
2.0
CONSTRUCTION FEATURES
2.1
CABINET
Constructed of 20 gauge pre-painted or vinyl laminated galvanized
steel. Choices available are either two-tone (vinyl) finish with "slate"
front panels and "platinum" cabinet for designer appearance, (gray)
or (beige) painted steel (select one). Vinyl finish is very resistant to
scratching and marring and is easy to clean.
fasteners are provided for access panels.
rollers for each installation into wall sleeve and removal for service,
if necessary. Front panel is hinged and lockable for filter service and
access to primary functional electrical controls.
2.2
INSULATION
Cabinet is fully insulated with foil covered, high-density fiberglass
insulation with sealed edge treatment and special sound deadening
insulation material in the compressor section.
designed to resist mold and mildew growth and facilitate ease of
cleaning.
F1915 (2012 04)
BARD MANUFACTURING COMPANY, INC.
QW2S-QW5S Water-to-Air H/P
Engineering Specification Guide
Page 1 of 6
Tamper resistant
Unit includes built-in
All insulation is

Advertisement

loading

Summary of Contents for Bard QW2S-QW5S Water-to-Air H

  • Page 1 GENERAL Furnish and install a self-contained, vertical, floor standing, heat pump to be manufactured by Bard Manufacturing Company, Inc. The unit shall be approved and Listed by Intertek ETL Listed (ETL US/C). Unit shall be factory assembled, pre-charged, pre-wired, tested and ready to operate.
  • Page 2: Indoor Blower Motor

    COMPRESSOR All models shall use a high efficiency scroll compressor with step capacity providing 2 stages of control. The compressor shall be covered by a 5-year parts warranty. The refrigeration circuit shall be equipped with factory installed high and low-pressure controls. The refrigeration control shall be a factory installed TXV.
  • Page 3 standard. One shall be used for fresh water applications, the other for protected (antifreeze) closed systems. The factory wired switch is for fresh water. Phase rotation protection and phase failure protection shall be standard factory installed features on all equipment with three-phase power.
  • Page 4 The ERV cassette including parts and media shall include 5year warranty subject to terms and conditions of Bard’s warranty. The ERV thermal performance shall be certified by the manufacturer in accordance with ASHRAE Standard 84, Method of Testing Air-to...
  • Page 5 2” Fiberglass – Pleated – MERV 8 HOT GAS REHEAT- (Factory installed option) The dehumidification circuit incorporates an independent heat exchanger coil in the supply air stream in addition to the standard evaporator coil. This coil reheats the supply air after it passes over the cooling coil, and is sized to nominally match the sensible cooling capacity evaporator...
  • Page 6 11.0 WARRANTY 11.1 The Bard product specified shall be free from defects in materials and workmanship for a period of 5 years for compressor, and for a period of 5 years for all parts. Warranty period shall start from date of installation as stated on warranty card;...

This manual is also suitable for: