Electrical Data - York ZKT06 Installation Manual

Table of Contents

Advertisement

5121835-TIM-J-1118
Table 10: Electrical data
ZKT06 through T12 standard motor - without powered convenience outlet
Compressors
(each)
Size
Volt
(tons)
RLA LRA
MCC
208
13.5
88.0
21.1
230
13.5
88.0
21.1
T06
(6.5)
460
6.0
44.0
9.3
575
4.9
34.0
7.7
208
13.1
83.1
20.5
230
13.1
83.1
20.5
T07
(7.5)
460
6.1
41.0
9.5
575
4.4
33.0
6.8
208
14.5
98.0
22.6
230
14.5
98.0
22.6
T08
(8.5)
460
6.3
55.0
9.9
575
6.0
41.0
9.4
20
OD fan
Supply
Pwr
Pwr exh
motors
blower
conv
motor
(each)
motor
outlet
FLA
FLA
FLA
FLA
2.1
5.2
5.5
0.0
2.1
5.2
5.5
0.0
1.3
2.6
2.2
0.0
0.7
2.0
1.8
0.0
2.1
5.2
5.5
0.0
2.1
5.2
5.5
0.0
1.3
2.6
2.2
0.0
0.7
2.0
1.8
0.0
2.1
6.8
5.5
0.0
2.1
6.8
5.5
0.0
1.3
3.4
2.2
0.0
0.7
2.4
1.8
0.0
Electric heat option
Model
kW
Stages
Amps
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
None
-
-
-
E09
6.8
1
18.9
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
None
-
-
-
E09
9.0
1
21.7
E18
18.0
2
43.3
E24
24.0
2
57.7
E36
34.0
2
81.8
None
-
-
-
E09
9.0
1
10.8
E18
18.0
2
21.7
E24
24.0
2
28.9
E36
34.0
2
40.9
None
-
-
-
E09
9.0
1
8.7
E18
18.0
2
17.3
E24
24.0
2
23.1
E36
34.0
2
32.7
2
Max fuse
/
1
MCA
1
3
MCA
breaker
with pwr
(amps)
size
exh (amps)
(amps)
39.8
45.3
50
39.8
45.3
50
53.3
60.2
60
69.0
75.8
70
95.0
101.9
100
39.8
45.3
50
39.8
45.3
50
60.6
67.5
70
78.7
85.5
80
108.7
115.6
110
18.6
20.8
20
18.6
20.8
20
30.3
33.1
35
39.3
42.1
40
54.4
57.1
60
14.3
16.1
15
14.3
16.1
15
24.2
26.4
25
31.4
33.6
35
43.4
45.6
45
38.9
44.4
50
38.9
44.4
50
53.3
60.2
60
69.0
75.8
70
95.0
101.9
100
38.9
44.4
50
38.9
44.4
50
60.6
67.5
70
78.7
85.5
80
108.7
115.6
110
18.8
21.0
20
18.8
21.0
20
30.3
33.1
35
39.3
42.1
40
54.4
57.1
60
13.2
15.0
15
13.3
15.6
15
24.2
26.4
25
31.4
33.6
35
43.4
45.6
45
43.6
49.1
50
43.6
49.1
50
55.3
62.2
60
71.0
77.8
80
97.0
103.9
100
43.6
49.1
50
43.6
49.1
50
62.6
69.5
70
80.7
87.5
90
110.7
117.6
125
20.1
22.3
25
20.1
22.3
25
31.3
34.1
35
40.3
43.1
45
55.4
58.1
60
17.2
19.0
20
17.2
19.0
20
24.7
26.9
25
31.9
34.1
35
43.9
46.1
45
Johnson Controls Ducted Systems
2
Max fuse
/
3
breaker
size with
pwr exh
(amps)
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
15
20
30
35
50
60
60
70
80
110
60
60
70
90
125
25
25
35
45
60
25
25
30
35
50