Electrical Data; Electrical Data (Cooling/Electric Heat) - York D2EB030 Technical Manual

Affinity series single package cooling units 2.5 thru 5 ton 8.8 - 9.4 eer export only
Hide thumbs Also See for D2EB030:
Table of Contents

Advertisement

TABLE 10: ELECTRICAL DATA
VOLTAGE
LIMITATIONS
MODEL
POWER
DEB
SUPPLY
MIN.
30
208/230-1-60
187
36
208/230-1-60
187
42
208/230-1-60
187
48
208/230-1-60
187
60
208/230-1-60
187
36
208/230-3-60
187
42
208/230-3-60
187
48
208/230-3-60
187
60
208/230-3-60
187
36
460-3-60
414
42
460-3-60
414
48
460-3-60
414
60
460-3-60
414
36
575-3-60
518
42
575-3-60
518
48
575-3-60
518
60
575-3-60
518
1. Rated in accordance with ARI Standard 110, utilization range "A".
2. Dual element, time delay type.
NOMINAL VOLTAGE VOLTAGE
ELECTRIC HEAT
240
CORRECTION
FACTORS
480
600
TABLE 11: ELECTRICAL DATA (COOLING / ELECTRIC HEAT)
COMPRESSOR
MODEL
POWER
DEB
SUPPLY
RLA
030
208/230-1-60
12.0
036
208/230-1-60
17.3
042
208/230-1-60
15.5
048
208/230-1-60
24.4
060
208/230-1-60
38.0
036
208/230-3-60
10.9
12
COMPRESSOR COND.
1
MOTOR,
MAX.
RLA
LRA
253
14.7
73
253
17.3
94
253
15.5
86
253
24.4
140
253
28.9
165
253
10.9
78.0
253
11.5
88.0
253
14.1
105.0
253
16.0
125.0
504
5.8
40.0
504
5.8
42.0
504
7.1
55.0
504
8.0
67.0
630
4.5
32.0
630
5.8
44.0
630
5.6
44.0
630
6.4
50.0
KW CAP.
MULTIPLIER
208
230
460
575
SUPPLY
COND. FAN
AIR
MOTORS
BLOWER
MOTOR
LRA
FLA
FLA
2NH04500506
2NH04500706
73.0
1.1
2.6
2NH04501006
2NH04501506
2NH04501006
94.0
1.1
3.5
2NH04501506
2NH04500506
2NH04500706
86.0
1.1
3.5
2NH04501006
2NH04501506
2NH04501006
2NH04501506
140.0
1.3
4.0
2NH04502006
2NH04502506
2NH04501006
2NH04501506
165.0
1.3
7.0
2NH04502006
2NH04502506
2NH04501025
78.0
1.1
3.5
2NH04501525
SUPPLY
AIR
MINIMUM
FAN
BLOWER
CIRCUIT
MOTOR
AMPACITY
FLA
FLA
1.1
2.6
22.1
1.1
3.5
26.2
1.1
3.5
23.9
1.3
4.0
35.8
1.3
4.0
44.4
1.1
3.5
18.2
1.1
3.5
19.0
0.7
4.0
22.3
1.3
7.0
28.3
0.6
1.8
9.6
0.6
1.8
9.7
0.6
2.0
11.5
0.7
3.5
14.2
0.4
1.5
7.6
0.4
1.5
9.1
0.6
1.6
9.3
0.6
2.8
11.4
.75
.92
.92
.92
ELECTRIC HEAT ACCESSORY
MODEL NO. STAGE
KW
1
3.8/5.0*
2
5.6/7.5*
2
7.5/10.0*
2
11.3/15.0*
2
7.5/10.0*
2
11.3/15.0*
1
3.8/5.0*
2
5.6/7.5*
2
7.5/10.0*
2
11.3/15.0*
2
7.5/10.0*
2
11.3/15.0*
2
15.0/20.0*
2
18.8/25.0*
2
7.5/10.0*
2
11.3/15.0*
2
15.0/20.0*
2
18.8/25.0*
1
7.5/10.0*
1
11.3/15.0*
MAX.
MAX.
HACR
UNIT
2
FUSE
BREAKER
POWER
SIZE,
SIZE,
FACTOR
AMPS
AMPS
30
30
0.96
35
35
0.96
30
30
0.96
45
45
0.96
60
60
0.96
25
25
0.96
25
25
0.96
30
30
0.96
40
40
0.96
15
15
0.96
15
15
0.96
15
15
0.96
20
20
0.96
15
15
0.96
15
15
0.96
15
15
0.96
15
15
0.96
MAX FUSE/
MCA
SIZE
(AMPS)
(AMPS)
TOTAL AMPS
18.1/20.8
25.8/29.3
30/30
27.3/31.3
37.1/42.3
40/45
36.1/41.7
48.4/55.3
50/60
54.2/62.5
71.0/81.4
80/90
36.1/41.7
49.5/56.5
50/60
54.2/62.5
72.1/82.5
80/90
18.1/20.8
26.9/30.4
35/35
27.1/31.3
38.2/43.4
40/45
36.1/41.7
49.5/56.5
50/60
54.2/62.5
72.1/82.5
80/90
36.1/41.7
50.1/57.1
60/60
54.2/62.5
72.1/83.1
80/90
72.2/83.3
95.3/109.2
100/110
90.3/104.2
117.8/135.2
125/150
36.1/41.7
53.9/60.8
70/70
54.2/62.5
76.5/86.9
80/90
72.2/83.3
99.0/112.9
100/125
90.3/104.2
121.6/139.0
125/150
20.8/24.1
30.4/34.4
35/35
31.3/36.1
43.5/49.5
45/50
Johnson Controls Unitary Products
360101-XTG-B-0508
TRANSFORMER
SIZE (VA)
40
40
40
40
40
75
75
75
75
75
75
75
75
75
75
75
75
2
MAX HACR
1
BREAKER SIZE
30/30
40/45
50/60
80/90
50/60
80/90
35/35
40/45
50/60
80/90
60/60
80/90
100/110
125/150
70/70
80/90
100/125
125/150
35/35
45/50