LOCKOUT CONTROL

Any one of four conditions will put the system into a lock-out
condition during the heating or cooling mode:
1. The discharge line temperature reaches 255 F (215 F
reset) or,
2. The discharge pressure reaches 398 PSIG (310 PSIG
reset) or,
3. The suction line freezestat equals 26 F (38 F reset) or,
4. The low-pressure cut-out equals 7 PSIG (22 PSIG reset).
A lock-out will energize the emergency heat light on the
thermostat and the red LED light on the unit relay board. Turning
the thermostat switch to "Off" then back to "On", will reset the
system.
NOTICE TO OWNER:
If a lockout occurs, check for the following problems before
calling a serviceman:
1. Dirty filters.
2. Snow accumulation.
3. Leaf or debris blockage.
After eliminating the problem, attempt to restart the system as
follows:
turn the system switch on the thermostat to its "OFF" position
for 10 seconds.
turn it back to its original position.
If the unit doesn't start, call a serviceman.
NOTE: Models with an anti-recycle accessory will have a
5-minute delay before starting.

CHECKING SUPPLY AIR CFM

The speed of the supply air blower will depend on the required
CFM, the unit accessories and the static resistances of both
the supply and the return air duct systems. With this
information, the speed for the supply air blower can be
TABLE 11 - BELT-DRIVE SUPPLY AIR
MOTOR PULLEY ADJUSTMENT
BLOWER DRIVE RANGE (RPM)
TURNS
OPEN*
3 TON
5
780
4
842
3
904
2
966
1
1028
0
1090
*Pulley can be adjusted in half-turn increments.
determined from the blower performance and static resistance
data on Tables 4 through 7.
Knowing the required blower RPM and the blower motor HP ,
the speed setting for the supply air motor can be determined.
The setting (turns open) for the optional belt-drive supply air
pulley can be determined from Table 11.
Unitary Products Group
4 TON
5 TON
790
850
856
924
922
998
988
1072
1054
1246
1120
1220
OPTIONAL BELT-DRIVE BLOWER
All units with belt-drive blowers have single speed motors. The
variable pitch pulley on the blower motor can be adjusted to
obtain the desired supply air CFM. Refer to Table 8 for blower
motor drive data. The tension on the belts should be adjusted
as shown in Figure 9.
FIG. 9 - BELT ADJUSTMENT
Start the supply air blower motor. Adjust the resistances in both
the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has been
completed:
5
1. Remove the (two)
" dot plugs from the holes located on
16
the filter access panel side of the unit.
2. Insert at least 8" of 1/4 inch tubing into each of these holes
for sufficient penetration into the air flow on both sides of
the indoor coil.
NOTE: The tubes must be inserted and held in a position
perpendicular to the air flow so that velocity pressure
will not affect the static pressure readings.
3. Using an inclined manometer, determine the pressure drop
across a dry indoor coil. Since the moisture on an indoor
coil may vary greatly, measuring the pressure drop across
a wet coil under field conditions would be inaccurate. To
ensure a dry coil, the compressors should be de-energized
while the test is being run.
4. Knowing the pressure drop across a dry coil, the actual CFM
through the unit can be determined from the curve in Figure 10.
511.06-N5Y
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents