10.3 Fuse Tables

10.3.1 Protection

Branch Circuit Protection
In order to protect the installation against electrical and
fire hazard, all branch circuits in an installation, switch
gear, machines etc., must be short-circuited and over-
current protected according to national/international
regulations.
Short-circuit Protection
The frequency converter must be protected against short-
circuit to avoid electrical or fire hazard. Trane recommends
using the fuses mentioned below to protect service
personnel and equipment in case of an internal failure in
the frequency converter. The frequency converter provides
full short-circuit protection in case of a short-circuit on the
motor output.
Over-current Protection
Provide overload protection to avoid fire hazard due to
overheating of the cables in the installation. The frequency
converter is equipped with an internal over-current
protection that can be used for upstream overload
Power
Size
Bussman
Littelfuse PN
PN
N110
170M2619 LA50QS300-4 L50S-300
N132
170M2620 LA50QS350-4 L50S-350
N160
170M2621 LA50QS400-4 L50S-400
N200
170M4015 LA50QS500-4 L50S-500
N250
170M4016 LA50QS600-4 L50S-600
N315
170M4017 LA50QS800-4 L50S-800
Table 10.6 Fuse Options for 380-480 V Frequency Converters
BAS-SVX54B-EN
TR200 D-Frame Operating Instructions
Fuse options
Littelfuse
Bussmann
Siba PN
PN
PN
FWH-300A
20 610
31.315
FWH-350A
20 610
31.350
FWH-400A
20 610
31.400
FWH-500A
20 610
31.550
FWH-600A
20 610
31.630
FWH-800A
20 610
31.800
protection (UL-applications excluded). See 4-18 Current
Limit. Moreover, fuses or circuit breakers can be used to
provide the over-current protection in the installation.
Over-current protection must always be carried out
according to national regulations.

10.3.2 Fuse Selection

Trane recommends using the following fuses which will
ensure compliance with EN50178. In case of malfunction,
not following the recommendation may result in
unnecessary damage to the frequency converter.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical).
N110-N315
380–500 V
N75K–N400
525–690 V
Table 10.5
Ferraz-Shawmut
Ferraz-Shawmut PN
PN
(Europe)
A50QS300-4
6,9URD31D08A0315
A50QS350-4
6,9URD31D08A0350
A50QS400-4
6,9URD31D08A0400
A50QS500-4
6,9URD31D08A0550
A50QS600-4
6,9URD31D08A0630
A50QS800-4
6,9URD32D08A0800
Specifications
type aR
type aR
Ferraz-Shawmut PN
(North America)
A070URD31KI0315
A070URD31KI0350
A070URD31KI0400
A070URD31KI0550
A070URD31KI0630
A070URD31KI0800
77