TABLE 8 - MOTOR AND DRIVE DATA w/Belt-Drive Blower
BLOWER
MODEL
RANGE
(RPM)
BCH 036
790 - 1120
BCH 048
790 - 1120
BCH 060
850 - 1220
*All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any
heating device.
TABLE 9 - ELECTRICAL DATA w/Direct-Drive Blower Motor
MODEL
POWER
BCH
SUPPLY
208/230-1-60
208/230-3-60
036
460-3-60
575-3-60
208/230-1-60
208/230-3-60
048
460-3-60
575-3-60
208/230-1-60
208/230-3-60
060
460-3-60
575-3-60
NOTES:
1. Rated in accordance wtih ARI Standard 110, utilizatin range "A".
2. Dual element, time delay type.
TABLE 10 - ELECTRICAL DATA
MODEL
POWER
BCH
SUPPLY
208/230-1-60
208/230-3-60
036
460-3-60
575-3-60
208/230-1-60
208/230-3-60
048
460-3-60
575-3-60
208/230-1-60
208/230-3-60
060
460-3-60
575-3-60
NOTES:
1. Utilization Range "A" in accordance with ARI Standard 110.
2. Dual element, time delay type.
Unitary Products Group
MOTOR*
FRAME
HP
RPM
SIZE
1-1/2
1725
56
1-1/2
1725
56
1-1/2
1725
56
VOLTAGE
LIMITATIONS
COMPRESSOR
(SEE NOTE 1)
MIN.
MAX.
RLA
187
253
19.0
187
253
11.9
414
504
5.9
518
630
4.8
187
253
23.1
187
253
14.7
414
504
7.7
518
630
6.4
187
253
32.1
187
253
19.3
414
504
10.0
518
630
7.9
w/Belt-Drive Blower Motor
VOLTAGE
LIMITATIONS
COMPRESSOR
(SEE NOTE 1)
MIN.
MAX.
RLA
187
253
19.0
187
253
11.9
414
504
5.9
518
630
4.8
187
253
23.1
187
253
14.7
414
504
7.7
518
630
6.4
187
253
32.1
187
253
19.3
414
504
10.0
518
630
7.9
ADJUSTABLE
MOTOR PULLEY
PITCH
SERVICE
BORE
DIA.
FACTOR
(in.)
(in.)
1.15
2.4 - 3.4
7/8
1.15
2.4 - 3.4
7/8
1.15
2.4 - 3.4
7/8
SUPPLY
OUTDOOR
AIR
FAN
BLOWER
MOTOR,
MOTOR,
FLA
LRA
FLA
105
1.7
4.4
85
1.7
4.4
42
1.0
2.2
34
1.0
2.2
105
2.3
5.0
130
2.3
5.0
64
1.4
2.2
52
1.4
2.2
169
2.3
6.6
137
2.3
6.6
62
1.4
3.3
50
1.4
3.3
SUPPLY
OUTDOOR
AIR
FAN
BLOWER
MOTOR,
MOTOR,
FLA
LRA
FLA
105
1.7
5.3
85
1.7
5.3
42
1.0
3.1
34
1.0
3.1
105
2.3
8.6
130
2.3
5.2
64
1.4
2.6
52
1.4
2.0
169
2.3
8.6
137
2.3
6.0
62
1.4
3.0
50
1.4
2.4
FIXED
BELT
BLOWER PULLEY
PITCH
PITCH
BORE
DIA.
LENGTH
(in.)
(in.)
(in.)
5.7
1
37.3
5.7
1
37.3
5.2
1
37.3
MAX.
MINIMUM
FUSE
CIRCUIT
SIZE,
AMPACITY
(SEE NOTE 2)
AMPS
29.9
45
21.0
30
10.6
15
10.2
15
36.1
50
25.7
40
13.2
20
11.6
15
49.0
80
33.0
50
17.2
25
14.6
20
MAX.
MINIMUM
FUSE
CIRCUIT
SIZE,
AMPACITY
(SEE NOTE 2)
AMPS
34.8
45
21.9
30
11.5
15
11.1
15
39.7
50
25.9
40
13.6
20
11.4
15
51.0
80
32.4
50
16.9
25
13.7
20
511.06-N5Y
DESIG-
NATION
A36
A36
A36
MAX.
HACR
BREAKER
SIZE,
AMPS
45
30
15
15
50
40
20
15
80
50
25
20
MAX.
HACR
BREAKER
SIZE,
AMPS
45
30
15
15
50
40
20
15
80
50
25
20
11