Controller Resetting Procedure

(Following Fault Shutdown)

Use the following procedure to restart the generator set
after a fault shutdown. Refer to Resetting Emergency
Stop Switches in this section to reset the generator set
after an emergency stop.
1. Place controller alarm horn switch in the SILENCE
position. A/V annunciator alarm horn and lamp are
activated, if equipped. Place A/V annunciator
alarm switch in SILENCE position to stop alarm
horn. A/V annunciator lamp stays lit. (The A/V
alarm uses one lamp to indicate a fault shutdown;
the appropriate fault lamp lights on the remote
annunciator to indicate a fault condition.)
2. Disconnect generator set from load with line circuit
breaker or automatic transfer switch.
3. Correct cause of fault shutdown. See Safety
Precautions section of this manual before
proceeding.
4. Place the generator set master switch in the
OFF/RESET position and then in the RUN position
to start generator set. A/V annunciator alarm horn
sounds and lamp, if equipped goes out.
5. Verify that cause of shutdown has been corrected
by test operating generator set.
6. Reconnect generator set to load via line circuit
breaker or automatic transfer switch.
7. Place generator set master switch in AUTO
position for start-up by remote transfer switch or
remote start/stop switch. Place A/V annunciator
alarm switch, if equipped in NORMAL position.
TP-5631 7/96
NOTE
Place generator set master switch in the AUTO
position before silencing alarm horn.
8. Place controller alarm horn switch in the NORMAL
position.

Resetting Emergency Stop Switches

Use the following procedure to restart the generator set
after shutdown by the remote emergency stop switch.
Refer to the Controller Resetting procedure in this
section to restart the generator set following a fault
shutdown.
1. Determine cause of emergency stop and correct
problem(s).
2. Replace glass piece in remote emergency stop
switch to reset switch, if equipped.
NOTE
The controller auxiliary lamp lights if the generator
set master switch is in the RUN or AUTO position
during the resetting procedure.
3. Toggle the generator set master switch to
OFF/RESET and then to RUN or AUTO to restart
generator set. The generator set does not crank
until the resetting procedure is completed.
Operation 2-9