TECHNICAL GUIDE
SUNLINE ULTRA™
SINGLE PACKAGE AIR-COOLED
AIR CONDITIONERS
3, 4 AND 5 NOMINAL TON
D1HE/D1HG036, 048 and D2HE/D2HG060
12.2 THROUGH 13.2 SEER
DHG MODEL SHOWN
®
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
FLEXIBLE LIGHT COMMERCIAL UNIT
GENERAL
YORK's Sunline Ultra package units are designed to han-
dle applications ranging from residential to light commer-
cial and any in between. The Sunline Ultra is a unit that
gives you the flexibility and choices you need in today's
market.
FEATURING
COOLING ONLY UNITS
COOLING/GAS HEATING UNITS (NATURAL GAS
OR PROPANE)
LOW PROFILE
QUIET OPERATION
COMMON FOOTPRINT
OPTIONAL FACTORY INSTALLED ECONOMIZERS
OPTIONAL SLIDE IN MOTORIZED DAMPERS
OPTIONAL SLIDE IN ECONOMIZERS
OPTIONAL ELECTRIC HEATERS
OPTIONAL PROPANE CONVERSION KIT
OPTIONAL HIGH ALTITUDE GAS OR PROPANE KIT
OPTIONAL NOx KIT
MODULAR ELECTRICAL CONNECTIONS FOR
EASY OF INSTALLATION
FULL PERIMETER BASE RAILS
TROUBLE FREE UTILITY CONNECTIONS
1" OR 2" THROWAWAY FILTERS
5 YEAR LIMITED WARRANTY ON COMPRESSOR
10 YEAR LIMITED WARRANT ON GAS-FIRED HEAT
EXCHANGERS
1 YEAR LIMITED WARRANTY ON ALL REPLACE-
MENT PARTS
036-21216-003-A-0204

Advertisement

Table of Contents
loading

Summary of Contents for York D1HE/D1HG036

  • Page 1 ® FLEXIBLE LIGHT COMMERCIAL UNIT GENERAL YORK’s Sunline Ultra package units are designed to han- dle applications ranging from residential to light commer- cial and any in between. The Sunline Ultra is a unit that gives you the flexibility and choices you need in today’s market.
  • Page 2: Table Of Contents

    DESCRIPTION ......3 FEATURES ....... . 3 FACTORY-INSTALLED OPTION .
  • Page 3: Description

    036-21216-003-A-0204 DESCRIPTION YORK Sunline Ultra units are high efficiency, convertible, sin- gle package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential, light commercial and commercial applications.
  • Page 4: Factory-Installed Option

    troubleshooting without affecting the normal system operat- ing pressures. AIR FILTERS - Units are shipped with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications FACTORY-INSTALLED OPTION ECONOMIZERS: Units equipped with a factory-installed economizer option have dampers that are positioned by a spring return, fully modulating damper actuator and are capa- ble of introducing up to 100% outdoor air.
  • Page 5: Sunline Ultra Cutaway

    036-21216-003-A-0204 WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. FIGURE 1 - SUNLINE ULTRA CUTAWAY (Model DHG gas heating) TABLE 1: CAPACITY RATING - COOLING / ELECTRIC HEAT ARI RATINGS COOLING CAPACITY MODEL 80 / 67-95°F SEER DHE036...
  • Page 6: Capacity Ratings - Cooling / Gas Heating

    TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING ARI RATINGS COOLING CAPACITY MODEL 80 / 67-95°F SEER DHG036N040 42.5 12.25 11.1 DHG036N079 42.5 12.25 11.1 DHG048N060 46.5 13.20 11.40 DHG048N099 DHG060N079 57.0 12.20 10.60 DHG060N099 Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240. Rated in accordance with ARI Standard 110, utilization range “A”.
  • Page 7: Cooling Capacities - Models

    036-21216-003-A-0204 TABLE 5: COOLING CAPACITIES - MODELS DHE/DHG 036 - AIR ON EVAPORATOR COIL TOTAL CAP. °F 55.2 49.1 1500 44.7 42.4 55.2 49.1 1350 44.7 42.4 51.9 46.1 1200 42.0 39.8 49.4 43.9 1050 40.0 37.9 46.9 41.7 38.0 36.0 AIR ON EVAPORATOR...
  • Page 8: Cooling Capacities - Models

    TABLE 6: COOLING CAPACITIES - MODELS DHE/DHG 036 - AIR ON EVAPORATOR COIL TOTAL CAP. °F 1500 47.6 42.5 38.0 37.4 1350 46.5 41.6 37.1 36.5 1200 45.4 40.6 36.2 35.7 1050 43.2 38.7 34.5 34.0 41.1 36.7 32.8 32.3 AIR ON EVAPORATOR COIL...
  • Page 9: Cooling Capacities - Models Dhe/Dhg048

    036-21216-003-A-0204 TABLE 7: COOLING CAPACITIES - MODELS DHE/DHG048 AIR ON EVAPORATOR COIL TOTAL POWER CAP. INPUT °F 2000 1800 1600 1400 1200 AIR ON EVAPORATOR COIL TOTAL POWER CAP. INPUT °F 2000 1800 1600 1400 1200 These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit These ratings include the compressor and the condenser fan motors but not the supply air blower motor.
  • Page 10: Cooling Capacities - Models Dhe/Dhg060

    TABLE 8: COOLING CAPACITIES - MODELS DHE/DHG060 AIR ON EVAPORATOR COIL TOTAL POWER CAP. INPUT °F 2500 2250 2000 1750 1500 AIR ON EVAPORATOR COIL TOTAL POWER CAP. INPUT °F 2500 2250 2000 1750 1500 These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit These ratings include the compressor and the condenser fan motors but not the supply air blower motor.
  • Page 11: Supply Air Blower Performance

    036-21216-003-A-0204 TABLE 9: SUPPLY AIR BLOWER PERFORMANCE -DHE/DHG036 MODEL FLOW 0.20 DHE/DHG RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1900 1800 1700 1600 1500 1400 1300 1200 MODEL FLOW 0.90 DHE/DHG RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270...
  • Page 12: Supply Air Blower Performance

    TABLE 10: SUPPLY AIR BLOWER PERFORMANCE DHE/DHG048 UNIT SIZE FLOW 0.20 0.30 (MBH Watts 2000 1900 1800 1700 1600 1500 1400 1300 1200 UNIT SIZE FLOW 0.90 1.00 (MBH Watts 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1700 1040 1075...
  • Page 13: Supply Air Blower Performance

    036-21216-003-A-0204 TABLE 11: SUPPLY AIR BLOWER PERFORMANCE DHE/DHG060 UNIT AIR FLOW SIZE 0.20 (MBH) Watts 2500 1059 1560 1077 2400 1032 1405 1054 2300 1005 1260 1024 2200 1160 1002 2100 1060 2000 1900 1800 1700 1600 1500 UNIT AIR FLOW SIZE 0.90 (MBH)
  • Page 14: Dhe/Dhg036

    TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER BLOWER MODEL RANGE (RPM) DHE/DHG 036 780 - 1120 1,725 DHE/DHG048 790 - 1,120 1,725 DHE/DHG060 850 - 1,220 1,725 All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device TABLE 14: ELECTRICAL DATA - BASIC UNIT VOLTAGE...
  • Page 15: Electrical Data - Cooling/Electric Heat Dhe036 & 048

    036-21216-003-A-0204 TABLE 15: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE036 & 048 HEATER MODEL POWER ACCESSORY SUPPLY MODEL NUMBER 2CE04500525 2CE04500725 208-3-60 2CE04501025 2CE04501525 2CE04502025 2CE04500525 2CE04500725 230-3-60 2CE04501025 2CE04501525 2CE04502025 2CE04500746 2CE04501046 460-3-60 2CE04501546 2CE04502046 2CE04500525 2CE04500725 208-3-60 2CE04501025 2CE04501525 2CE04502025 2CE04500525 2CE04500725...
  • Page 16: Field Power Wiring

    TABLE 18: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE060 HEATER MODEL POWER ACCESSORY SUPPLY MODEL NUMBER 2CE04500525 2CE04500725 2CE04501025 208-3-60 2CE04501525 2CE04502025 2CE04503025 2CE04500525 2CE04500725 2CE04501025 230-3-60 2CE04501525 2CE04502025 2CE04503025 2CE04500746 2CE04501046 460-3-60 2CE04501546 2CE04502046 2CE04503046 Dual element, time delay type. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
  • Page 17: Control Wiring Single Stage

    036-21216-003-A-0204 C O O L I N G / H E A T I N G ( E L E C T R O N I C T H E R M O S T A T ) S I N G L E S T A G E T H E R M O S T A T U N I T T E R M I N A L T E R M I N A L S...
  • Page 18: Dhe Unit Dimensions

    FIGURE 7 - DHE UNIT DIMENSIONS TABLE 19: UTILITIES ENTRY DATA KNOCKOUT HOLE SIZE (DIA.) 7/8” 2” 1-5/8” 1-1/2” Knockouts in the bottom of the unit can be located by the slice in the insulation DO NOT remove the 2” knockout ring. USED FOR Control Wiring (Side or Bottom)
  • Page 19: Unit Dimensions Dhg Unit

    036-21216-003-A-0204 FIGURE 9 - UNIT DIMENSIONS DHG UNIT TABLE 20: CLEARANCES DHE UNITS FRONT DHG UNITS BACK LEFT SIDE (Filter Access) RIGHT SIDE (Cond. Coil) BELOW UNIT ABOVE UNIT Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. Units must be installed outdoors.
  • Page 20: Rear Dimensions Of Dhe And Dhg Units 3, 4 & 5 Ton Units

    FIGURE 10 - REAR DIMENSIONS OF DHE AND DHG UNITS 3, 4 & 5 TON UNITS Duct covers - units are shipped with all air duct openings cov- ered. For side duct applications: • Remove and discard the supply and return air duct covers.
  • Page 21: Detail "B" Unit With Fixed Outdoor Air/Motorized Damper Rainhood

    036-21216-003-A-0204 FIGURE 12 - DETAIL “B” UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD 3.69" BASE RAIL 3.56" FIGURE 13 - UNIT AND CURB APPLICATION Unitary Products Group...
  • Page 22: Roof Curb Dimensions Dhe/Dhg

    FIGURE 14 - ROOF CURB DIMENSIONS DHE/DHG 3, 4 & 5 TON FIGURE 15 - CENTER OF GRAVITY AND CORNER WEIGHTS TABLE 21: BASIC UNIT WEIGHT UNIT CORNER WEIGHTS UNIT WEIGHT “A” “B” (lbs.) DHG036 DHG048 DHG060 DHE036 DHE048 DHE060 Weight = Unit with economizer and high heat.
  • Page 23 036-21216-003-A-0204 FIGURE 16 - TYPICAL APPLICATIONS FIGURE 17 - TYPICAL ROOF-TOP INSTALLATION (DHG) Unitary Products Group ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION...
  • Page 24: Mechanical Specifications

    MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION Single packaged outdoor mounted rooftop with built in field convertible duct connections for vertical discharge/return air or horizontal discharge/return air configuration. Cooling per- formance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA Certified to ANSIZ21.47 stan- dards and UL 1995/CAN/CSA No.
  • Page 25 036-21216-003-A-0204 Unit shall incorporate a lock-out circuit which pro- vides reset capability at the space thermostat, should any of the following standard safety devices trip and shut off compressor: I.AUTO RESET - Compressor over temperature, over current. II.Loss-of-charge/low-pressure switch. III.Freeze-protection thermostat, evaporator coil. IV.High-pressure switch.
  • Page 26 036-21216-003-A-0204 Unitary Products Group...
  • Page 27 036-21216-003-A-0204 Unitary Products Group...
  • Page 28 Subject to change without notice. Printed in U.S.A. Copyright © 2004 by Unitary Products Group. All rights reserved. Unitary Products Group Supersedes: 036-21216-002 (0601) 5005 York Drive 036-21216-003-A-0204 Norman 73069...