Dimensions - (Si Units) - York YCUL0016 User Manual

Air-cooled scroll condensing units
Table of Contents

Advertisement

Dimensions -
MODEL YCUL
0016
0026
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure
safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m; rear to wall –
2m; control panel to end wall – 1.2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one
adjacent wall may be higher than the unit.
78
YCUL0016 - YCUL0026 (SI)
���
���
���
��
�����������
������������������������
���������������������
������
����������
������������
���
�����
A
567
564
��
�������
���
�������
�������������
�������������������� �
�����������
���
����
��
YORK INTERNATIONAL