Electrical Data - York J ZJ Series Instruction Manual

Hide thumbs Also See for J ZJ Series:
Table of Contents

Advertisement

5803641-JIM-B-0620
Table 9: Electrical Data
JA3 thru A5ZJ Standard Indoor Blower - Without Powered Convenience Outlet
Compressors
(each)
Size
Volt
(Tons)
RLA LRA
MCC
208
9.2
70
13
230
9.2
70
13
JA3
(3)
460
4
31
6
575
3.5
27
5
208
13.8
83.1
22
230
13.8
83.1
22
JA4
(4)
460
6.2
41
10
575
4.9
33
8
208
12.4
93
19
230
12.4
93
19
JA5
(5)
460
6
60
9
575
4.7
41
7
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
20
OD Fan
Supply
Pwr
Pwr
Motors
Blower
Exh
Conv
(each)
Motor
Motor
Outlet
FLA
FLA
FLA
FLA
2.1
5.2
5.5
2.1
5.2
5.5
1.26
2.6
2.2
0.66
2
1.8
2.1
5.2
5.5
2.1
5.2
5.5
1.26
2.6
2.2
0.66
2
1.8
2.1
5.2
5.5
2.1
5.2
5.5
1.26
2.6
2.2
0.66
2
1.8
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
-
E03
2.3
1
6.4
E06
4.5
1
12.5
E08
6.8
1
18.9
E15
11.3
2
31.4
None
-
-
-
E03
3
1
7.2
E06
6
1
14.4
E08
9
1
21.7
E15
15
2
36.1
None
-
-
-
E03
3
1
3.6
E06
6
1
7.2
E08
9
1
10.8
E15
15
2
18
None
-
-
-
E08
9
1
8.7
E15
15
2
14.4
None
-
-
-
E06
4.5
1
12.5
E08
6.8
1
18.9
E15
11.3
2
31.4
E20
15
2
41.6
None
-
-
-
E06
6
1
14.4
E08
9
1
21.7
E15
15
2
36.1
E20
20
2
48.1
None
-
-
-
E06
6
1
7.2
E08
9
1
10.8
E15
15
2
18
E20
20
2
24.1
None
-
-
-
E08
9
1
8.7
E15
15
2
14.4
E20
20
2
19.2
None
-
-
-
E06
4.5
1
12.5
E08
6.8
1
18.9
E15
11.3
2
31.4
E20
15
2
41.6
E23
18
2
50
None
-
-
-
E06
6
1
14.4
E08
9
1
21.7
E15
15
2
36.1
E20
20
2
48.1
E23
24
2
57.7
None
-
-
-
E06
6
1
7.2
E08
9
1
10.8
E15
15
2
18
E20
20
2
24.1
E23
24
2
28.9
None
-
-
-
E08
9
1
8.7
E15
15
2
14.4
E20
20
2
19.2
E23
24
2
23.1
1
2
MCA
Max Fuse
1
3
MCA
w/Pwr
Breaker
(Amps)
Exh
Size
(Amps)
(Amps)
18.8
24.3
25
18.8
24.3
25
22.1
29
25
30.1
37
35
45.8
52.6
50
18.8
24.3
25
18.8
24.3
25
24.5
31.4
25
33.6
40.5
35
51.6
58.5
60
8.9
11.1
15
8.9
11.1
15
12.3
15
15
16.8
19.5
20
25.8
28.5
30
7.1
8.9
15
13.4
15.6
15
20.5
22.8
25
24.6
30.1
35
24.6
30.1
35
30.1
37
35
45.8
52.6
50
58.5
65.4
60
24.6
30.1
35
24.6
31.4
35
33.6
40.5
35
51.6
58.5
60
66.6
73.5
70
11.7
13.9
15
12.3
15
15
16.8
19.5
20
25.8
28.5
30
33.4
36.1
35
8.8
10.6
15
13.4
15.6
15
20.5
22.8
25
26.5
28.8
30
24.9
30.4
35
24.9
30.4
35
30.1
37
35
45.8
52.6
50
58.5
65.4
60
69
75.9
70
24.9
30.4
35
24.9
31.4
35
33.6
40.5
35
51.6
58.5
60
66.6
73.5
70
78.6
85.5
80
12.6
14.8
15
12.6
15
15
16.8
19.5
20
25.8
28.5
30
33.4
36.1
35
39.4
42.1
40
9.2
11
15
13.4
15.6
15
20.5
22.8
25
26.5
28.8
30
31.4
33.6
35
Johnson Controls Ducted Systems
2
Max Fuse
/
/
3
Breaker
Size w/
Pwr Exh
(Amps)
30
30
30
40
60
30
30
35
45
60
15
15
15
20
30
15
20
25
40
40
40
60
70
40
40
45
60
80
20
20
20
30
40
15
20
25
30
40
40
40
60
70
80
40
40
45
60
80
90
20
20
20
30
40
45
15
20
25
30
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ja3zjJa4zjJa5zj

Table of Contents