1.5 If the electric wirings
Check the condenser motor ventilator (start or no)
Check the solenoid valve (start or no)
Check the charge of GAS
.
Check the calibration of the pressostat, in case change it or change the pressostat
1.
If the electric wirings
1K4
(picture page 3 alarm E10)
2.
If there is still the alarm
1- 4
are open the double pressostat is activated
verify the follwing point :
1- 4
are closed with power supply in the coil 1K4, change the relay
E10
follow the points described in page 3 point 1.4
.
.
.