Specification - York YCUL0016 User Manual

Air-cooled scroll condensing units
Table of Contents

Advertisement

Specification

GENERAL
The 15 - 130 Ton (53 - 457 kW) YCUL Condensing Unit
Models are shipped complete from the factory ready for
field installation.
The unit is pressure-tested, evacuated and given a nitro-
gen holding charge and includes an initial oil charge (R-
22 or HFC-407C refringerant supplied by others). After
assembly, a operational test is performed to assure that
each control device operates correctly.
The unit structure is heavy-gauge, galvanized steel.
This galvanized steel is coated with baked-on powder
paint, which, when subjected to ASTM B117 500 hour,
salt spray testing, yields a minimum ASTM 1654 rating
of "6". Units are designed in accordance with NFPA 70
(National Electric Code), ASHRAE/ANSI 15 Safety code
for mechanical refrigeration, and are cETL listed. All units
are produced at an ISO 9000-registered facility.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll
compressors. The compressors incorporate a compli-
ant scroll design in both the axial and radial direction.
All rotating parts of the compressors are statically and
dynamically balanced. A large internal volume and oil
reservoir provides greater liquid tolerance. Compressor
crankcase heaters are also included for extra protection
against liquid migration.
CONDENSER
Coils – Fin and tube condenser coils of seamless, inter-
nally-enhanced, high-condensing-coefficient, corrosion
4
resistant copper tubes are arranged in staggered rows,
mechanically expanded into aluminum fins. Integral
subcooling is included. The design working pressure of
the coil is 450 PSIG (31 bar).
Fans – The condenser fans are composed of corrosion-
resistant aluminum hub and glass-fiber-reinforced
polypropylene composite blades molded into a low
noise airfoil section. The are designed for maximum
efficiency and are statically and dynamically balanced
for vibration free operation. They are directly driven
by independent motors, and positioned for vertical air
discharge. The fan guards are constructed of heavy-
gauge, rust-resistant, coated steel. All blades are
statically and dynamically balanced for vibration-free
operation.
Motors – The fan motors are Totally Enclosed Air-Over,
squirrel-cage type, current protected. They feature
ball bearings that are double-sealed and permanently
lubricated.
REFRIGERANT CIRCUIT
One (YCUL0016-0040) or two (YCUL0046-0130) inde-
pendent refrigerant circuits will be finished on each unit.
All unit piping will be copper, with brazed joints. The
liquid line will include a field connection shutoff valve with
charging port located on each condenser circuit. Suc-
tion line connections are provided on each refrigeration
circuit. A filter drier and sight glass are shipped loose
for field installation on each refrigerant circuit.
All expansion valves, liquid line solenoid valves, refriger-
ant, and refrigerant field piping are supplied by others.
YORK INTERNATIONAL

Advertisement

Table of Contents
loading

Table of Contents