York SUNLINE 2000 Technical Manual
Hide thumbs Also See for SUNLINE 2000:

Advertisement

TECHNICAL GUIDE
SINGLE PACKAGE
GAS/ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
DM300 CONSTANT VOLUME
25 NOMINAL TONS
(WORLD 50 HZ)
1
This product was
manufactured in a
plant whose quality
system is certified/
registered as being
in conformity with
ISO9001.
®
SUNLINE
2000
TM
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
TM
Sunline
2000 series convertible package rooftop models have two
independent refrigerant circuits for efficient part load operation.
Although the units are primarily designed for curb mounting on a roof,
they can also be slab-mounted at ground level or set on steel beams
above a finished roof.
Cooling only, cooling with gas heat and cooling with electric heat
models are available with wide variety of factory-mounted options
and field-installed accessories to make them suitable for almost
every application.
All units are self-contained and assembled on full perimeter base
rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the fac-
tory to simplify the field installation and to provide years of depend-
able operation. Powder paint cabinets provide an exceptionally
durable finish with the 750 hour salt spray process per ASTM-B117
test standard.
All models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with power
exhaust are suitable for bottom duct connections only. For bottom
duct, remove the sheet metal panels from the supply and return air
openings through the base of the unit. For horizontal duct, replace
the supply and return air panels on the rear of the unit with a side
duct flange accessory.
All models are available with three different outdoor air damper
options:
Single enthalpy economizer
Single enthalpy economizer with power exhaust
Motorized outdoor air damper
The enthalpy system contains one sensor that monitors the outdoor
air and determines when the air is cool enough and dry enough to
provide "free" cooling.
The rainhood is painted to match the basic unit and must be field-
assembled before installing.
Power exhaust is not available as a field installed option.
036-21060-004-A-1102

Advertisement

Table of Contents
loading

Summary of Contents for York SUNLINE 2000

  • Page 1 036-21060-004-A-1102 DESCRIPTION ® Sunline 2000 series convertible package rooftop models have two independent refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
  • Page 2: Table Of Contents

    036-21060-004-A-1102 TABLE OF CONTENTS DESCRIPTION ......1 LIST OF TABLES Tbl. # Pg.
  • Page 3: Description

    036-21060-004-A-1102 “three times, you’re out” philosophy. The high and DESCRIPTION (Cont’d.) low-pressure switches and the freezestats must trip A fixed outdoor air intake assembly is shipped in the return air three times within two hours before the unit control compartment of all units ordered without an economizer or board will lock out the associated compressor.
  • Page 4: Field-Installed Accessories

    036-21060-004-A-1102 The rainhood is painted to match the basic unit and must thermostat, indicating that there is an abnormally high be field-assembled before installing. pressure drop across the filters. Factory installed option or field installed accessory. Power exhaust is not available as a field installed option.
  • Page 5 036-21060-004-A-1102 • SIDE DUCT FLANGES - One-inch flanges replace the • FLUE EXHAUST EXTENSION KIT - In locations with supply and return air panels on the rear of the unit to wind or weather conditions which may interfere with accommodate horizontal duct connections. These proper exhausting of furnace combustion products, this flanges can also be used individually for bottom supply/ kit can be installed to prevent the flue exhaust from...
  • Page 6: Product Nomenclature

    036-21060-004-A-1102 PRODUCT NOMENCLATURE 25T Sunline™ 2000 Model Number Nomenclature York Brand D M 300 N 24 A 7 A AA 1 Product Category D = Air Cond., Single Package Product Generation 1 = First Generation Product Identifier M = R-22 Standard Efficiency...
  • Page 7 036-21060-004-A-1102 PRODUCT NOMENCLATURE - Continued 25T Sunline™ 2000 Model Number Nomenclature Additional Options None Phase Monitor Coil Guard Dirty Filter Switch Phase Monitor & Coil Guard Phase Monitor & Dirty Filter Switch Coil Guard & Dirty Filter Switch Phase Monitor, Coil Guard, & Dirty Filter Switch Hinged Filter Door &...
  • Page 8 036-21060-004-A-1102 Additional Options CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap.
  • Page 9 036-21060-004-A-1102 Additional Options Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch Honeywell Excel 10 Controller, DFS, APS & Phase Monitor Honeywell Excel 10 Controller, DFS, APS & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS &...
  • Page 10 036-21060-004-A-1102 Additional Options Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils Novar ETC-3 Controller, DFS, APS, Technicoat Evap.
  • Page 11 036-21060-004-A-1102 Additional Options Technicoat Evaporator & Condenser Coils & Phase Monitor Technicoat Evaporator & Condenser Coils & Coil Guard Technicoat Evaporator & Condenser Coils & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch Technicoat Evaporator &...
  • Page 12: Capacity Ratings - Cooling

    036-21060-004-A-1102 TABLE 1: CAPACITY RATINGS - COOLING TOTAL OUTPUT KW/ MODEL TOTAL INPUTKW ELECTRIC HEAT NOMINAL CAPACITY KW 85.2 / 293 35.4 18, 36, 54, 72 TABLE 2: CAPACITY RATINGS - GAS HEAT MODEL TOTAL OUTPUT kW/ GAS HEAT RATINGS MBH TOTAL INPUT kW MBH OUTPUT DM300...
  • Page 13: Cooling Capacities - 25 Ton (Dm300) Cfm

    036-21060-004-A-1102 TABLE 4: COOLING CAPACITIES - 25 TON (DM300) CFM Temperature of Air on Condenser Coil OD Dry Bulb - 80.0 OD Dry Bulb - 95.0 OD Dry Bulb - 115.0 Air On Evaporator Coil Sensible Capacity Sensible *Capacity Sensible Capacity Total Power...
  • Page 14: Blower Performance - Dm300

    036-21060-004-A-1102 TABLE 5: BLOWER PERFORMANCE - DM300 - BOTTOM DUCT CONNECTIONS (COOLING APPLICATIONS) DM300 UNIT - DOWNFLOW DUCT CONNECTIONS 7500 CFM 8750 cfm 10000 cfm BLOWER PULLEY INPUT INPUT SPEED (rpm) TURNS OPEN ESP (iwg) OUTPUT (bhp) INPUT (kW) ESP (iwg) OUTPUT (bhp) ESP (iwg) OUTPUT (bhp) (kW)
  • Page 15 036-21060-004-A-1102 TABLE 6: STATIC RESISTANCES - EXTERNAL STATIC PRESSURE DROP RESISTANCE, Pa / iwg DESCRIPTION /s / CFM 3.78/ 8,000 4.25 / 9,000 4.72 / 10,000 WET COIL 25 / 0.1 25 / 0.1 25 / 0.1 GAS HEAT 25 / 0.1 25 / 0.1 25 / 0.1 18 KW...
  • Page 16: Physical Data

    036-21060-004-A-1102 TABLE 8: PHYSICAL DATA UNIT COMPONENT DESCRIPTION MODEL 300 DIA. X. WD. (mm) 457 x 381 CENTRIFUGAL BLOWER SUPPLY AIR BLOWER DIA. X. WD. (in.) 18 x 15 FAN MOTOR kW / HP 7.5 / 10 ROWS DEEP FINS PER 25mm (1 in.) 13.5 INDOOR COIL FACE AREA...
  • Page 17: Heat

    036-21060-004-A-1102 TABLE 10: ELECTRICAL DATA - UNITS WITH ELECTRIC HEAT HEATER OPTION MAXIMUM MINIMUM OVERCURRENT MODEL POWER CIRCUIT SUPPLY AMPACITY DEVICE MODEL STAGES AMPS (AMPS) (AMPS) E018 11.3 17.1 76.0 E036 22.6 34.3 76.0 380-3-50 E054 33.8 51.4 87.9 E072 45.1 68.6 109.4...
  • Page 18: Field Wiring - Dm Electric/Electric And

    036-21060-004-A-1102 THERMOSTAT CONTROL TERMINALS TERMINAL BLOCK Smoke Detector Jumper 24 VAC Class 2 TERMINALS ON A LIMITED NUMBER OF THERMOSTATS Second stage heating not required on single stage heating units. Second stage cooling not required on single stage cooling units. Jumper is required if there is no Smoke Detector circuit.
  • Page 19: Unit Dimensions - Dm Gas Heat

    036-21060-004-A-1102 Return Air Supply Air Condenser Air Outdoor Air Note: All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. OPENING USED FOR HOLE (DIA.) (mm / in.) Front 29 / 1-1/8" KO Control Wiring 19 / 3/4"...
  • Page 20: Accessory Side Supply And Return Air

    036-21060-004-A-1102 DUCT COVERS - Units are shipped with the bottom duct CONDENSER openings covered. An accessory flange kit is available for EVAPORATOR SECTION connecting side ducts. SECTION GAUGE LINE ACCESS For bottom duct applications: DOT PLUG (For pressure 1. Remove the side panels from the supply and return air 40-3/8"...
  • Page 21: Roof Curb Dimensions (All Models)

    036-21060-004-A-1102 * Supply and Return air (including duct support rails) as shown, are typical for Downflow duct applications For location of Sideflow duct applica- tions (on back of unit), refer to Unit Dimension details. FIGURE 7: ROOF CURB DIMENSIONS (ALL MODELS) FIGURE 9: UNIT CURB AND APPLICATIONS FIGURE 8: ROOF CURB BENEFITS Unitary Products Group...
  • Page 22: Typical Application

    036-21060-004-A-1102 FIGURE 10: TYPICAL APPLICATION FIGURE 11: TYPICAL ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN) Unitary Products Group...
  • Page 23 036-21060-004-A-1102 Unitary Products Group...
  • Page 24 Subject to change without notice. Printed in U.S.A. 036-21060-004-A-1102 Copyright © by Unitary Products Group 2002. All rights reserved. Supersedes: 036-21060-003-A-0802 Unitary 5005 Norman Products York Group Drive 73069...