Dimensions; Ycul0045Sc (English) - York MILLENNIUM YCUL0045SC Installation Operation & Maintenance

Air-cooled condensing units hermetic scroll
Table of Contents

Advertisement

Installation
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance,
reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance
high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit
control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall
– 6'; control panel to end wall – 4'0; top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent
wall may be higher than the unit.
36
DIMENSIONS - YCUL0045SC (ENGLISH)
LD04417
YORK INTERNATIONAL