York YCAS0130 Installation, Operation & Maintenance Manual page 155

Ycas air-cooled liquid chillers style g
Hide thumbs Also See for YCAS0130:
Table of Contents

Advertisement

S Y S
#
O I L =
S P =
6 2
D P =
This message indicates the system oil pressure, suc-
tion pressure, and discharge pressure at the time of the
fault.
S Y S
#
O I L =
S T =
3 9 . 0
D T = 1 2 3 . 7
This message shows the system oil temperature, suction
temperature, and discharge temperature at the time of
the fault.
S #
S A T
S U C T
S U C T
S H E A T
These messages indicate compressor suction gas sat-
u ra tion temperature and superheat at the time of the
fault.
S #
S A T
D S C H =
D S C H
S H E A T
This message indicates compressor discharge gas sat-
u ra tion temperature and superheat at the time of the
fault.
S Y S
#
S V
S T E P
This message indicates the compressor slide valve po-
si tion at the time of the fault. 0 steps equals minimum
capacity and 75 steps equals fully loaded.
S Y S
X
E E V
S U C T
S H E A T
This message indicates the EEV preheat % and the suc-
tion superheat.
S Y S
#
C O O L E R
R E F R I G
T E M P
This message, which is only displayed if the unit is in
R-407C mode, indicates the refrigerant temperature at
the inlet of the evaporator.
YORK INTERNATIONAL
1 7 5
P S I G
2 7 1
P S I G
1 5 4 . 8
° F
° F
= 3 4 . 7 ° F
= 1 0 . 5 ° F
1 2 9
° F
= 6 2 . 8 ° F
=
4 0
=
3 7 . 4
%
=
1 0 . 2
º F
I N L E T
=
2 8 . 2 ° F
S Y S
#
L L S V
E C O N
T X V
S O L
This message indicates the EEV PILOT So le noid Valve
and the economizer Thermal Expansion Valve So le noid
Valve position: ON = Energized / OFF = De-En er gized
(OFF) at the time of the fault.
S Y S
#
F A N
C O M P
H E A T E R
This message indicates the stage of condenser fan op-
er a tion on the system and the status of the com pres sor
heat er at the time of the fault. See Section 8.4 for de tails
of fan staging.
S Y S
#
W Y E - D E L T A
This message indicate whether the WYE-DELTA out-
put to the compressor was energized at the time of the
fault
S Y S
X
D S C H
C L
S Y S
X
W Y E - D E L T A
This message indicates whether the discharge cooling
solenoid was energized at the time of the fault and if the
WYE-DELTA output to the compressor was energized.
(Low Temperature Glycol Chillers Only)
FORM 201.19-NM1 (204)
I S
O N
I S
O F F
S T A G E
3
I S
O F F
O N
S V
OFF
OFF
155
8