8.12 Isn Control; Table 12 - Isn Received Data; Table 13 - Isn Transmitted Data - York YCAS0130 Installation, Operation & Maintenance Manual

Ycas air-cooled liquid chillers style g
Hide thumbs Also See for YCAS0130:
Table of Contents

Advertisement

RECEIVED DATA (CONTROL DATA)
The microprocessor receives 8 data values from the
ISN. The fi rst 4 are analog values and the last 4 are
digital values. These 8 data values are used as con trol
pa ram e ters when in RE MOTE mode. When the unit is
in LO CAL mode, these 8 values are ignored. If the unit
re ceives no valid ISN trans mis sion for 5 min utes it will
re vert back to all local control values. Table 12 lists
the 4 control pa ram e ters. These values are found under
fea ture 54 on the ISN.
TABLE 12 – ISN RECEIVED DATA
ISN
CONTROL DATA
PAGE
P03
SETPOINT
P04
ISN Current Limit
P05
P06
P07
START/STOP COMMAND (0 = STOP, 1 = RUN)
P08
P09
P10
HISTORY BUFFER REQUEST
(0 = CURRENT DATA, 1 = LAST HISTORY DATA)
TABLE 13 – ISN TRANSMITTED DATA
ISN
Character
Page
P11
8-11
P12
12-15
P13
16-19
P14
20-23
P15
24-27
P16
28-31
P17
32-35
P18
36-39
P19
40-43
P20
44-47
P21
48-51
P22
52-55
P23
56-59
P24
60-63
P25
64-67
P26
68-71
YORK INTERNATIONAL

8.12 ISN CONTROL

Type
Analog
Leaving Chilled Liquid Temp
A
Return Chilled Liquid Temp
Mixed Chilled Liquid Temp (optional) - YCAS
A
Leaving Hot Liquid Temp - YCWS
Hot Liquid Temp - Heat Recovery
A
Sys 1 Suction Temperature
A
Sys 1 Discharge Temperature
A
Ambient Air Temperature
A
Sys 1 Oil Temperature
A
Sys 1 Oil Pressure
A
Sys 1 Suction Pressure
A
Sys 1 Discharge Pressure
A
Sys 1 % Full Load Amps
A
Sys 1 Total Run Hours
A
Sys 1 Total Number of Stats
A
Sys 1 Anti-Recycle Timer
A
Anti-Coincident Timer
A
Sys 2 Oil Temperature
TRANSMITTED DATA
After receiving a valid transmission from the ISN, the
unit will transmit either op er a tion al data or history buf-
f er data de pend ing on the "History Buffer Re quest" on
ISN PAGE 06. Data must be trans mit ted for every ISN
page un der fea ture 54. If there is no value to be sent to
a par tic u lar page, a zero will be sent. Tables 13 and 14
show the data val ues and page listings for this unit.
DXST Chiller Data
FORM 201.19-NM1 (204)
8
189