Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1)
Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 Vdc output
Terminal number
Max. load
The 24 Vdc supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
1)
Max. terminal load (AC-1)
on 1-2 (NO) (Resistive load)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
1)
Max. terminal load (AC-1)
1)
on 1-3 (NC) (Resistive load)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
1)
1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO)
Environment according to EN 60664-1
Relay 02 Terminal number
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
1)
Max. terminal load (DC-13)
1)
1)
Max. terminal load (AC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
1)
Max. terminal load (DC-13)
Min. terminal load on 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1)
IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300 Vac 2 A
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
The 10 Vdc supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
BAS-SVX54B-EN
TR200 D-Frame Operating Instructions
2)3)
on 1-2 (NO) (Inductive load @ cosφ 0.4)
on 1-2 (NO) (Resistive load)
on 1-2 (NO) (Inductive load)
on 1-3 (NC) (Inductive load @ cosφ 0.4)
on 1-3 (NC) (Resistive load)
on 1-3 (NC) (Inductive load)
2)3)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
on 4-5 (NO) (Resistive load)
on 4-5 (NO) (Inductive load)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
on 4-6 (NC) (Resistive load)
on 4-6 (NC) (Inductive load)
Max. error: 0.1 % of full scale
1-3 (break), 1-2 (make)
24 Vdc 10 mA, 24Vac 2 mA
overvoltage category III/pollution degree 2
4-6 (break), 4-5 (make)
24 Vdc 10 mA, 24Vac 2 mA
overvoltage category III/pollution degree 2
Specifications
2
27, 29
1)
0-24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
12 bit
12, 13
200 mA
2
400 Vac, 2 A
240 Vac, 0.2 A
80 Vdc, 2 A
24 Vdc, 0.1 A
240 Vac, 2 A
240 Vac, 0.2 A
50 Vdc, 2 A
24 Vdc, 0.1 A
400 Vac, 2 A
240 Vac, 0.2 A
80 Vdc, 2 A
24 Vdc, 0.1 A
240 Vac, 2 A
240 Vac, 0.2 A
50 Vdc, 2 A
24 Vdc, 0.1 A
50
10.5 V ±0.5 V
25 mA
75