Circuit Requirements for G9953ZX
Full-Load Current Rating ................... 25 Amps
Nominal Voltage .............................. 220V/240V
Cycle ..........................................................60 Hz
Phase .................................................... 1-Phase
Circuit Rating ...................................... 30 Amps
Plug/Receptacle ...........................NEMA L6-30
Cord .........3-Wire, 10 AWG, 300VAC, "S"-Type
L6-30 GROUNDED
G9953ZX
LOCKING
RECEPTACLE
Grounding Prong
is Hooked
L6-30
LOCKING
PLUG
Current Carrying Prongs
Figure 4. Typical L6-30 plug and receptacle.
G9953ZXF Circuit Requirements for
220V Operation
This machine is prewired to operate on a power
supply circuit that has a verified ground and meets
the following requirements:
Full-Load Current Rating ................... 14 Amps
Nominal Voltage .............................. 220V/240V
Cycle ..........................................................60 Hz
Phase .................................................... 3-Phase
Circuit Rating ...................................... 20 Amps
Connection ......Hardwire with Locking Switch
G9953ZXF Circuit Requirements for
440V Operation
This machine can be converted to operate on a
power supply circuit that has a verified ground
and meets the requirements listed below. (Refer
to Voltage Conversion instructions for details.)
Full-Load Current Rating ..................... 7 Amps
Nominal Voltage .............................. 440V/480V
Cycle ..........................................................60 Hz
Phase .................................................... 3-Phase
Rated Size ........................................... 15 Amps
Connection ......Hardwire with Locking Switch
-10-
A permanently connected (hardwired) power sup-
ply is typically installed with wires running through
mounted and secured conduit. A disconnecting
means, such as a locking switch (see following
figure), must be provided to allow the machine
to be disconnected (isolated) from the power
supply when required. This installation must be
performed by an electrician in accordance with all
applicable electrical codes and ordinances.
G9953ZXF
Locking
Disconnect Switch
Power
Source
Conduit
Ground
Figure 5. Typical setup of a permanently
connected machine.
Serious injury could occur if you connect
machine to power before completing setup
process. DO NOT connect to power until
instructed later in this manual.
Note: Circuit requirements in this manual apply to
a dedicated circuit—where only one machine will
be running on the circuit at a time. If machine will
be connected to a shared circuit where multiple
machines may be running at the same time, con-
sult an electrician or qualified service personnel to
ensure circuit is properly sized for safe operation.
Extreme Series Jointer (Mfd. Since 10/20)
Machine
Conduit
Ground