Table 6.7 Start/Stop with Reversing and 4 Preset Speeds
Table 6.8 External Alarm Reset
BAS-SVX54B-EN
TR200 D-Frame Operating Instructions
Parameters
Function
Setting
5-10 Terminal 18
[8] Start
Digital Input
5-11 Terminal 19
[10]
Digital Input
Reversing*
5-12 Terminal 27
[0] No
Digital Input
operation
5-14 Terminal 32
[16] Preset
Digital Input
ref bit 0
5-15 Terminal 33
[17] Preset
Digital Input
ref bit 1
3-10 Preset
Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
*=Default Value
Notes/comments:
Parameters
Function
Setting
5-11 Terminal 19
[1] Reset
Digital Input
*=Default Value
Notes/comments:
Table 6.9 Speed Reference (using a Manual Potentiometer)
Table 6.10 Speed Up/Down
Application Examples
Parameters
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
*=Default Value
Notes/comments:
Parameters
Function
Setting
[8] Start*
5-10 Terminal 18
Digital Input
5-12 Terminal 27
[19] Freeze
Digital Input
Reference
5-13 Terminal 29
[21] Speed
Digital Input
Up
5-14 Terminal 32
[22] Speed
Digital Input
Down
*=Default Value