TABLE 15: BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA
MODEL
POWER
DEE/
SUPPLY
DEG
208/230-1-60
208/230-3-60
036
460-3-60
3
575-3-60
208/230-1-60
208/230-3-60
048
460-3-60
3
575-3-60
208/230-1-60
208/230-3-60
060
460-3-60
3
575-3-60
1.
Rated in accordance with ARI Standard 110, utilization range "A".
2.
Dual element, time delay type.
3.
= DEE models only.
16
VOLTAGE
COMPRESSOR
1
LIMITATIONS
MIN
MAX
RLA
187
253
16.7
187
253
13.1
414
504
6.7
518
630
5.1
187
253
18.7
187
253
11.9
414
504
6.3
518
630
4.9
187
253
32.1
187
253
19.3
414
504
10.0
518
630
7.9
SUPPLY
CON.
AIR
FAN
BLOWER
MOTOR,
MOTOR,
LRA
FLA
FLA
87
2.3
7.6
110
2.3
5.3
54
1.4
2.6
44
1.4
2.0
135
2.3
8.6
130
2.3
5.2
64
1.4
2.6
52
1.4
2.0
169
2.3
8.6
123
2.3
6.0
62
1.4
3.0
50
1.4
2.4
036-21411-002-A-0204
MAX.
MAX.
MINIMUM
HACR
FUSE
CIRCUIT
BREAKER
2
SIZE
AMPACITY
SIZE,
AMPS
AMPS
30.1
45
23.9
35
12.4
20
9.8
15
42.6
60
26.3
40
14.3
20
11.4
15
51.0
80
32.4
50
16.9
25
13.7
20
Unitary Products Group
45
35
20
15
60
40
20
15
80
50
25
20