An optional line circuit breaker (sized for generator
output) is available to protect the generator from
damage because of overload or short circuits. If the
circuit breaker trips, reduce the load and switch the
breakers back to the ON position. With the breaker in
the OFF position, the generator set runs but there is no
output voltage.
NOTE
If the generator set circuit breaker trips repeatedly, see
Section 4. Troubleshooting for possible causes.
The controller circuitry is protected by a replaceable
10-amp fuse. Check the controller fuse if the generator
set will not crank and the battery and/or connections
appear correct. Replace fuse. If fuse blows again, see
Section 4. Troubleshooting for possible causes.

Voltage Regulator Fuse

A replaceable 10-amp fuse protects the voltage
regulator circuitry. The generator set shuts down if this
fuse is blown.
Typically with this condition, the
generator set starts and then shuts down in 8 seconds.
If this fuse is replaced and then blows again, see Section
4, Troubleshooting for possible causes. Location of the
voltage regulator fuse for 10-18 kW is shown in Figure
2-2. See Figure 2-7 for 6.5 kW.
2-12 Operation

Circuit Protection (relay controller)

1
1. 10-amp fuse
Figure 2-6. 10-18 kW Voltage Regulator
Fuse Location
1. 10-amp fuse
Figure 2-7. 6.5 kW Voltage Regulator
Fuse Location
TP-5631-2
1
ADV-5815C-A
TP-5631 7/96