York PCG4A24 Technical Manual

York PCG4A24 Technical Manual

York pcg4*24 thru 60 single package air conditioner/gas

Advertisement

TECHNICAL GUIDE
SINGLE PACKAGE
AIR CONDITIONER/GAS
14 SEER – R-410A
2 THRU 5 NOMINAL TONS
50 - 125 MBH HEAT INPUT
MODELS: PCG4*24 THRU 60
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Years limited parts and compressor warranty
Lifetime gas heat exchanger.
* Extended warranty requires online registration within 90 days of purchase for
replacement or closing for new home purchase. See limited warranty certificate
in User's Information Manual for details.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
®
DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
• Operating Efficiency - All PCG4 model gas units provide a
minimum AFUE of 81.0% in heating and 14.0 SEER, 11.0
EER rating for cooling operation. All models meet current
California Low-Nox requirements of 40 ng/joule emission
level for Air Quality Management Districts.
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexi-
bility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibil-
ity with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor cur-
rents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance.
Equal size side supply and return duct connections allow
easy connection of ducts to match low crawl spaces without
transition pieces.
• Utility Connections Made Easy - Gas and electric utility
access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed elec-
trical disconnect switch must be installed.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, water-
tight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 62-
89 standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protec-
tion. The pre-treated galvanized steel provides a better paint-
to-steel bond, which resists corrosion and rust creep. Special
primer formulas and finish insure less fading when exposed
to sunlight, and provides superior corrosion resistance (1000
hour salt spray tested).
5005562-YTG-A-0215
Continued on next page.

Advertisement

Table of Contents
loading

Summary of Contents for York PCG4A24

  • Page 1 Convertible airflow design Visit us on the web at allows maximum field flexibility and minimum inventory. www.upgnet.com and www.york.com • Condensate Pan - A corrosion-resistant, long-lasting, water- Additional rating information can be found at: tight pan is positioned below the evaporator coil to collect www.ahridirectory.org...
  • Page 2 5005562-YTG-A-0215 • Full Perimeter Base Rails - The easily removable base rails • Protected Compressor - The compressor is internally pro- provide a solid foundation for the entire unit and protects the tected against high pressure and temperature. This is unit during shipment.
  • Page 3: Component Location

    5005562-YTG-A-0215 NOMENCLATURE 1. Model Family 5. Gas Heating Input BTU/Hr x 1000 PCG - packaged A/C with gas heat, 050 = 50,000 BTU/Hr. input, blank = electric heat PHG - packaged heat pump with gas heat, 6. Voltage-Phase-Frequency PCE - packaged A/C with electric heat, 2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60 PHE - packaged heat pump with electric heat 2.
  • Page 4 5005562-YTG-A-0215 ACCESSORIES • Rectangle to Round (Horizontal) Adapter (S1-1AK0109, S1-1AK0108) - Kit includes one supply and • Propane Conversion Kit (S1-1NP0702, S1-1NP0701) - Kit one return air rectangle to round duct adapter. Adapters are includes burner orifices, gas valve conversion and installa- preformed and designed to fit over current horizontal duct tion instructions necessary to field convert unit from natural openings on the base unit.
  • Page 5: Guide Specifications

    5005562-YTG-A-0215 GUIDE SPECIFICATIONS OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fan shall be of the direct-driven propeller type, GENERAL discharge air vertically, have aluminum blades riveted to Units shall be manufactured by Unitary Products in an ISO corrosion resistant steel spider bracket and shall be statically 9001 certified facility.
  • Page 6: Physical Data

    5005562-YTG-A-0215 PHYSICAL DATA MODELS COMPONENT PCG4A24 PCG4A30 PCG4A36 PCG4A42 PCG4B48 PCG4B60 NOMINAL TONNAGE AHRI Cooling Performance Gross Capacity @ AHRI A point (MBH) 23.7 30.1 37.2 43.5 47.7 55.0 AHRI net capacity (MBH) 22.8 29.0 34.6 41.0 45.5 52.5 11.0 11.0...
  • Page 7: Cooling Performance Data

    5005562-YTG-A-0215 COOLING PERFORMANCE DATA PACKAGED UNIT MODEL NO. PCG4A24 ID CFM 1000 CONDENSER ENTERING AIR IDDB TEMPERATURE IDWB T.C. 30.0 33.4 33.4 36.7 39.8 27.4 30.9 31.2 34.3 37.6 24.9 28.4 29.0 31.8 35.4 55 / 45 S.C. 30.0 28.6 23.8...
  • Page 8 5005562-YTG-A-0215 COOLING PERFORMANCE DATA PACKAGED UNIT MODEL NO. PCG4A36 ID CFM 1600 1400 1200 CONDENSER ENTERING AIR IDDB TEMPERATURE IDWB T.C. 45.3 48.1 48.0 53.1 54.6 42.2 46.3 46.2 51.3 53.5 39.2 44.6 44.5 49.5 52.4 55 / 45 S.C. 45.3 43.2 36.0...
  • Page 9 5005562-YTG-A-0215 COOLING PERFORMANCE DATA PACKAGED UNIT MODEL NO. PCG4B48 ID CFM 1600 1400 1200 CONDENSER ENTERING AIR IDDB TEMPERATURE IDWB T.C. 58.1 61.5 60.2 66.8 70.0 55.6 59.5 58.7 65.1 70.0 53.1 57.5 57.2 63.4 69.9 55 / 45 S.C. 57.1 53.6 44.4...
  • Page 10 5005562-YTG-A-0215 DIMENSIONS COIL GUARD HIGH VOLTAGE CONNECTION 7/8” HIGH VOLTAGE COMBUSTION AIR INTAKE CONNECTION 1-3/32” HEAT EXCHANGER ACCESS PANEL COMPRESSOR ACCESS PANEL EXHAUST HOOD CONDENSATE DRAIN BLOWER ACCESS LOW VOLTAGE CONNECTION CONTROL ACCESS PANEL GAS SUPPLY PANEL A0296-001 Unit Dimensions Dimensions Model 35-5/8...
  • Page 11: Indoor Blower Specifications

    5005562-YTG-A-0215 INDOOR BLOWER SPECIFICATIONS Motor Model EFF. Frame 24050 Variable 24075 Variable 30050 Variable 30075 Variable 36050 Variable 36075 Variable 36100 Variable 42075 Variable 42100 Variable 48065 Variable 48100 Variable 48125 Variable 60065 Variable 60100 Variable 60125 Variable SOUND PERFORMANCE Octave Band Centerline Frequency (Hz) Model Sound Rating...
  • Page 12: Weights And Dimensions

    5005562-YTG-A-0215 WEIGHTS & DIMENSIONS "D" CENTER OF GRAVITY COMPRESSOR "C" "A" FRONT OF UNIT "B" A0295-001-TG Weights and Dimensions Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) Model Shipping Operating 24050 24075 30050 30075 36050 36075 36100 42075 42100 48065 48100...
  • Page 13: Airflow Performance

    5005562-YTG-A-0215 AIRFLOW PERFORMANCE Airflow - Side Duct Application External Static Pressure (Inches WC) Model Motor Speed SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM Low (1) Low/Medium (2) 24050 Medium (3) Medium/High (4) High (5) 1148 1108 1071 1035 Low (1) Low/Medium (2) 24075 Medium (3)
  • Page 14 5005562-YTG-A-0215 Airflow - Side Duct Application (Continued) External Static Pressure (Inches WC) Model Motor Speed SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM Low (1) 1620 1564 1517 1466 1418 1360 1308 1206 Low/Medium (2) 1694 1630 1580 1530 1482 1430 1380 1292...
  • Page 15 5005562-YTG-A-0215 Airflow - Bottom Duct Application External Static Pressure (Inches WC) Model Motor Speed SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM Low (1) Low/Medium (2) 24050 Medium (3) Medium/High (4) 1024 High (5) 1204 1159 1121 1085 1051 1013 Low (1) Low/Medium (2) 1033...
  • Page 16 5005562-YTG-A-0215 Airflow - Bottom Duct Application (Continued) External Static Pressure (Inches WC) Model Motor Speed SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM Low (1) 1598 1548 1502 1454 1410 1362 1307 1251 Low/Medium (2) 1663 1612 1568 1522 1476 1422 1370 1297...
  • Page 17: Bottom Duct Dimensions (Inches)

    5005562-YTG-A-0215 BOTTOM DUCT DIMENSIONS (Inches) REAR DUCT DIMENSIONS (Inches) 15.6 A0299-001 A0298-001 Model Model 24, 30, 36, 42 21.5 4.94 4.34 24, 30, 36, 42 48, 60 13.5 3.56 48, 60 13.6 ROOF CURB ROOF CURB INSTALLATION INSTALLATION REAR DUCT BOTTOM DUCT SLAB ON GROUND...
  • Page 18 CONTROL WIRING TO INDOOR THERMOSTAT RETURN SUPPLY AIR DUCT AIR DUCT A0326-001 Subject to change without notice. Published in U.S.A. 5005562-YTG-A-0215 Copyright © 2015 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing York International Corp. 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Pcg4a30Pcg4b48Pcg4a36Pcg4b60Pcg4a42

Table of Contents