Physical Data; Supply Air Blower Perf . 3 - 6 Ton Direct-Drive 9 Motor & Drive Data-Belt-Drive Blower; Center Of Gravity - York SUNLINE 2000 D2CG 072 Installation Instructions Manual
NOTE: Filter racks are adapted for 1" or 2" thick filters.
CORNER C
BACK
CORNER D
7 8
44
"
Y
FIG 8 - CENTER OF GRAVITY
TABLE 6 - SUPPLY AIR PERFORMANCE - 3 Thru 6 Ton w/Direct-Drive Blower
GAS HEAT VALUES SHOWN @ 230/460/575 Volts
UNIT
MOTOR
0.20
SIZE
SPEED
CFM
HI
-
036
MED
1684
LOW
1487
HI
1996
048
MED
1804
LOW
1681
HI
2400
060
MED
2290
LOW
2150
072
HI
2461
NOTE: For 208 volts,multiply values by 0.95.
*Includes allowances for a wet evaporator coil, 1" filters and gas fired heat exchangers. Refer to Table 8 for static resistance values on applications other than side duct airflows.
TABLE 7 - MOTOR AND DRIVE DATA - Belt-Drive Blower
BLOWER
UNIT
RANGE
SIZE
(RPM)
036
780 - 1090
048
790 - 1120
060
850 - 1220
072
900 - 1250
*
All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any